FIRE ALARM SYSTEM <br />Section 16710 <br />15-1207 <br />all equipment against defects in material and workmanship for two (2) years, and provide <br />on -the -premises service during normal working hours for two years, at no cost to Owner if <br />trouble is not caused by misuse, abuse, or accident, or at current labor rates if so caused. <br />Provide manufacturer's written one-year guarantee for equipment and parts. <br />2. Service shall normally be available within 24 hours from service department of authorized <br />distributor of manufacturer by factory trained servicemen. <br />3. On -the -premises service at other than normal working hours to also be available, but labor <br />charges for ci iirh rallc to be paid by purchaser at Owner labor rates. <br />PART 2 - PRODUCTS <br />2.01 SYSTEM OPERATION <br />A. Activation of any manual station or automatic detector shall cause the operation of all audible <br />and visual signals. In addition to sounding local alarm signals, operation of manual stations or <br />automatic detectors shall activate a digital communicator for telephone leased line reporting to <br />remote SB575 compliant supervisory station. Telephone company leased lines and remote <br />station monitoring shall be arranged by the Owner. <br />The system shall be electrically supervised against open circuits and grounds on the wiring to <br />the alarm and initiating devices. <br />B. Contractor to ensure synchronization of visual devices where required by NFPA 72. <br />2.02 STANDARD PRODUCTS <br />A. Equipment and accessories furnished under the terms of these specifications shall be the <br />standard products of the manufacturers specified or required. All equipment shall be listed by <br />U.L. and State Fire Marshal. New equipment shall be compatible with existing system. <br />B. Refer to drawings for devices used. <br />PART 3 - EXECUTION <br />3.01 INSTALLATION REQUIREMENTS <br />A. Electrical Contractor shall retain the services of the duly appointed representative as specified <br />hereinbefore, who shall furnish all equipment, make all connections to same, and place system <br />in operation. Technician and workman employed shall be particularly skilled in this type of <br />work. Technicians and workmen must have NICET certification as required hereinbefore. Fire <br />alarm system contractors shall possess a valid C10 California Electrical Contractors license. <br />Only contractors holding a valid license may perform any fire alarm work. <br />B. Existing system shall be tested as soon as possible after award of contract and prior to any <br />demolition work and prior to preparing submittals. Contractor shall test entire system to insure <br />proper operation. Any defects or deficiencies found shall be listed and presented to Owner in <br />letter form. It will be assumed that existing equipment is fully functional unless identified <br />otherwise by Contractor. <br />Testing shall be scheduled by the Contractor and shall be conducted at time least disruptive to <br />CI <br />