FIRE DEPARTMENT NOTES GENERAL NOTES Al <br /> 1. THE APPLICANT SHALL INSTALL APPROVED FIRE EXTINGUISHERS, ONE (1) PER EACH 3000 SQUARE FEET, WITH A 1. THE CONTRACTOR AND/OR SUBCONTRACTOR SHALL VISIT THE SITE PRIOR TO THE SUBMITTAL OF BIDS. NO <br /> MAXIMUM TRAVEL FROM ANY POINT IN THE BUILDING 75 FEET. THESE SHOULD BE LOCATED AND APPROVED BY PERSON, OR CORPORATION SHALL ERECT, CONSTRUCT, ENLARGE, ALTER, REPAIR, MOVE, IMPROVE, REMOVE, Architecture / Development <br /> THE LOCAL FIRE DEPARTMENT PRIOR TO BUILDING OCCUPANCY. CONVERT, OR DEMOLISH ANY BUILDING OR STRUCTURE ON THE SITE, OR CAUSE THE SAME TO BE DONE <br /> WITHOUT FIRST OBTAINING A BUILDING PERMIT FOR EACH SUCH BUILDING OR STRUCTURE FROM THE BUILDING 14901 Quorum Drive <br /> 2. THE APPLICANT SHALL INSTALL PROTECTION OF COOKING EQUIPMENT BY MEANS OF AN AUTOMATIC FIRE OFFICIAL. Suite 300 <br /> EXTINGUISHING SYSTEM COMPLYING WITH UL 300 THAT IS LISTED AND LABELED FOR ITS INTENDED USE. A FIRE Dallas Texas 75254 <br /> EXTINGUISHER LISTED AND LABELED FOR CLASS K FIRES SHALL BE INSTALLED WITHIN 30 FEET OF COMMERCIAL 2. THE CONTRACTOR OR SUBCONTRACTOR SHALL VISIT THE SITE AND SHALL VERIFY ALL EXISTING CONDITIONS AND <br /> FOOD HEAT PROCESSING. DIMENSIONS PRIOR TO COMMENCING ANY WORK. ALL DISCREPANCIES SHALL BE REPORTED TO THE ARCHITECT Ph:(972)239-8884 <br /> UPON DISCOVERY. Fax: (972)239-5054 <br /> 3. ALL FIRE LANES SHALL BE POSTED WITH SIGNS AND/OR THE CURBS SHALL BE PAINTED RED PER LOCAL FIRE <br /> DEPARTMENT. 3. WRITTEN DIMENSIONS SHALL TAKE PRECEDENCE OVER SCALED DIMENSIONS. LARGER SCALE DRAWINGS SHALL ISSUE RECORD <br /> TAKE PRECEDENCE OVER SMALLER SCALE DRAWINGS. DATE DESCRIPTION <br /> 4. ADDRESS NUMBERS SHALL BE INSTALLED ON BUILDING IN ACCORDANCE WITH LOCAL FIRE DEPARTMENT URBAN PROTOTYPE <br /> 4. IT IS THE INTENT OF THESE DRAWINGS TO MEET OR EXCEED ALL APPLICABLE REGULATIONS OF ALL GOVERNING 7_7_2020 ISSUED FOR PERMIT <br /> 5. SMOKE DETECTORS ARE TO BE MOUNTED IN SUPPLY AND/OR RETURN DUCT WORK (DEPENDING ON LOCAL AHJ) AUTHORITIES. ALL WORK SHALL CONFORM TO THE CODE OR AS AMENDED BY THE CITY OR COUNTY BUILDING <br /> OF NEW AIR CONDITIONING SYSTEMS SUPPLYING GREATER THAN 2000 CFM. THE DETECTORS SHALL BE WIRED TO CODE AUTHORITY AND TO THE LATEST EDITIONS OF ALL OTHER APPLICABLE CODES OR REQUIREMENTS OF ALL <br /> SHUT OFF HVAC IF SMOKE IS