Laserfiche WebLink
SECTION 230000 - HVAC GENERAL CONDITIONS covers and suitable weather-proof covering. For extended outdoor storage, remove 2.03 SEISMIC RESTRAINTS 1. Summary Comments: .up <br /> motors from equipment and store separately. A. Type: Non-directional and double acting unit consisting of interlocking steel a. Design versus final performance MW <br /> PART 1 GENERAL 1.10 WARRANTY AND GUARANTEE members restrained by neoprene elements. b. Notable characteristics of system <br /> A. Submit manufacturer's warranty and ensure forms have been filled out in Owner's B. Elements: Replaceable neoprene, minimum of 0.75 inch thick with minimum 1/8 inch C. Summary of outdoor and exhaust flows to indicate amount of building <br /> 1.01 APPLICABILITY name and registered with manufacturer. air gap. pressurization <br /> A. This section supplements all sections of the Specifications for Division 23 and B. Provide one year manufacturer warranty for pumps. C. Capacity: 4 times load assigned to mount groupings at 0.4 inch deflection. d. Nomenclature used throughout report and test conditions. <br /> shall apply to all phases of work hereinafter specified, shown on the Drawings, or C. Provide three year manufacturers warranty for solid state ignition modules. D. Attachment Points and Fasteners: Capable of withstanding 3 times rated load B. Electric Motors and drives: <br /> required to provide a complete installation of approved HVAC systems. D. Provide five year manufacturers warranty for compressors, heat exchangers, capacity of seismic snubber. 1. Manufacturer; Model/Frame; HP/BHP; Phase, voltage, amperage; nameplate, <br /> 1.02 DEFINITIONS condensing units, and electronic air cleaners. actual , no load; RPM; Service factor; Sheave Make/Size/Bore. <br /> A. "Work" is hereby defined as, "The construction and services required by the PART 3 EXECUTION 2. V-Belt Drives: Identification/location; Required driven RPM; Driven sheave, <br /> Contract Documents whether completed or partially completed and includes all labor, PART 2 PRODUCTS diameter and RPM; Belt, size and quantity; <br /> materials, equipment, and services provided or to be provided by the Contractor to 3.01 INSTALLATION C. Cooling and Heating Coils: ©2017 STARBUCKS COFFEE COMPANY <br /> fulfill the Contractor's obligations. The work may constitute the whole or a part 2.01 SUBSTITUTIONS A. Install in accordance with manufacturer's instructions. 1. Identification/number; Manufacturer <br /> of the project." A. The manufacturers listed are listed to set minimum standards for quality, design, B. On closed spring isolators, adjust so side stabilizers are clear under normal 2. Air flow, design and actual <br /> B. "Furnish" is hereby defined as, "To supply and deliver, unload, and inspect for and functionality. The products of other manufacturers may be submitted, at the operating conditions. 3. Air pressure drop, design and actual STARBUCKS C 0 F F E E <br /> damage." Contractor's option, during shop drawing review unless indicated otherwise. The C. Prior to making piping connections to equipment with operating weights 4. Entering and leaving air DB and WB temperature, design and actual <br /> C. "Install" is hereby defined as, "To unpack, assemble, erect, apply, place, finish, products of other manufacturers shall meet or exceed all requirements of the substantially different from installed weights, block up equipment with temporary 5. Water flow, design and actual (if applicable) <br /> cure, protect, clean, connect, and place into operation into the work. Contract Documents. The Contractor accepts all responsibility for costs and shims to final height. When full load is applied, adjust isolators to load to 6. Water pressure drop, design and actual (if applicable) COMPANY <br /> D. Provide is hereby defined as, To furnish and install . coordination issues arising out of the substitution of materials or equipment, and allow shim removal . 7. Entering and leaving water temperature, design and actual (if applicable) <br /> E. "Connect" is hereby defined as, "To bring service to the equipment and make final the coordination of such substitutions with all other contractors and D. Support piping connections to equipment mounted on isolators using isolators or D. Air Moving Equipment: 2401 UTAH AVENUE SOUTH <br /> attachment"including necessary ductwork, piping, wiring, etc." subcontractors. resilient hangers to nearest flexible pipe connector. 