Afforda Test MAR 18 2019 <br /> OVERFILL WORKSHEETENVl � <br /> ENVIRONMENTAL F ` ALTH <br /> nFPAPTMIT <br /> Facility Name : Arch Road AmPm INFORMATIONAL ONLY <br /> Facility Address : 4855 South Highway 99, Stockton, Ca. 95215 <br /> Facility Contact: <br /> OVERFILLS : 2-749 <br /> Tank Charts Used: Xerxes <br /> I * TANK INFORMATION <br /> Tank Chart Tank Manufacturer Industry Standard Chart <br /> Tank # 1 Tank # 2 Tank # 3 Tank #4 Tank #5 Tank #6 <br /> 19703 11849 10369 <br /> Tank Capacity: 20K 12K 10K <br /> Tank Material : Fiberglass Fiberglass Fiberglass <br /> Tank Manufacturer: XERXES XERXES XERXES <br /> Product Stored : Regular 87 Plus 89 Super 91 <br /> Diameter: 117 117 117 <br /> Length: <br /> Inches to the bottom 98 . 5 98 97 . 5 <br /> of Tank: <br /> Volume of Overfill 17768 10691 9332 <br /> % 90 90 90 <br /> Xerxes DW 10' Dia Xerxes DW 10' Diain Xerxes DW 10' Di m <br /> 19703k (20k). pdf 11849k (12k). pdf 10369 tank (10k) . p <br /> Test Result : Pass Pass Pass Pass/ Fail Pass/ Fail Pass/ Fail <br /> Comments — (include information on repairs made prior to testing, and recommended follow-up for failed tests) <br />