2 FIRE ALARM RISER DIAGRAM ELECTRICAL SPECIFICATIONS
<br /> 33 THE ELECTRICAL CONTRACTOR SHALL FURNISH AND INSTALL, COMPLETE AND READY FOR 33.22 FIRE ALARM CIRCUITS SHALL BE IDENTIFIED AT TERMINAL AND JUNCTION LOCATIONS, IN A H
<br /> OPERATION, A HARDWIRED, SUPERVISED, ZONED AUTOMATIC FIRE AND SMOKE DETECTION MANNER THAT WILL PREVENT UNINTENTIONAL INTERFERENCE WITH THE SIGNALING CIRCUIT
<br /> SYSTEM INCLUDING A CENTRAL CONTROL PANEL, DETECTION AND ALARM INITIATING DEVICES, DURING TESTING AND SERVICING. W o
<br /> 2 D RELAYS, WIRING, ALL IN ACCORDANCE WITH THE DRAWINGS AND APPLICABLE STANDARDS. N
<br /> COMPLY WITH NEC 760 (2008), NFPA 72 (2007) AND 90A (2002), AND ALL FEDERAL, 33.21 WIRING TO BE AS HEREINBEFORE SPECIFIED AND BE COPPER, 300 VOLT RATING. AUDIO x o 0-)
<br /> 1-1/4"C AND WIRE STATE AND LOCAL LAWS AND ORDINANCES, INCLUDING THE AMERICANS WITH DISABILITIES VISUAL APPLIANCE WIRING TO BE PVC JACKETED, 16 AWG MINIMUM SIZE, NUMBER OF �..� CD
<br /> AS REQUIRED ACT. THE ELECTRICAL CONTRACTOR SHALL VERIFY THAT THE COMPLETED SYSTEM CONDUCTORS REQUIRED. SUBMIT CALCULATIONS ON LOAD AND VOLTAGE DROP. INITIATING w x
<br /> OPERATES IN ACCORDANCE WITH THIS SPECIFICATION. SYSTEMS SHALL BE U.L. AND/OR DEVICE WIRING TO BE PVC JACKETED, 18 AWG MINIMUM SIZE. SUBMIT CALCULATIONS ON o
<br /> F.M. LISTED AND APPROVED. LOAD AND VOLTAGE DROP. VOICE EVACUATION SPEAKER WIRING TO BE PVC JACKETED, 16 x o � x
<br /> _
<br /> FIRE ALARM CABLE IN CONDUIT AWG MINIMUM SIZE. SUBMIT CALCULATIONS ON LOAD AND VOLTAGE DROP. W Q
<br /> TO TELEPHONE BACKBOARD FOR 33.1 WHERE SHOWN ON THE DRAWINGS OR REQUIRED BY REGULATORY CODES PROVIDE A ' C o
<br /> 2 DEDICATED PHONE LINES. FAP DACT TO HOOD SUPPRESSION RAP 33.24 CONTROLLED OUTPUT DEVICES SHALL BE SUPERVISED TO WITHIN THREE FEET OF THE w o 0
<br /> ( ) / DIGITALLY DERIVED AUTO DIALER SYSTEM TO AUTOMATICALLY SEIZE A DEDICATED
<br /> MAKE CONNECTION TO DACT. SYSTEM CONTROL PANEL 0--
<br /> TELEPHONE LINE TO DIAL AND SIGNAL AN ALARM TO A REMOTE LOCATION. DEVICE CONTROLLED (AIR UNIT STARTER, KITCHEN HOOD, ETC.). �: Q
<br /> o o�
<br /> TO SPRINKLER HEAT TRACE TO AIR UNIT SHUT DOWN 33.2 THE ELECTRICAL CONTRACTOR SHALL ENGAGE A FIRE DETECTION SYSTEM CONTRACTOR AS 33.25 WHERE A FIRE DETECTION SYSTEM AS SPECIFIED HEREIN AND REQUIRED FIRE PROTECTION
