Laserfiche WebLink
INSULATED CONDUCTORS <br />Section 16070 <br />15-1207 <br />PART 1 - GENERAL <br />1.1 CONDITIONS: <br />A. The Requirements of the General Conditions and Special Conditions apply to the Work of this <br />Section as if fully repeated herein. <br />1.2 WORK INCLUDED: <br />A. Provide all wire for all systems including lighting systems, mechanical systems, receptacles, <br />communication system, fire detection systems, electrical service and distribution system. <br />1.3 PRODUCT, DELIVERY, STORAGE, AND HANDLING: <br />A. Deliver wire to site in its original unbroken packages, plainly marked or tagged as follows: <br />1. Underwriters' labels. <br />2. Size, kind, and insulation of wire. <br />3. Name of manufacturing company and trade name of wire. <br />1.4 QUALITY ASSURANCE: <br />A. Reference Standards: <br />1. UL - Underwriter's Laboratories, Inc.: <br />44 Wires and Cables, Rubber -Insulated. <br />83 Wires and Cables, Thermoplastic -Insulated. <br />1569 Metal -Clad Cables. <br />2. NEMA - National Electrical Manufacturer's Association: <br />WC 5 Thermoplastic -Insulated Wire and Cable for the Transmission and <br />Distribution of Electric Energy. <br />WC 7 Cross -Linked -Thermosetting -Polyethylene Insulated Wire and Cable for <br />the Transmission and Distribution of Electrical Energy. <br />3. FS - Federal Specification: <br />HH -1-595 Insulated Tape, Electrical, Pressure- Sensitive Adhesive, Plastic. <br />PART 2 - PRODUCTS <br />2.1 MATERIALS: <br />A. Wire and Cable: <br />1. Single conductor, stranded, soft drawn copper wire having conductivity of not less than <br />ninety-eight percent (98%) of that of pure copper, with insulation rated at 600 volts AC, <br />E <br />