Laserfiche WebLink
CONDUIT, FITTINGS & <br />SUPPORTS <br />Section 16021 <br />15-1207 <br />PART 1 - GENERAL <br />1.1 CONDITIONS: <br />A. The Requirements of this Section apply to all Work of Division 16, as applicable. <br />B. Where items specified in other Sections of Division 16 conflict with Requirements of this Section, <br />the most stringent requirements shall govern. <br />1.2 WORK INCLUDED: <br />A. Furnish, assemble, erect, install, connect, and test all power, control and lighting conduits, <br />including fittings, boxes, sealing materials, drain fittings and any other miscellaneous equipment <br />and material required and as specified herein and as shown to form complete installation. <br />B. Install all equipment in accordance with Requirements of 2013 California Electrical Code unless <br />otherwise specified or shown. <br />1.3 QUALITY ASSURANCE: <br />A. Reference Standards: <br />1. ANSI -American National Standards Institute <br />C80.3 Specification for Electrical Metallic Tubing, Zinc -Coated. <br />C80.1 Specification for Rigid Steel Conduit, Zinc -Coated. <br />C33.91 Specification for Rigid PVC Conduit. <br />2. FS - Federal Specifications <br />WW -C-563 <br />Conduit, Metal, Rigid: Electrical, Thin -Wall Steel Type (Electrical <br />Metallic Tubing); Straight Lengths, Elbows, and Bends. <br />WW -C-566 <br />Conduit, Metal, Flexible. <br />WW -C-581 E <br />Conduit, Metal, Rigid; and Coupling, Elbow, and Nipple, Electrical <br />Conduit: Zinc -Coated. <br />W -C -1094A <br />Conduit and Conduit Fittings, Plastic, Rigid. <br />W -C-586 <br />Conduit, Outlet Boxes, Bodies and Entrance Caps (Cast Metal). <br />W -J-800 <br />Junction Box; Extension, Junction Box; Cover, Junction Box <br />(Steel, Cadmium, or Zinc -Coated). <br />W -S-865 <br />Switch, Box (enclosed), Surface -Mounted. <br />3. NEMA - National Electrical Manufacturer's Association <br />RNI Polyvinyl -Chloride Externally Coated Galvanized Rigid Steel <br />Conduit and Electrical Metallic Tubing. <br />TC -2 Electrical Plastic Tubing (EPT) and Conduit (EPC -40 and EPC - <br />80). <br />TC -3 PVC Fitting for Use with Rigid PVC Conduit and Tubing. <br />TC -6 PVC and ABS Plastic Utilities Ducts for Underground Installation. <br />