1. Manufacturer; Model number; Serial number; Arrangement/Class/Discharge SEATTLE,WASHINGTON 98134 <br /> F. Concealed is hereby defined as, Hidden from sight in chases, furred spaces, B. The Contractor may use any of the following ductwork, piping or insulation E. Provide flexible connections on all piping and ductwork connections to equipment. 2. Air flow, specified and actual _ <br /> shafts, hung ceilings, embedded in construction, in crawl spaces, or buried. materials at his option, provided the selected material meets with the approval of Refer to other sections of this Specification for the acceptable types of flexible 3. Inlet; Discharge; Total static pressure (total external), specified and (206)318 1575 <br /> G. "Exposed" is hereby defined as, "Not installed underground nor concealed as defined all State, local authorities and any utility company requirements. Verification of connectors to be used. actual <br /> by the Specifications." comp I i once of the se I ected materia I i s the so I e respons i b i I i ty of the i nsta I I i ng F. Se I ect i on of type, thickness and def I ect i on of v i brat i on i so I at i on sha I I be by the E. A i r D i str i but i on Tests: THESE DRAWINGS AND SPECIFICATIONS ARE <br /> H. "Draw i ngs" i s hereby defined as, "All plans, detaiIs, equipment schedules, Contractor. v i brat i on contro I manufacturer based on the spec i f i c equipment type and s i ze, as 1. A i r term i na I number CONFIDENTIAL AND SHALL REMAIN THE SOLE <br /> diagrams, sketches, etc. i ssued for the construction of the work." schedu I ed on the Drawings and i nd i Gated be I ow. 2. Room number/I ocat i on <br /> 3. PROPERTY OF STARBUCKS CORPORATION <br /> 1.03 CODES AND STANDARDS PART 3 EXECUTION 3.02 SCHEDULES Terminal type <br /> A. Perform work in accordance with the applicable Building Code, Electrical Code, Fire A. Equipment Isolation Schedule: (Minimum deflection as sized by the isolation 4. Terminal size WHICH IS THE OWNER OF THE COPYRIGHT IN <br /> Code, Mechanical Code, Plumbing Code, Energy Code, and all other applicable codes, 3.01 COORDINATION OF WORK equipment manufacturer.) 5. Area factor THIS WORK. THEY SHALL NOT BE <br /> amendments, and ordinances. A Iso perform a I I work i n accordance w i th the Americans A. Examine the Contract Documents as a who I e for the work of other trades. Coordinate 1. Fans, ax i a I and centr i f uga I . 6. Design ve I oc i ty REPRODUCED (IN WHOLE OR IN PART), SHARED <br /> with D i sab i I i t i es Act (ADA) and the Authority Having Jurisdiction (AHJ) i nc I ud i ng a I I work accord i ng I y. <br /> a. Sma I I fans up to 22 d i ameter whee I: 7. Design a i r f I ow WITH THIRD PARTIES OR USED IN ANY MANNER <br /> Fire Marshal(s). B. Promptly report to the Architect any delay or difficulties encountered in the 1. Rubber Mount or Hanger 8. Test final velocity <br /> B. Perform work i n accordance w i th Land I ord requirements, i nc I ud i ng any Tenant i nsta I I at i on of the work, which m i ght prevent prompt and proper i nsta I I at i on, or 2. Packaged roof top equipment. 9. Test f i na I a i r f I ow ON OTHER PROJECTS OR EXTENSIONS TO THIS <br /> Cr i ter i a Manua I s and Lease Exhibits, where app I i cab I e. make i t unsu i tab I e to connect w i th or receive the work of others. Fa i I ure to so <br /> a. Above grade roof structures: 10. Percent of design a i r f I ow PROJECT WITHOUT THE PRIOR WRITTEN <br /> C. Perform work i n accordance w i th the app I i cab I e ut i I i ty companies serving the report sha I I constitute an acceptance of the work of other trades as being f i t and 1. Base: Roof Curb. CONSENT OF STARBUCKS CORPORATION. <br /> project. Make a I I arrangements w i th the ut i I i ty companies for proper coordination proper for the execution of th i s work. 2. Isolation: Fu I I perimeter Neoprene Pad between curb and units. END OF SECTION THESE DRAWINGS AND SPECIFICATIONS ARE <br /> of the work. C. P Ian, I ay out, and coordinate the work w i th a I I trades we I I enough i n advance so Provide restrained spring v i brat i on i so I at i on curbs when <br /> D. INTENDED TO EXPRESS DESIGN INTENT FOR A <br /> Recognized Standards: Design, manufacture, testing and method of installation of that it proceeds with a minimum of interference to work that has not been completed indicated on the Drawings. <br /> a I I apparatus and mater i a I s furnished under the requirements of these and work that i s i n progress. Inform a I I trades of openings required for the work SECTION 230713 - DUCT INSULATION PROTOTYPICAL STARBUCKS STORE(WHICH IS <br /> Specifications sha