DETECTED. A SMOKE DETECTOR SHUT-OFF TEST IS REQUIRED. SEE HVAC DRAWINGS OTHER REGULATING AGENCIES HAVING AUTHORITY OVER ANY PORTION OF THE WORK. NOTHING IN THESE <br /> FOR DUCT SMOKE DETECTOR LOCATIONS. DOCUMENTS SHALL BE CONSTRUED TO PERMIT DEVIATION FROM THE REQUIREMENTS OF THE GOVERNING CODES. <br /> 6. ANY ROOM HAVING AN OCCUPANT LOAD OF 50 OR MORE AND WHICH IS USED FOR ASSEMBLY PURPOSES SHALL 5. THE CONTRACTOR AND/OR SUBCONTRACTORS SHALL FURNISH ALL MATERIALS, LABOR, EQUIPMENT, <br /> HAVE THE CAPACITY OF THE ROOM POSTED IN A CONSPICUOUS PLACE ON A APPROVED SIGN NEAR THE MAIN EXIT TRANSPORTATION, AND SERVICES NECESSARY TO COMPLETE THE WORK AS INDICATED ON THE DRAWINGS, AS <br /> FROM THE ROOM. REQUIRED BY CODE, AND AS SPECIFIED HEREIN, EXCEPT AS PROVIDED BY THE OWNER OR AS OTHERWISE <br /> NOTED. <br /> 6. ALL MATERIAL AND EQUIPMENT SHALL BE NEW, FULL WEIGHT, AND OF THE BEST QUALITY AND SHALL BE <br /> INSTALLED IN NEAT AND WORKMANLIKE MANNER BY COMPETENT SPECIALISTS FOR EACH SUB-TRADE. ALL ITEMS <br /> REQUIRED TO INSURE PROPER INSTALLATION SHALL BE PROVIDED BY THE CONTRACTOR AND/OR <br /> SUBCONTRACTOR EVEN THOUGH NOT SPECIFIED ON THE DRAWINGS. REVISION RECORD <br /> 7. THE CONTRACTOR AND/OR SUBCONTRACTOR SHALL BE RESPONSIBLE FOR THE APPROPRIATE CONNECTION TO <br /> ALL UTILITIES REQUIRED TO SUPPORT THEIR WORK. WHERE CONSTRUCTION DETAILS ARE NOT SHOWN OR NOTED <br /> THE DETAILS SHALL BE THE SAME AS FOR OTHER SIMILAR WORK. <br /> 8. THE CONTRACTOR SHALL COORDINATE WORK WITH WORK PERFORMED BY OTHER CONTRACTORS, <br /> SUBCONTRACTORS ARE CONSIDERED SPECIALISTS IN THEIR FIELD AND SHALL NOTIFY THE CONTRACTOR OF ANY <br /> WORK CALLED OUT ON THE DRAWINGS IN THEIR TRADE THAT THEY CANNOT FULLY GUARANTEE. ALL <br /> DISCREPANCIES SHALL BE BROUGHT TO THE ATTENTION OF THE ARCHITECT FOR RESOLUTION PRIOR TO <br /> COMMENCEMENT OF WORK. <br /> 9. ALL PROPERTY DAMAGED BY WORK UNDER THIS CONTRACT SHALL BE REPAIRED AND/OR REPLACED TO THE <br /> SATISFACTION OF THE OWNER. <br /> 10. THE CONTRACTOR AND/OR SUBCONTRACTOR SHALL PROVIDE SUFFICIENT MEANS FOR PROTECTION OF EXISTING <br /> INTERIOR FINISHES AS WELL AS NEW CONSTRUCTION AND MATERIALS FROM DAMAGE BY WEATHER OR VANDALS <br /> DURING THE COURSE OF THE PROJECT CONSTRUCTION. <br /> 11. THE CONTRACTOR SHALL PROVIDE ALL BARRICADES AND FENCES TO SCREEN THE PROJECT FROM THE