<br /> CONTROLLER A SUBCONTRACTOR TO COORDINATE THE INSTALLATION OF THE WORK AND PROVIDE SHOP SPRINKLER SYSTEM ARE INSTALLED, IT SHALL BE PART OF THIS FIRE DETECTION SYSTEM °� N
<br /> TO BACKFLOW PREVENTER o ~
<br /> DRAWINGS FOR REVIEW. SHOP DRAWINGS MUST BE SUBMITTEDAPPROVED AND CLEARED CONTRACTOR'S WORK TO NOTIFY IN WRITING THE OWNER OF THE FACILITY OR THE OWNER'S o �0"),TAMPER SWITCHES AND HEAT co
<br /> TO POST INDICATOR VALVE FROM THE FIRE MARSHAL'S OFFICE BEFORE ANY WORK IS PERFORMED. THE CONTRACTOR REPRESENTATIVE THAT THE FIRE PROTECTION SYSTEM MUST, BY APPLICABLE CODES, BE
<br /> CO
<br /> CONTACTS CD
<br /> TRACE CONTROL VOLTAGE. WILL BE SOLELY RESPONSIBLE FOR ANY WORK PERFORMED BEFORE FINAL FIRE MARSHAL ADEQUATELY SUPERVISED BY A RESPONSIBLE AUTHORITY APPROVED SUPERVISORY COMPANYCD
<br /> MONITOR VOLTAGE ON THE APPROVAL. THAT WILL PROVIDE THE CONTINUOUS MONITORING OF THE SYSTEM TO ASSURE RELIABLE
<br /> LOAD SIDE OF THE OPERATION. INSTRUCTIONS SHALL INCLUDE ADVISING THE OWNER TO WRITE THE INSPECTING
<br /> DISCONNECT. 33.3 THE MAIN CONTROL PANEL SHALL BE RECESSED MOUNTED AND SHALL BE LISTED BY AUTHORITY ADVISING OF THIS COMPLIANCE.
<br /> UNDERWRITERS' LABORATORIES, INC. FOR FIRE PROTECTIVE SIGNALING SYSTEMS. THE MAIN
<br /> CONTROL PANEL SHALL CONTAIN THE PROPER NUMBER OF ZONES AND ZONE MODULES TO
<br /> PROVIDE FOR THE NUMBER OF ZONES SHOWN ON THE DRAWINGS AND SPECIFIED HEREIN,
<br /> FLOOR INCLUDING SPACE CAPABILITY FOR FUTURE. PROVIDE 3 EACH 3/4" EMPTY CONDUIT IN
<br /> WALL TO THE ACCESSIBLE CEILING SPACE. MAKE OF MODEL SHALL BE HONEYWELL/ES-50X Store:
<br /> FIRE ALARM PANEL AND SHALL BE PROVIDED BY CONTRACTOR.
<br /> 33.4 WHERE THE MAIN CONTROL PANEL WILL INITIATE AN EMERGENCY FORCES NOTIFICATION 1311 E. YOSEMITE AVE.
<br /> PROCEDURE, THE CONTRACTOR SHALL SHOW THE U.L. LISTING FOR THE CONTROL PANEL MANTECA, CA 95336
<br /> FOR THIS FUNCTION.
<br /> 33.5 THE REQUIRED SECONDARY POWER SOURCE SHALL BE PROVIDED FOR BY A U.L. LISTED Restaurant #RC529
<br /> POWER SUPPLY, CHARGER AND BATTERY SYSTEM. THE SYSTEM SHALL BE SIZED FOR ALL
<br /> ZONES CONNECTED PLUS THE ZONE CAPABILITY OF THE SYSTEM, AND AN ADDITIONAL 30%
<br /> SAFETY FACTOR.
