Laserfiche WebLink
ENTRANCES & STOREFRONTS <br />Section 08410 <br />15-1207 <br />PART 2 -PRODUCTS <br />2.01 PERFORMANCE REQUIREMENTS <br />A. Wind loads: Provide framing system; include anchorage, capable of withstanding wind load <br />design pressures of (25) lbs./sq. ft. inward and (25) lbs./sq. ft. outward. The design wind load <br />shall be based on 85 MPH exposure "C" per Article 1.06 A. <br />B. Air Infiltration: The test specimen shall be tested in accordance with ASTM E 283. Air <br />infiltration rate shall not exceed 0.06 cfm/ft2 at a static air pressure differential of 6.24 psf. <br />C. Water Resistance: The test specimen shall be tested in accordance with ASTM E 331. There <br />shall be no leakage at a minimum static air pressure differential of 8 psf as defined in AAMA <br />501. <br />D. Uniform Load: A static air design load of 20 psf shall be applied in the positive and negative <br />direction in accordance with ASTM E 330. There shall be no deflection in excess of L/175 of <br />the span of any framing member. At a structural test load equal to 1.5 times the specified <br />design load, no glass breakage or permanent set in the framing members in excess of 0.2% <br />of their clear spans shall occur. <br />E. Thermal Transmittance (U -factor): When tested to AAMA Specification 1503, the thermal <br />transmittance (U -factor) shall not be more than: <br />1. Glass to Exterior — 0.47 (low -e). <br />2. Glass to Center — 0.44 (low -e). <br />3. Glass to Interior — 0.41 (low -e). <br />F. Condensation Resistance (CRF): When tested to AAMA Specification 1503, the <br />condensation resistance factor shall not be less than: <br />1. Glass to Exterior — 70frame and 69glass (low -e). <br />2. Glass to Center — 62 name and 68glass (low -e). <br />3. Glass to Interior — 56 fame and 67 g,ass (low -e). <br />G. Entrance Performance Requirements: <br />1. Air Infiltration: For single action offset pivot or butt hung entrances in the closed and <br />locked position, the test specimen shall be tested in accordance with ASTM E 283 at a <br />pressure differential of 6.24 psf for single doors and 1.567 psf for pairs of doors. A single <br />3'0" x 7'0" entrance door and frame shall not exceed 0.50 cfm per linear foot of perimeter <br />crack. A pair of 6'0" x 7'0" entrance doors and frame shall not exceed 1.0 cfm per linear <br />foot of perimeter crack. <br />2. Structural: Corner strength shall be tested per Kawneer's dual moment load test <br />procedure and certified by an independent testing laboratory to ensure weld compliance <br />and corner integrity. <br />2.02 MANUFACTURER <br />A. Acceptable Manufacturers: Kawneer Company, Inc. of Norcross, GA <br />3 <br />