PUBLIC <br /> VIEW AND FOR PUBLIC PROTECTION AS REQUIRED BY THE CODE OR OTHER LOCAL ORDINANCE. <br /> 12. THE CONTRACTOR SHALL AT ALL TIMES KEEP THE PREMISES FREE OF RUBBISH AND WASTE MATERIALS. <br /> 13. UPON COMPLETION OF THE WORK, ALL WORK AREAS SHALL BE THOROUGHLY CLEANED TO THE APPROVAL OF <br /> THE OWNER. <br /> 14. ALL EXISTING EQUIPMENT REMOVED DURING DEMOLITION OR REHABILITATION SHALL BE DISPOSED OF AS PROFESSIONAL SEAL <br /> DIRECTED BY THE OWNER. <br /> 15. ALL MATERIALS SHALL BE INSTALLED PER MANUFACTURER'S LATEST PRINTED SPECIFICATIONS AND � ►5E ���i►j� <br /> RECOMMENDATIONS. C� F <br /> 16. BRACING AND TEMPORARY SUPPORTS SHALL BE PROVIDED AS REQUIRED TO HOLD THE WORK SECURELY IN G <br /> PLACE, AND TO SUSTAIN ALL LOADS THAT MAY OCCUR DURING ERECTION AND UNTIL SUBSEQUENT <br /> CONSTRUCTION IS ADEQUATE TO REPLACE TEMPORARY BRACING. <br /> $E 30 21 <br /> 17. ALL SHORING AND BRACING SHALL BE IN ACCORDANCE WITH CURRENT STATE REQUIREMENTS AND OTHER PUBLIC <br /> AGENCIES HAVING JURISDICTION. gr <br /> 18. SHOULD ANY CONDITIONS ARISE WHERE THE INTENT OF THE DRAWINGS IS IN DOUBT OR WHERE THERE IS A <br /> DISCREPANCY OR APPEARS TO BE AN ERROR ON THE DRAWINGS OR BETWEEN THE DRAWINGS AND THE FIELD <br /> CONDITIONS, THE ARCHITECT AND STRUCTURAL ENGINEER SHALL BE NOTIFIED AS SOON AS REASONABLY <br /> POSSIBLE. NO STRUCTURAL CHANGES SHALL OCCUR WITHOUT PRIOR WRITTEN DIRECTION AND APPROVAL OF THE <br /> STRUCTURAL ENGINEER. <br /> 19. THE CONTRACTOR SHALL FURNISH AND MAINTAIN TEMPORARY SANITATION FACILITIES AS REQUIRED DURING <br /> CONSTRUCTION. <br /> 20. THE CONTRACTOR SHALL PROVIDE PEDESTRIAN PROTECTION BARRICADES, LIGHTING, ETC. AS REQUIRED BY LOCAL <br /> AUTHORITIES. PROTOTYPE VERSION <br /> 16U.2.61 <br /> 21. OBTAIN PERMITS FROM STATE AND LOCAL JURISDICTION FOR ALL EXCAVATION FIVE FEET AND GREATER IN DEPTH <br /> IN WHICH A PERSON IS REQUIRED TO DESCEND. <br /> PROJECT NAME <br /> 22. THE CONTRACTOR IS RESPONSIBLE FOR ALL METHODS AND MEANS OF CONSTRUCTION AND SHALL OBTAIN N N 0 UT <br /> REQUIRED APPROVALS AND PERMITS. <br /> 23. THE CONTRACTOR SHALL KEEP THE CONSTRUCTION AREA FREE OF ALL DEBRIS AND BROOM CLEAN TO THE BURGER <br /> SATISFACTION OF THE OWNER AND THE ARCHITECT. <br /> 24. THE CONTRACTOR SHALL VERIFY THE LOCATION, SIZE, AND DEPTH OF ALL UTILITIES PRIOR TO START OF <br /> CONSTRUCTION