<br /> Professional of Record: NAME
<br /> 33.6 THE REMOTE INDICATING PANEL SHALL SHOW ALL VISUAL AND AUDIBLE TROUBLE SIGNALS
<br /> AND ZONE INDICATORS THE SAME AS THE MAIN CONTROL PANEL BUT WILL NOT HAVE THE
<br /> RESET FUNCTION. REMOTE PANEL SHALL BE FOR RECESSED MOUNTING.
<br /> 33.7 PROVIDE A SOLID STATE ACTIVE SURGE PROTECTOR FOR THE INCOMING 120V A.C. LINE.
<br /> UNIT TO CLAMP SPIKES AND PEAKS TO A LEVEL BELOW THE DAMAGE THRESHOLD OF THE
<br /> UNIT. UNIT TO HAVE OPERATING LIGHT TO INDICATE PROTECTION. SYSTEM TO BE U.L.
<br /> LISTED FOR FIRE PROTECTION SYSTEM APPLICATION.
<br /> 33.8 THE CONTROL PANEL SHALL PROVIDE POWER FOR AND RECEIVE THE INPUT INITIATION FROM
<br /> INSTALLED SMOKE DETECTORS. DETECTORS SHALL BE U.L. LISTED FOR THE APPLICATION ROBISON
<br /> AND BE COMPATIBLE LISTED WITH THE MAIN CONTROL PANEL.
<br /> 33.9 DO NOT LOCATE SMOKE DETECTORS WITHIN THREE FEET OF ANY SUPPLY OR RETURN AIR ENGINEERING, INC
<br /> GRILLE OR DIFFUSER. UNIT SHALL BE CAPABLE OF OPERATING IN AIR CURRENTS OF UP TO 19401/OTF AVE W..SUITE 3C2
<br /> 1500 FEET PER MINUTE. v
<br /> LYNNWOOD,WA 98036
<br /> 206-3643343 TE_
<br /> 33.10 DETECTORS MOUNTED IN SUPPLY, RETURN OR EXHAUST AIR DUCTS SHALL BE UL LISTED
<br /> FOR DUCT SERVICE UTILIZING AIR SAMPLING TUBES, LENGTH OF THE TUBE THE FULL WIDTH REI# 424-1497
<br /> OF THE DUCT. THIS DETECTOR SHALL BE PHOTOELECTRIC TYPE, LOW FLOW TYPE WITH A
<br /> RANGE OF 100 TO 4,000 FEET PER MINUTE. DETECTOR SHALL BE UL COMPATIBLE WITH
<br /> THE CONTROL PANEL AND UL LISTED FOR DUCT MOUNTING.
<br /> 33.11 DUCT DETECTORS SHALL HAVE SUPERVISED AUXILIARY CONTACTS FOR USE IN THE
<br /> INTERLOCK AND SHUT DOWN CONTROL SCHEMES AS REQUIRED BY THIS SECTION AND THE
<br /> MECHANICAL SECTIONS OF THIS SPECIFICATION.
<br /> 33.12 PROVIDE AS PART OF THE MAIN CONTROL PANEL AN AUTO TELEPHONE NUMBER DIALER QROFESS/ON,9
<br /> SYSTEM. THE DIALER SYSTEM IS TO ACTIVATE UPON THE FIRE DETECTION SYSTEM ALARM
<br /> AND WILL HAVE AN OUTPUT DIALER NUMBER SUCH THAT A DEDICATED NUMBER CAN BE C/)
<br /> DIALED AND GIVEN SEPARATE DIGITAL ALARM SEQUENCES. SYSTEM MUST BE A DACT AND `9 Z
<br /> BE U.L. LISTED FOR THIS APPLICATION. MAKE OF MODEL SHAKL BE TELGUARD TG-7FS AND cD o. E-23059 m
<br /> SHALL BE PROVIDED BY CONTRACTOR.
