CONDUIT, FITTINGS & <br />SUPPORTS <br />Section 16021 <br />15-1207 <br />1) Exposed EMT shall be supported with one (1) hole strap within thirty-six <br />inches (36") of connector or within thirty-six inches (36") on each side of <br />coupling. <br />b. Galvanized iron hanger rods sizes one-quarter inch (1/4") diameter and larger with <br />spring steel fasteners, clips or clamps specifically designed for purpose for conduit <br />up to one inch (1") size may be used. <br />C. Individual conduit three-quarter inch (3/4") and smaller run above suspended <br />ceilings shall be supported from an independent hanger wire with approved spring <br />steel clips. Conduit shall not be secured to, or supported by, the ceiling assembly, <br />including ceiling support wires. <br />d. Support conduit to wood structure by means of bolts or lag screws in shear, to <br />concrete by means of insert or expansion bolts and to brickwork by means of <br />expansion bolts. <br />e. Support multi -parallel vertical conduit runs with galvanized "Unistrut", or approved <br />equal, type supports anchored to wall. Where larger conduit of multi -story buildings <br />pass through floors, support conduit with riser clamps at each floor. <br />21. Conduit support spacings shall be in accordance with NECA Standard of Installation, as <br />follows: <br />1,1-1/4 <br />- - - Exposed............................................8 <br />Conduit <br />No. of <br />Max. Spacing <br />Size <br />Conductors <br />of Supports <br />Inches <br />In Run <br />Location Ft. <br />Horizontal Runs <br />Any <br />- - - Concealed........................................10 <br />3/4 <br />1 or 2 <br />Flat ceiling or wall ..............................5 <br />3/4 <br />1 or 2 <br />Where it is difficult to provide supports <br />except at intervals fixed by the building <br />construction......................................7 <br />3/4 <br />3 or more <br />Any location......................................7 <br />1 and larger 1 or 2 Flat ceiling or wall...............................6 <br />1 and larger 1 or 2 Where it is difficult to provide support except <br />at intervals fixed by the building <br />construction.... .............................10 <br />1 and larger 3 or more Any location.....................................10 <br />Any - - - Concealed........................................10 <br />Vertical Runs <br />3/4 <br />Screws Sizes for Conduit Supports <br />7 <br />Exposed............................................7 <br />1,1-1/4 <br />- - - Exposed............................................8 <br />1-1/2 & larger <br />- - - Exposed...........................................10 <br />Up to 2 <br />- - - Shaftway..........................................14 <br />2-1/2 & larger <br />- - - Shaftway...........................................28 <br />Any <br />- - - Concealed........................................10 <br />Screws Sizes for Conduit Supports <br />7 <br />