AND IS RESPONSIBLE TO REPAIR TO THE STANDARDS OF UTILITY COMPANIES ANY DAMAGE TO <br /> EXISTING UTILITIES. STO C KTO N <br /> 25. THE CONTRACTOR SHALL CARRY LIABILITY INSURANCE AND WORKMEN'S COMPENSATION INSURANCE AS REQUIRED CALIFORNIA <br /> BY THE STATE OR GOVERNING AUTHORITIES. <br /> 26. THE GENERAL CONTRACTOR IS RESPONSIBLE TO PROVIDE OPENINGS. PENETRATIONS, ETC. AS REQUIRED FOR <br /> COMPLETION OF PLUMBING, ELECTRICAL, AND MECHANICAL INSTALLATION. 5202 PACIFIC AVE <br /> 27. THE CONTRACTOR OR SUBCONTRACTOR IS RESPONSIBLE TO REPAIR OR REPLACE ALL DAMAGED WORK CAUSED STOCKTION, CA 95207 <br /> BY THE CONTRACTOR OR SUBCONTRACTOR. <br /> 28. IF REQUIRED BY LOCAL CODE, INSPECTION SHALL BE BY BUILDING INSPECTOR FOR ALL INTERIOR AND EXTERIOR <br /> IN-PLACE LATH AND/OR WALLBOARD BEFORE ANY PLASTERING IS APPLIED OR ANY JOINTS AND FASTENERS <br /> HAVE BEEN TAPED AND FINISHED. <br /> 29. ALL HANDICAPPED AND PUBLIC ACCESSES SHALL CONFORM TO THE REQUIREMENTS OF THE 2016 ADA <br /> STANDARDS FOR ACCESSIBLE DESIGN AND LOCAL GOVERNING REQUIREMENTS. <br /> 30. SINGLE SERVICE SOAP AND TOWEL DISPENSERS SHALL BE PROVIDED AT ALL HAND SINKS. MoNmOUT <br /> 31. EXTERIOR DOORS TO OPEN FROM INSIDE WITHOUT USE OF A KEY OR ANY SPECIAL KNOWLEDGE OF OPERATION. `BURGER® <br /> 32. ALL DELIVERY DOORS SHALL BE EQUIPPED WITH AIR SCREEN TO PROVIDE A DOWNWARD-OUTWARD AIR VELOCITY GOD BLESS AMERICA <br /> OF 750 FEET PER MIN. OVER ENTIRE OPENING DOWN TO 3 FEET ABOVE FLOOR. <br /> 33. THE FLOOR OR LANDING SHALL NOT BE MORE THAN 1/2" LOWER THAN THE THRESHOLD OF THE EXTERIOR <br /> DOOR. <br /> 34. ALL DOORS TO BE SELF CLOSING. SEE SHEET A11.0 DOOR SCHEDULE. <br /> PROJECT NUMBER <br /> 35. WEATHER-STRIP ALL EXTERIOR DOORS. 190955 <br /> 36. DRAIN LINES AND ELECTRICAL CONDUIT MUST BE AT LEAST 6" OFF FLOOR AND 1/2" AWAY FROM WALLS. SHEET TITLE <br /> 37. SURVEY BY A LICENSED SURVEYOR OR CIVIL ENGINEER IS REQUIRED TO VERIFY ELEVATION OF LOWEST FINISHED <br /> FLOOR. GENERAL NOTES <br /> E 38. ALL ROUGH METAL EDGES OF HARDWARE, PUSH PLATES, PIPING, FASTENERS, TOP OF TOILET PARTITIONS, ETC... <br /> 0 <br /> TO BE FILED SMOOTH SO THAT THERE ARE NO SHARP EDGES FOR CUSTOMERS OR CLEANING CREW. <br /> 0 <br /> N <br /> O <br /> N <br /> SHEET NUMBER <br /> C � <br /> C:) <br /> mLijA2mO <br /> a <br /> a a <br /> z z <br /> C= = <br /> a � <br />