Laserfiche WebLink
■:w GerrcER-RVAN INC. GR Job # 22200026 <br /> u FORM 1 <br /> SUMMARY OF SOURCE TEST DATA <br /> SOURCE INFORMATION FACILITY PARAMETERS <br /> GDF Name and Address GDF Representative and Title PHASE II SYSTEM TYPE <br /> Arco 2186 Kimberly Medicus ICheckOne) <br /> 3212 N California <br /> Stockton, CA 95204 GDF Phu neNo. Balance <br /> 360-970-2296 Hirt <br /> Permit Condit ons Source.GDF Vaper Recovery System Red Jacket <br /> CAS Hasstech <br /> Healy <br /> GDF# Other <br /> A/C d <br /> Min folded? Yes NO <br /> Operating Parameters <br /> Number of Nozzles Served by Tank#1 8 Number of Nozzles Served by Tank#3 8 <br /> Number of Nozzles Served by Tank 42 a Number of Nozzles Served by Tank#4 <br /> Applicable Regulations: VR-203-1 and VR-204-1 - —VN Recommended <br /> Source Test Results and Comments <br /> Tank#: 1 2 3 4 <br /> 1. Product Grade 87 87 91 <br /> 2. Actual Tank Capacity, gallons 19703 10180 11849 <br /> 3. Gasoline Volume Total 9845 5494 3214 <br /> 4. Ullage,gallons (#2-#3) 23179 9858 4686 8635 <br /> S. Initial Pressure,inches H2O 2.00 <br /> & Pressure After 1 Minute, inches H2O 2.00 <br /> 7. Pressure After 2 Minutes, inches H2O 2.00 <br /> 8. Pressure After 3 Minutes, inches H2O 1.99 <br /> 9. Pressure After Minutes, inches H2O 1.99 <br /> 10. Final Pressure After 5 Minutes, inches H2O 1.98 <br /> 11. Allowable Final Pressure 1.94 <br /> Test Conducted by: Test Company: Date of Test: <br /> Darnell Smith Gettler-Ryan Inc. 1/14/2022 <br /> California Air Resource Board March 17, 1999 <br /> TP-201.3, Page 14 <br />