Laserfiche WebLink
Underground Storage Tank <br /> Overfill Prevention Equipment Inspection Report <br /> 8. OVERFILL PREVENTION EQUIPMENT DETAILS <br /> Tank ID (one OPE per column) 57-1 67-1 e7-2 91 <br /> Are both vent and tank riser piping f Yes f Yes f Yes f Yes <br /> secondarily contained? No No No No <br /> OPE Model OPw OPw oPw OPW <br /> What is the OPE response when activated? 21 Shut off Shut off f Shut off f Shut off <br /> (Check all that apply.) Flow Flow Flow Flow <br /> estricts estricts estricts Restricts <br /> Flow Flow Flow Flow <br /> Audible Audible Audible Audible <br /> Alarm Alarm Alarm Alarm <br /> Visual Visual Visual Visual <br /> Alarm Alarm Alarm Alarm <br /> Are flow restrictors installed on vent piping Yes* Yes* Yes' Yes* <br /> that may interfere with the OPE operation? ✓ No No f No f No <br /> At what-level-in the tank is-the OPE set-to <br /> activate Inches from bottom of tank 101 1/2" 104 3/4" 102 3/4" <br /> What is the percent capacity of the tank at 92% 93% 91% <br /> which the OPE activates? <br /> Is the OPE in proper operating condition to f Yes Yes f Yes f Yes <br /> respond when the stored substance No DNo No No <br /> reaches the designated regulatory level? <br /> 7. SUMMARY OF TESTING RESULTS <br /> OPE Inspection Results f Pass Pass f Passf Pass <br /> Fail HFail Fail Fail <br /> 8. COMMENTS <br /> Describe all results marked "Fail"and each proposed remedy. <br /> Was unable to test one of the 87-1 drop tubes due to nipple being seized to spill bucket. Will need to return and cut nipple off spill bucket and retest. <br /> * Mark here if: <br /> Flow restrictors interfere with overfill prevention and equipment repairs required. <br /> Additional copies of this page may be attached. <br /> Attach tank chart(s), measurements, calculations, and In-Tank Setup report(s) <br /> Page 2 of 2 <br />