Laserfiche WebLink
PANELBOARDS <br />Section 16435 <br />15-1207 <br />PART 1 - GENERAL <br />1.1 CONDITIONS: <br />A. The Requirements of the General Conditions and Special Conditions apply to the Work of this <br />Section as if fully repeated herein. <br />1.2 WORK INCLUDED: <br />A. Furnish all labor, materials, and equipment and perform operation required for complete <br />installation of panelboards, individual mounted circuit breakers, and safety switches as indicated <br />on Drawings and/or specified herein. Such Work includes, but is not limited to, furnishing and <br />installation of power and lighting panelboards and fused safety switches. <br />1.3 QUALITY ASSURANCE: <br />A. Reference Standards: <br />1. FS - Federal Specification <br />W -C-375 Circuit Breakers, Molded Case: Branch Circuit and Service. <br />2. CEC - 2013 California Electrical Code: <br />Art. 384 Switchboards and Panelboards. <br />3. NEMA - National Electrical Manufacturer's Association <br />PB1 Panelboards. <br />AB Molded Case Circuit Breakers. <br />4. UL - Underwriter's Laboratories Inc. Standards <br />489 Molded Case Circuit Breakers and Circuit Breaker Enclosures. <br />67 Electric Panelboards. <br />1.4 SUBMITTALS: <br />A. Refer to Division 1 and Section 260120. <br />B. Test Reports: Production tests of circuit breakers when requested. <br />C. Show: <br />1. Circuit breaker numbering. <br />2. Circuit breaker type and short circuit rating. <br />1 <br />