Laserfiche WebLink
Project Name:Nonresidential Building NRCC-PRF-01-E Page 2 of 16 <br />Project Address:610 West Kettleman Lane Lodi 95240 Calculation Date/Time:14:44, Wed, Feb 17, 2021 <br />Input File Name:2020-121 Takeoff.cibd19x <br />CA Building Energy Efficiency Standards- 2019 Nonresidential Compliance Report Version: NRCC-PRF-01-E-11022020-6384 Report Generated at: 2021-02-17 14:45:26 <br />C1. COMPLIANCE RESULTS FOR PERFORMANCE COMPONENTS (Annual TDV Energy Use, kBtu/ft 2-yr) <br />COMPLIES <br />Energy Component Standard Design (TDV)Proposed Design (TDV)Compliance Margin (TDV)1 <br />Space Heating 20.22 20.01 0.21 <br />Space Cooling 87.37 85.93 1.44 <br />Indoor Fans 26.43 22.51 3.92 <br />Heat Rejection ------ <br />Pumps & Misc.0.06 0.06 -- <br />Domestic Hot Water 7.78 7.78 -- <br />Indoor Lighting 37.32 37.32 -- <br />ENERGY STANDARDS COMPLIANCE TOTAL 179.18 173.61 5.57 (3.1%) <br />1 Notes: The number in parenthesis following the Compliance Margin in column 4. represents the Percent Better than Standard. <br />C2. RESULTS FOR 'ABOVE CODE' QUALIFICATIONS1 <br />This project is pursuing CalGreen Tier 1 This project is pursuing CalGreen Tier 2 <br />Miscellaneous Energy Component Standard Design (TDV)Proposed Design (TDV)Compliance Margin (TDV)1 <br />Receptacle 165.32 165.32 -- <br />Process ------ <br />Other Ltg 7.90 7.90 -- <br />Process Motors 0.46 0.46 -- <br />COMPLIANCE TOTAL PLUS MISCELLANEOUS COMPONENTS 352.86 347.29 5.6 (1.6%) <br />1 Notes: This table is used to document compliance with programs OTHER THAN Title 24 Part 6, if applicable.