ELECTRICAL WORK, GENERAL <br />REQUIREMENTS <br />Section 16000 <br />15-1207 <br />6. Safety Switches: F.S. W -S-865, Type "HD" with externally operated handle. Switches shall <br />be rated 250 and 600 volts AC, of size and poles as shown. <br />7. Fuses: <br />a. All fuses rated up to 600 amperes: UL labeled as Class RK1 or Class J (RK5) with <br />time delay and suitable for up to 200,000 amperes, current limiting, such as <br />Gould/Shawmut Amp -Trap, Bussman Low -Peak, (Fusetron) or equal. Time delay: <br />ten (10) seconds minimum at five hundred percent (500%) of fuse rating. <br />b. Spare Fuses: Provide minimum of three (3) of each ampere rating.' <br />C. Fuseholders: Rejection type. Where Class J fuses are used, holders will required <br />Class J spacing. <br />8. Pull Line: Jet Line No. 232, Greenlee No. 430, or equal, one -eight inch (1/8") diameter <br />braided line of polypropylene line of continuous fiber polyolefin; minimum break strength, two <br />hundred (200) pounds. Furnish pull line in all unused (empty) raceways. <br />R. Fabrication and Manufacture: Follow manufacturer's directions where manufacturers of articles <br />used furnish directions covering points not shown or specified. <br />PART 3 - EXECUTION <br />3.1 INSTALLATION: <br />A. Manufacturer's Directions: Follow manufacturer's directions where manufacturers of articles <br />used furnish directions covering points not specified or shown. <br />B. Equipment: Accurately set and level, neatly place support and anchor properly. Anchorage shall <br />conform to the requirements of 2013 California Building Code Part 2, Table 13A-0. No allowance <br />will be made for negligence to foresee means of placing, installing or supporting equipment in <br />position. <br />C. Assemble together all equipment which requires assembling including Contractor -supplied <br />bussing, internal wire connections where required; connect all incoming conduit, cable and wires <br />properly; and adjust and make ready for service electrical equipment and material required by <br />this Contract. <br />D. All Work shall be done in orderly, workmanlike manner and present neat appearing installation <br />when completed. <br />E. Normal Contingencies: <br />1. Existing conduits which are required to be extended, altered, or reconnected shall be <br />accomplished as shown or as directed. Existence of any wires, conduits, or other facilities <br />are shown in a general way only. Determine existence, location, and condition on site. <br />2. Where existing conduits which are shown to be revised or which will be essential to <br />functioning of particular system are cut or exposed due to construction changes, new <br />connections shall be made in most expeditious manner as directed or shown. Where wiring <br />is involved, new wires shall be "pulled -in" between nearest available accessible reused <br />11 <br />