Laserfiche WebLink
I TAI T <br /> YISINO To TME CNALLtNO! 11280 Trode Center Drive, Roncho Cordovo,CA 95742 <br /> p:916/635/2444 www.tait.com <br /> 14. Page 8 of the application: Veeder Root 794380-208 sensor is not an appropriate tank <br /> interstitial sensor and is not designed for use with brine. Indicate an appropriate sensor. <br /> RESPONSE: Tank interstitial sensor has been revised to 794380-303. Please see revised <br /> application. <br /> 15. Spill bucket models were not included on page 7 of the application nor on the part list of <br /> the engineered plans. Cut sheets were provided for the OPW-1-2100-DEVR spill bucket, and <br /> the OPW Edge double walled spill bucket. Clarify which spill buckets will be used. Provide an <br /> updated application, parts list, and/or cut sheets. <br /> RESPONSE: The spill buckets being used are P761C-FLDV& P761C-FLPL. The spill bucket are <br /> included with the multiport sumps. Please see revised application and attached cut sheets. <br /> 16. Plans do not indicate longest piping run. Provide an indication of the longest piping run. <br /> RESPONSE: Longest piping run and total piping length have been added to sheet G0.1. <br />