Laserfiche WebLink
SAN J 0 A Q I I I Irl Environmental Health Department <br /> CCUNT <br /> Underground Storage Tank Program Inspection Report <br /> Facility Name: Facility Address: Date: <br /> STOCKTON AUTO CENTER CAR WASH T3434 E HAMMER LN, STOCKTON November 01, 2022 <br /> SUMMARY OF VIOLATIONS <br /> (CLASS I,CLASS II,or MINOR-Notice to Comply) <br /> Item# Remarks <br /> 311 HSC 2636(a)(1), 25291(b) Monitoring system incapable of detecting leak into secondary containment(pre-Jul <br /> 2003). <br /> OBSERVATION: The diesel annular sensor failed to activate an audible and visual alarm when tested and, <br /> therefore,the tank is not monitored. <br /> REGULATION GUIDANCE: The UST system shall be designed and constructed with a monitoring system capable <br /> of detecting leaks from primary containment into secondary containment. <br /> CORRECTIVE ACTION: The sensor was replaced and retested during the inspection. <br /> This is a Class II violation. <br /> 318 CCR 2635, 2637.1,2665, 2712 Failed to meet spill container requirements. <br /> OBSERVATION: The 91, 87, and diesel spill container failed when tested. <br /> REGULATION GUIDANCE:All spill containers shall have a minimum capacity of five gallons and be capable of <br /> containing a spill or overfill until it is detected or cleaned up. <br /> CORRECTIVE ACTION: Immediately discontinue deposition of petroleum into this tank until the component is <br /> repaired or replaced by a properly licensed, trained, and certified contractor under permit and inspection of the EHD. <br /> If the spill container can't be replaced immediately,there is a possibility that the 91, 87, and diesel UST system may <br /> be red tagged to prevent fuel inputs. <br /> This is a repeat violation, Class II. <br /> Overall Inspection Comments: <br /> An inspection report was provided to the facility operator on the day of inspection. The report was amended <br /> and replaces the initial report. <br /> Violation#311 was added. Updated violations#118 and #208. <br /> Complete and submit a copy of the Return to Compliance Certification form to the EHD with a statement <br /> documenting the corrective actions that have been or will be taken for each violation, and any supporting <br /> paperwork, within 30 days of receiving the amended inspection report. <br /> AFTER THE COMPLIANCE DATE, EHD WILL BILL FOR ALL TIME AND ACTIVITIES ASSOCIATED WITH BRINGING <br /> THIS FACILITY BACK INTO COMPLIANCE. <br /> THIS FACILITY IS SUBJECT TO REINSPECTION AT ANY TIME AT EHD'S CURRENT HOURLY RATE. <br /> Received by: Date: November 01, 2022 Inspector: Inspector Phone: <br /> Printed Name and Title: KRISTINA SAETERN, EH Specialist (209)616-3045 <br /> Emailed to Josh Karpinski, General Manager <br /> FA0003681 PR0232398 SCO01 11/01/2022 <br /> EHD 23-01 Rev.12/06/2021 Page 7 of 7 Underground Storage Tank Program OIR <br /> 1868 E. Hazelton Avenue I Stockton, California 95205 1 T 209 468-3420 1 F 209 464-0138 1 www.sjgov.org/EHD <br />