Laserfiche WebLink
Underground Storage Tank <br /> Secondary Containment Testing Report Form <br /> 8. SUMP/UDC TEST (continued) <br /> Test Method Developed by ❑ Manufacturer D Industry Standard ❑ Professional Engineer <br /> Test Type ❑ Pressure ❑ Vacuum 0 Hydrostatic <br /> Test Equipment Used: Incon Tester <br /> Sump/UDC ID 87 STP 91 STP DSL STP <br /> Sump Manufacturer Fiberglass Fiberglass Fiberglass <br /> Sump Depth (inches) 48" 48" 48" <br /> Sump Bottom to Top of <br /> Highest Pipe Penetration 29" 27" 26" <br /> (inches) <br /> Test Start Time 9:37 am 9:59 am 9:37 am <br /> Initial Reading 4.3603 6.1863 3.5936 <br /> Test End Time 9:52 am 10:15 am 9:52 am <br /> Final Reading 4.3611 6.1857 3.5932 <br /> Change in Reading 0.0008 0.0006 0.0004 <br /> Pass/Fail Criteria 0.002 0.002 0.002 <br /> Tightness Test Results 0 Pass ❑ Fail 0 Pass ❑ Fail 0 Pass ❑ Fail ❑ Pass ❑ Fail <br /> Sump/UDC ID 87 FILL 91 FILL DSL FILL <br /> Sump Manufacturer Fiberglass fiberglass fiberglass <br /> Sump Depth (inches) 48" 48" 48" <br /> Sump Bottom to Top of <br /> Highest Pipe Penetration N/A N/A N/A <br /> (inches) <br /> Test Start Time 8:03 am 8:03 am 8:03 am <br /> Initial Reading 3.1779 1.5120 6.1857 <br /> Test End Time 8:19 am 8:19 am 8:19 am <br /> Final Reading 3.1681 1.5099 6.0802 <br /> Change in Reading 0.0098 0.0021 0.1055 <br /> Pass/Fail Criteria 0.002 0.002 0.002 <br /> Tightness Test Results ❑ Pass 0 Fail ❑ Pass El Fail ❑ Pass 0 Fail ❑ Pass ❑ Fail <br /> Additional copies of this page may be attached. <br /> All tests marked "Fail"and any repairs made before or during the tightness test must be described in <br /> the COMMENTS section. <br /> Page 4 of 5 <br />