Laserfiche WebLink
Underground Storage Tank <br /> Secondary Containment Testing Report Form <br /> 8. SUMP/UDC TEST <br /> Test Method Developed by Manufacturer Industry Standard Li Professional Engineer <br /> Test Type Ll Pressure Ll Vacuum ZHydrostatic <br /> Test Equipment Used:TS-STS <br /> Sump/UDC ID 87STP 87-2STP 91STP 87 Fill <br /> Sump Manufacturer Xerxes Xerxes Xerxes Xerxes <br /> Sump Depth (inches) 61" 60" 61" 60" <br /> Sump Bottom to Top of <br /> Highest Pipe Penetration 30" 26" 31" 19" <br /> (inches) <br /> Test Start Time 10:11AM 10:11AM 10:11AM 8:36AM <br /> Initial Reading 5.2377" 3.5948" 2.2695" 2.8252" <br /> Test End Time 10:27AM 10:27AM 10:27AM 8:51AM <br /> Final Reading 5.2385" 3.5955" 2.2712" 2.8287" <br /> Change in Reading 0.0008" 0,0007" 0.0017" 0.0005" <br /> ass ail Criteria +/- 0.0021, +/- 0.002" +/- 0.002 +!- 0.00216 <br /> Tightness Test Results -7--"2]Pass Fail ✓ Pass Fail �/ Pass Fail Pass Fail <br /> Sump/UDC ID 97-2 Fitz 91 Fill 1/2 3/4 <br /> Sump Manufacturer Xerxes Xerxes Bravo Brava <br /> Sump Depth (inches) 60" 60" 30" 30" <br /> Sump Bottom to Top of <br /> Highest Pipe Penetration 20" 20" 9" 9.1 <br /> (inches) <br /> Test Start Time 8:36AM 8:36AM 11:27AM 11:27AM <br /> Initial Reading 0.8052" 0.9818" 5.9439" 2.4160" <br /> Test End Time 8:51AM 8:51AM 11:42AM 11:42AM <br /> Final Reading 0.8046" 0.9814" 5.9439" 2.4172" <br /> Change in Reading 0.0006" 0.00041, 0" 0.0012" <br /> Pass/ ail Criteria +/- 0.00211 +/- 0.002" +/- 0.002" +/- 0.00211 <br /> Tightness Test Results � Pass Fail ZPass Fail IZPassLjFail ZPass Fail <br /> Additional copies of this page may be attached. <br /> All tests marked "Fail'and any repairs made before or during the tightness test must be described in <br /> the COMMENTS section. <br /> Page 3 of 5 <br />