Laserfiche WebLink
PANELBOARDS <br />Section 16435 <br />15-1207 <br />3. Provisions for future addition of circuit breakers. <br />4. Bussing and rating of, including neutral and ground. <br />5. Enclosures: <br />a. Dimension. <br />b. Trim. <br />PART 2 - PRODUCTS <br />2.1 MATERIALS: <br />A. Panelboards: Eaton, General Electric, Siemens, Square D. <br />1. Panelboards: Factory -assembled, dead -front, metal encased safety type; construction <br />consisting of structural or formed steel frame carefully braced and welded into rigid structure <br />which shall maintain its alignment and not be damaged in shipment or erection, or by <br />stresses resulting from short circuits. Bolted housing construction with tack -welded joints will <br />be acceptable. Frame: Completely enclosed on rear, top and sides with sheet steel covers, <br />doors and panels, accessible from front. Cabinet: Of sufficient size to conform to both <br />minimum dimensional requirements and minimum wiring gutter requirements of Article 373 <br />CEC (2013). Minimum Cabinet Size: twenty inches (20") wide by five and three-quarters <br />inches (5 3/4") deep. Stationary Portions of Steel Frame and Covers: 12 -gauge minimum <br />with concealed trim clamps. Old style screw fastener type not acceptable. Doors: Sheet <br />metal construction with concealed hinges and equipped with flush type lock and catch. All <br />panels shall be keyed alike. Supply two (2) keys with each lock. Distribution panels installed <br />in outdoor locations shall be free standing in NEMA 3R enclosure. Equipped with heater(s) <br />and thermostat. Heater(s) shall prevent condensation from forming in the inside of the panel. <br />Set thermostat at fifty-five degrees (551) F. <br />2. Busses: Hard-drawcoppei, ,ii,lety-eight percent (AuB0/v) conductivity, Grade ED, ASTM <br />B230, in accordance with NEMA Standards and as hereinafter specified. <br />3. Connectors: Silver plated copper. <br />4. Structure Housing, Bus, and Connections; Construct brace to safely withstand rated short <br />circuit currents in conformance with UL Standard Ui-67. Connections shall be bolted or <br />welded and laminations arranged to provide adequate contact area. All contact surfaces of <br />copper shall be silver-plated. Copper sizes and arrangement shall be such that temperature <br />rise of bus shall not exceed fifty degrees (500) C. with a forty degrees (400) C. ambient <br />outside enclosure. <br />5. Provide a bare copper neutral bus on insulated bus supports and an uninsulated copper <br />equipment ground bus bar secured to each unit frame, to provide separate, integrated, <br />continuous, neutral and equipment ground buses. Neutral Bus: Same size as associated <br />phase buses for 480/277 volt panels, 200% rated for 208/120 volt panels. Ground Bus: <br />Arranged to ground panelboard's non -current -carrying parts, provided with brazed or <br />approved pressure connector terminations for feeder ground conductors. <br />6. PanelhnnrA KAnin nnA Rrnnrh Circuit Prntertinn, Rnit-nn typnr mniriie41 race rirrwiit breakers <br />with sizes as shown. Individual panelboards shall be constructed to have short circuit rating <br />consistent with circuit breaker being installed. <br />7. Circuit Breakers: <br />L <br />