Laserfiche WebLink
Underground Storage Tank <br /> Secondary Containment Testing Report Form <br /> 9. COMMENTS <br /> 87 Secondary Line Failed Due to Bad Bravo Hub in UDC 5/6. <br /> 91 STP Sump Increased.Adjusted/Compensate for Increase. Block for Wind; Eliminate Potential Vibrations;Adjust for <br /> Traffic; Adjust for Testing Probe-Retested and Passed. <br /> 87, 91, Diesel Fill Sumps Failed -Possible Conduit Penetration Boots. <br /> UDC 1/2 Failed -Possible Conduit Penetrations. <br /> UDC 5/6 Failed Due to Bad Bravo Hub. <br /> No Inspector Present. <br /> * Pressurized Secondary Piping to 3 psi Due to Bravo Flex Boots. <br /> All tests marked "Fail"and any repairs made before or during the tightness test must be described in <br /> the COMMENTS section. <br /> Page 5 of 5 <br />