Laserfiche WebLink
A NJ O A Q U l N Environmental Health Department <br /> COUNTY— V AMENDED <br /> 2/1/2022 <br /> Underground Storage Tank Program Inspection Report <br /> Facility Name: Facility Address: Date: <br /> COUNTRY CLUB MOBIL CIRCLE K 2575 COUNTRY CLUB BLVD, STOCKTON January 28, 2022 <br /> SUMMARY OF VIOLATIONS <br /> (CLASS I,CLASS II,or MINOR-Notice to Comply) <br /> Item# Remarks <br /> hours of being provided a signed copy of the report, the owner or operator shall provide a description of each <br /> corrective action taken or to be taken and shall sign and date the report, acknowledging the identified compliance <br /> issues. <br /> CORRECTIVE ACTION: Ensure all designated operator inspection reports are completed and signed within the <br /> required time frame in the future. <br /> This is a repeat violation, Class II. <br /> 308 CCR 2632(c), 2634(d), 2636(f) Failure of the leak detection equipment to have an audible and visual alarm. <br /> OBSERVATION:Vacuum sensors, S1 87 Product and S3 91 Product,were in alarm at the time of inspection. <br /> According to the owner, Sartaj (Nick)Singh, Elite IV is waiting on parts to repair the sensors. <br /> REGULATION GUIDANCE:All monitoring equipment shall be maintained to activate an audible and visual alarm or <br /> stop the flow of product at the dispenser when it detects a leak. <br /> CORRECTIVE ACTION: Correct immediately by having a properly licensed,trained, and certified contractor replace <br /> the failed component with a functional component(LG 113-x listed, if applicable), and obtain a permit within one <br /> business day from the EHD, if needed. If the failed component can't be replaced immediately,there is a possibility <br /> that the 87 and 91 UST systems may be red tagged to prevent fuel inputs. <br /> This is a repeat violation, Class II. <br /> 313 HSC 25290.1(d)Monitoring system incapable of detecting entry into secondary containment(post-Jul 2004). <br /> OBSERVATION:Vacuum sensors, S1 87 Product and S3 91 Product,were in alarm at the time of inspection. <br /> According to the owner, Sartaj (Nick)Singh, Elite IV is waiting on parts to repair the sensors. <br /> REGULATION GUIDANCE: The continuous monitoring system shall be maintained to detect the entry of the liquid <br /> or vapor phase of the hazardous substance stored in the primary containment into the secondary containment, and <br /> to detect water intrusion into the secondary containment. <br /> CORRECTIVE ACTION: Correct immediately by having a properly licensed,trained, and certified contractor replace <br /> the failed component with a functional component(LG 113-x listed, if applicable), and obtain a permit within one <br /> business day from the EHD, if needed. If the failed component can't be replaced immediately,there is a possibility <br /> that the 87 and 91 UST systems may be red tagged to prevent fuel inputs. <br /> This is a repeat violation, Class II. <br /> FA0006439 PR0231070 SCO01 01/28/2022 <br /> EHD 23-01 Rev.12/06/2021 Page 8 of 9 Underground Storage Tank Program OIR <br /> 1868 E. Hazelton Avenue I Stockton, California 95205 1 T 209 468-3420 1 F 209 464-0138 1 www.sjgov.org/EHD <br />