Laserfiche WebLink
SAN �� IIIN Environmental Health Department <br /> .PCOUNTY <br /> Greotness grows here. <br /> r. <br /> Corrective Action Statement <br /> RE: May 13, 2021, Underground Storage Tank inspection report <br /> For each violation listed below, indicate if the violation has been corrected or will be corrected by a certain date. <br /> Also, describe what was done to correct the violation in the space provided below each violation. Submit this <br /> completed form with the Return to Compliance Certification within 30 days of inspection. If you have any questions, <br /> please contact Lydia Baker at(209)616-3046 or(baker@sjgov.org. <br /> SAFEWAY FUEL CENTER#2707, 6425 N PACIFIC AVE, CERS ID: 10156811, PR0231211 <br /> Violation#317-Failure of the line leak detector to detect a 3.0 gph leak at 10 psi and restrict or shut off flow. <br /> $] This violation was corrected ❑This violation will be corrected by(date): <br /> ❑ Supporting documents included <br /> Describe actions taken or will be taken to correct violation: This was corrected the day of the monitor <br /> cert. The syphon jets were replaced, line purged, retested and passed. <br /> Page 3 of 3 <br /> Rev.9/16/2020 <br /> 1868 E. Hazelton Avenue I Stockton, California 95205 1 T 209 468-3420 1 F 209 464-0138 1 www.sjgov.org/EHD <br />