Laserfiche WebLink
Underground Storage Tank <br /> Secondary Containment Testing Report Form <br /> 8. SUMP/UDC TEST <br /> Test Method Developed by ❑ Manufacturer D Industry Standard ❑ Professional Engineer <br /> Test Type ❑ Pressure ❑ Vacuum 0 Hydrostatic <br /> Test Equipment Used: Incon Tester <br /> Sump/UDC ID UDC 1/2 UDC 3/4 UDC 5/6 UDC 7/8 <br /> Sump Manufacturer Bravo Steel Bravo steel Bravo steel Bravo steel <br /> Sump Depth (inches) 12" 12" 12" 12" <br /> Sump Bottom to Top of <br /> Highest Pipe Penetration 4" 4" 4" 4" <br /> (inches) <br /> Test Start Time 10:33 am 10:33 am N/A 10:33 am <br /> Initial Reading 0.8811 2.5264 N/A 3.5362 <br /> Test End Time 10:48 am 10:48 am N/A 10:48 am <br /> Final Reading 0.8643 2.5261 N/A 3.5363 <br /> Change in Reading 0.0168 0.0003 N/A 0.0001 <br /> Pass/Fail Criteria 0.002 0.002 0.002 0.002 <br /> Tightness Test Results ❑ Pass 0 Fail 0 Pass ❑ Fail ❑ Pass 0 Fail 0 Pass ❑ Fail <br /> Sump/UDC ID UDC 9/10 <br /> Sump Manufacturer Bravo steel <br /> Sump Depth (inches) 12" <br /> Sump Bottom to Top of <br /> Highest Pipe Penetration 4" <br /> (inches) <br /> Test Start Time 10:33 am <br /> Initial Reading 2.7509 <br /> Test End Time 10:48 am <br /> Final Reading 2.7501 <br /> Change in Reading 0.0008 <br /> Pass/Fail Criteria 0.002 <br /> Tightness Test Results 0 Pass ❑ Fail ❑ Pass ❑ Fail ❑ Pass ❑ Fail ❑ Pass ❑ Fail <br /> Additional copies of this page may be attached. <br /> All tests marked "Fail"and any repairs made before or during the tightness test must be described in <br /> the COMMENTS section. <br /> Page 3 of 5 <br />