Monitoring System Certification - Page 2 of 3 <br />Site Address: 13975 E. Hwy 88 Date of Testing/Servicing: 8128118 <br />D. Results of Testing /Servicing <br />Software version Installed• 331.01 <br />Com tete the followin checklist: <br />Is the audible alarm operational? <br />® Yes <br />❑ No <br />® Yes <br />❑ No* <br />Is the visual alarm operational? <br />Were all sensors visually inspected, functionally tested, and confirmed operational? <br />Were all sensors installed at lowest point of secondary containment and positioned so that other equipment will <br />not interfere with their proper operation? <br />® Yes <br />❑ No* <br />® Yes <br />❑ No* <br />N Yes <br />Do Yes <br />❑ No* <br />❑ N/A <br />❑ No* <br />❑ N/A <br />If alarms are relayed to a remote monitoring station, is all communications equipment (e.g. modem) <br />operational? <br />For pressurized piping systems, does the turbine automatically shut down if the piping secondary containment <br />monitoring system detects a leak, fails to operate, or is electrically disconnected? If yes: which sensors initiate <br />positive shut -down? (Check all that apply) R Sump/Trench Sensors; ® Dispenser Containment Sensors. <br />Did you confirm positive shut -down due to leaks and sensor failure/disconnection? ® Yes ❑ No <br />❑ Yes <br />❑ Yes* <br />❑ No* <br />® N/A <br />® No <br />For tank systems that utilize the monitoring system as the primary tank overfill warning device (i.e. no <br />mechanical overfill prevention valve is installed), is the overfill warning alarm visible and audible at the tank <br />fill point(s) and operating proper l ? If so, at what percent of tank capacity does the alarm trigger? 0 % <br />Was any monitoring equipment replaced? If yes, identify specific sensors, probes, or other equipment replaced <br />and list the manufacturer name and model for all replacement parts in Section E, below. <br />❑ Yes* <br />0 No <br />Was liquid found inside any secondary containment systems designed as dry systems? (Check all that apply) <br />❑ Product; ❑ Water. If yes, describe causes in Section E, below. <br />0 Yes <br />❑ No* <br />Was monitoring system set-up reviewed to ensure proper settings? Attach set-up reports, if applicable) <br />® Yes <br />❑ No* <br />Is all monitoring equipment operational per manufacturer's specifications? <br />E below, describe how and when these deficiencies were or will be corrected. <br />* In Section <br />E. Comments: Vent Sump Sensor (857080-111) & (794380-304) -Tested &Passed. <br />All Sumps & UDC's are monitored by additional Brine Sensors (797380-304) -Tested &Passed. <br />91 &Diesel are Split Tanks and Share Annular. <br />Estop - Tested &Passed. <br />