Laserfiche WebLink
Underground Storage Tank <br /> Secondary Containment Testing Report Form <br /> 8. SUMP/UDC TEST <br /> Test Method Developed by ❑ Manufacturer ❑ Industry Standard ® Professional Engineer <br /> Test Type ❑ Pressure ❑ Vacuum ® Hydrostatic <br /> Test Equipment Used: Caldwell Level Change Indicator <br /> Sump/UDC ID 1-91-PS 2-87-M-PS 3-87-S-PS 4-Diesel-PS <br /> Sump Manufacturer CSI CSI CSI CSI <br /> Sump Depth (inches) 54" 52" 51" 44" <br /> Sump Bottom to Top of 14" 27" 24" 12" <br /> Highest Pipe Penetration <br /> (inches) <br /> Test Start Time 9:42 10:22 11:02 11:42 <br /> Initial Reading .001 .001 .001 .001 <br /> Test End Time 10:12 10:52 11:32 12:12 <br /> Final Reading .001 .001 .001 .001 <br /> Change in Reading 0 0 0 0 <br /> Lss/FailCriteria > .002 > .002 > .002 > .002 <br /> htness Test Results M Pass ❑ Fail ® Pass ❑ Fail ® Pass ❑ Fail ® Pass ❑ Fail <br /> Sump/UDC ID UDC 1&2 UDC 3&4 UDC 5&6 UDC 7&8 <br /> Sump Manufacturer Environ Environ Environ Environ <br /> Sump Depth (inches) 30" 29" 30" 30" <br /> Sump Bottom to Top of 9" 9" 9" 9" <br /> Highest Pipe Penetration <br /> (inches) <br /> Test Start Time 11:47 11:52 11:57 12:32 <br /> Initial Reading .001 .001 .001 .001 <br /> Test End Time 12:17 12:22 12:27 1:02 <br /> Final Reading .001 .001 .001 .001 <br /> Change in Reading 0 0 0 0 <br /> Pass/Fail Criteria > .002 > .002 > .002 > .002 <br /> Tightness Test Results ® Pass ❑ Fail ® Pass ❑ Fail ® Pass ❑ Fail ® Pass ❑ Fail <br /> Additional copies of this page may be attached. <br /> All tests marked "Fail'and any repairs made before or during the tightness test must be described in <br /> the COMMENTS section. <br /> Page 3 of 5 <br />