<br /> �
<br /> 33.13 AUTO—DIALER SHALL BE CONNECTED WITH TWO TELEPHONE LINES USING FIRE ALARM RATED EXP. 3—al-22
<br /> CABLE. CATEGORY RATED CABLE IS NOT ACCEPTABLE. QFC \
<br /> 33.14 PROVIDE A DEDICATED SOURCE OF POWER FOR THE SYSTEM AS PER NFPA 72. THE q�F CA\\F��
<br /> CIRCUIT SHALL BE DEDICATED TO ONLY THIS SERVICE AND CONNECTIONS SHALL BE
<br /> MECHANICALLY PROTECTED. THE CIRCUIT DISCONNECTING MEANS SHALL HAVE A RED
<br /> MARKING, BE ACCESSIBLE ONLY TO AUTHORIZED PERSONNEL, AND BE IDENTIFIED AS "FIRE
<br /> ALARM CIRCUIT CONTROL." THE LOCATION OF THE CIRCUIT DISCONNECTING MEANS SHALL 08/07/20
<br /> BE PERMANENTLY IDENTIFIED AT THE FIRE ALARM CONTROL PANEL WITH AN ENGRAVED
<br /> LABEL.
<br /> Prototype : P4 EXTENDED- HV. SCHEME A
<br /> 33.15 THE ELECTRICAL CONTRACTOR SHALL PROVIDE ALL CONDUIT, WIRING AND CONNECTIONS TO
<br /> ALL EQUIPMENT BEFORE CALLING THE UNIT MANUFACTURER'S REPRESENTATIVE FOR FINAL Prototype Issue Date: 6 29 2020
<br /> CHECKOUT. ALL WIRING IS TO BE INSTALLED IN A SEPARATE CONDUIT SYSTEM, AS PER
<br /> OTHER SECTIONS OF THIS SPECIFICATION, UNLESS SPECIFICALLY NOTED OTHERWISE. Design Bulletin Updates: INCLUDED
<br /> 33.16 ALL SPLICES AND CONNECTIONS TO BE WHOLLY CONTAINED WITHIN APPROVED AND Date Issued: Bulletin Number:
<br /> ACCESSIBLE JUNCTION BOXES. ALL INPUT INITIATING DEVICES AND OUTPUT SIGNALING
<br /> APPLIANCES ARE TO BE MOUNTED WITH BACK BOXES AS PER THE U.L. TESTING PROCEDURE NOV. 2018 1 &2
<br /> FOR THAT DEVICE. NO DIRECT MOUNTED DEVICES ARE ALLOWED. HARDWIRED SYSTEMS p
<br /> SHALL NOT BE "T—TAPPED" TO SERVE INPUT INITIATING OR OUTPUT NOTIFICATION DEVICES. 1St Building Submittal
<br /> 33.17 THE SYSTEM SHALL BE ZONED AS PER DRAWINGS; INCLUDE A SEPARATE ZONE FOR EACH
<br /> FIRE PROTECTION ALARM SYSTEM FLOW SWITCH, AS APPLICABLE. REFER TO THE
<br /> MECHANICAL SPECIFICATIONS AND DRAWINGS. IT SHALL BE THE RESPONSIBILITY OF THE
<br /> FIRE DETECTION SYSTEM CONTRACTOR TO PROVIDE ALL COMPONENTS NECESSARY TO TIE
<br /> INTO THE SYSTEMS PROVIDED BY OTHERS. THE ELECTRICAL CONTRACTOR SHALL ALSO
<br /> PROVIDE ALL WIRING AS REQUIRED INCLUDING ALL ACCESSORIES DEMANDED BY THE WIRING
<br /> SYSTEM FOR THE FIRE PROTECTION SYSTEM COVERED UNDER THE MECHANICAL
<br /> SPECIFICATIONS.
<br /> 33.18 USE RED COLORED MULTI CONDUCTOR FIRE PROTECTIVE SIGNALING CIRCUIT CABLES. THE
<br /> CABLE MARKING SHALL BE IN ACCORDANCE WITH TABLE 760 179 (I) OF THE NEC. THIS
<br /> CABLE SHALL BE USED FOR ALL INITIATING AND SIGNALING WORK AND FOR THE TELEPHONE REVISIONS:
<br /> LINES FOR ANY DACT UNITS IN THE SYSTEM. CONDUCTORS SHALL BE INSTALLED IN
<br /> ACCORDANCE WITH ARTICLE 760 OF THE NEC. CABLES THAT ARE INSTALLED WITH 1 08-07-20 1st. Bldg. Submittal
<br /> PORTIONS IN CONDUIT UNDERGROUND OR UNDER SLAB SHALL BE NEC RATED FOR WET 2
<br /> LOCATIONS. SUCH CABLES SHALL BE GEL FILLED OR WATER BLOCKED CONSTRUCTION AND
<br /> SHALL HAVE THE FULL LENGTH INSTALLED IN CONDUIT. CABLE SHALL BE BELDEN 3
<br /> WATERDOG SERIES, WEST PENN AQUASEAL SERIES OR EQUAL AS LISTED BY ADDENDA. 4
<br /> SUBMIT ALL CABLES FOR REVIEW WITH THE SHOP DRAWINGS.
<br /> 5
<br /> 33.19 FIRE ALARM CIRCUITS SHALL BE INSTALLED IN A NEAT AND WORKMANLIKE MANNER. CABLES 6
<br /> SHALL BE SUPPORTED BY THE BUILDING STRUCTURE IN SUCH A MANNER THAT THE CABLE 7
<br /> WILL NOT BE DAMAGED BY NORMAL BUILDING USE.
<br /> 8
<br /> 33.20 ALL WIRING SHALL BE INSTALLED IN A SEPARATE CONDUIT SYSTEM FROM ALL OTHER 9
<br /> SYSTEMS. WIRING INSIDE WALLS AND INSTALLED IN INACCESSIBLE CEILING SPACES TO BE IN
<br /> CONDUIT. WIRING INSTALLED IN ACCESSIBLE CEILINGS MAY BE ROUTED WITHOUT CONDUIT.
<br /> ROUTE ALL CABLES PARALLEL OR PERPENDICULAR TO WALLS. DO NOT RUN IN A DIAGONAL
<br /> FASHION.
<br /> 33.21 WIRING WITHOUT CONDUIT SHALL USE DEDICATED J HOOKS MOUNTED AT 4'-0" MAXIMUM Sheet Title:
<br /> APART. DO NOT ROUTE FIRE ALARM CABLES BUNDLED WITH ANY OTHER CABLING. DO NOT ELECTRICAL
<br /> STRAP TO CONDUIT. USE B—LINE BCH SERIES OR CADDY CAT SERIES J—HOOKS WITH
<br /> MOUNTING AS APPROPRIATE TO THE LOCATION. DO NOT USE NYLON OR PLASTIC STRAPS. SPECIFICATIONS
<br /> DO NOT FASTEN TO CONDUIT OR TO ANY MECHANICAL OR OTHER MOVING EQUIPMENT.
<br /> MOUNT ALL SYSTEMS AS HIGH AS POSSIBLE AND ROUTED SO AS TO AVOID ACCESS POINTS
<br /> TO OTHER EQUIPMENT AND PERMIT SERVICING. DO NOT ATTACH TO HANGERS USED FOR
<br /> CEILING SYSTEMS, LIGHTING FIXTURES, HVAC DUCTWORK, ETC. Date: 08 07 2020
<br /> Project Number: RAC19024.0
<br /> Drawn By: XXX/XXX
<br /> Sheet Number:
<br /> E4 . 2
<br /> J
<br /> Q
<br /> H
<br /> CH
<br /> L
<br /> m
<br /> COPYRIGHT 2020, ROBISON ENGINEERING, INC.
<br /> JESCALONA F:\3EDRO+MCCRACKEN\JRAISING CANES\424-1497 MANTECA, CA\DWG\E42P4.DWG 07-22-2020 15:54