I I conform to the I atest pub I i cat i ons or standard ru I es of and provide a I I spec i a I f Names, s I eeves, and anchor bo I is required. The HVAC END OF SECTION SUBJECT TO CHANGE AT ANYTIME)AND DO <br /> Underwriters Laboratories, Inc. (U.L.), American Society for Testing and Materials system layout may be altered to suit the conditions with engineer approval , prior PART 1 GENERAL NOT REFLECT ACTUAL SITE CONDITIONS. <br /> ASTM), American Nat i ona I Standards Institute (ANSI), and Nat i ona I E I ectr i ca I Code to the i nsta I I at i on of any work and w i thout add i t i ona I cost to the Owner. <br /> NEC), National Fire Protection Association (NEPA), American Society of Heating, Conflicts arising from lack of coordination shall be this Contractor's SECTION 230593 - TESTING, ADJUSTING, AND BALANCING FOR HVAC 1.01 SECTION INCLUDES NEITHER PARTY SHALL HAVE ANY OBLIGATION <br /> Refrigerating and A i r-Conditioning Engineers (ASHRAE), and the Sheet Meta I and A i r respons i b i I i ty. A. Duct i nsu I at i on. NOR LIABILITY TO THE OTHER(EXCEPT STATED <br /> Conditioning Contractors' Nat i ona I Association (SMACNA). D. Perform a I I work i n conformity w i th the Contract Documents and afford other trades PART 1 GENERAL B. Duct I i ner. ABOVE) UNTIL A WRITTEN AGREEMENT IS <br /> E. The Contract Documents shall take precedence where the Contract Documents exceed reasonable opportunity for the execution of their work. Properly connect and C. Insulation jackets. FULLY EXECUTED BY BOTH PARTIES. <br /> code, Landlord, utility, or recognized standards requirements. coordinate this work with the work of other trades at such time and in such a 1.01 SECTION INCLUDES D. Supply, return or exhaust ducts in ceiling spaces. <br /> 1.04 PERMITS AND FEES manner as not to delay or interfere with their work. A. Testing, adjustment, and balancing of air systems. E. Supply, return or exhaust ducts in interior unconditioned areas. <br /> A. Permits, licenses, fees, inspections and arrangements required for the work under E. All roofing penetrations shall be flashed and weather sealed by,the roofing 1. Air handling units; Packaged heating and/or cooling equipment; Fans. (Exhaust F. Supply, return or exhaust ducts in exposed locations. <br /> this Contract shall be obtained by the Contractor at his expense, unless otherwise manufacturer s authorized roofing contractor at this Contractor s expense. This and supply); Coils; Terminal equipment; Air inlets and outlets. (Diffusers, 1.02 FIELD CONDITIONS ARCHITECT OF RECORD <br /> indicated. Contractor shall contract with the factory authorized roofing contractor for the grilles, louvers, etc.) A. Maintain ambient temperatures and conditions required by manufacturers of mcg architecture <br /> 1.05 CONTRACT DRAWINGS specific roofing system applicable to this Project. The use of an unauthorized B. Measurement of final operating condition of HVAC systems. adhesives, mastics, and insulation cements. <br /> A. The Contractor is responsible to obtain, fully understand, and coordinate the work roofing contractor may result in removal and replacement of the penetration systems C. Independent agency requirements. B. Maintain temperature during and after installation for minimum period of 24 hours. 5 <br /> Cn with the complete set of Contract Documents. Any required corrections, including at this Contractor's expense. 1.02 SUBMITTALS15 -55--, i-, <br /> IM <br /> all associated costs, arising from issues caused by the Contractor's failure to F. All temperature control wiring, thermostat wiring, damper interlock wiring, control A. Qualifications: Submit name of adjusting and balancing agency and TAB supervisor PART 2 PRODUCTS Co a <br /> understand and/or coordinate the work with the complete set of Contract Documents panel interlock wiring and miscellaneous low voltage wiring associated with the for approval within 30 days after award of Contract. Provide TAB Agency LL_ G <br /> are the Contractor's sole responsibility. equipment furnished or installed under this contract shall be furnished and qualifications. 2.01 REQUIREMENTS FOR ALL PRODUCTS OF THIS SECTIONW III <br /> B. Work under these sections is diagrammatic unless indicated otherwise and is installed by the mechanical contractor or his sub-contractor. All wiring installed B. Final Report: Indicate deficiencies in systems that would prevent proper testing, A. Surface Burning Characteristics: Flame spread/Smoke developed index of 25/50, `n <br /> intended to convey the scope of work and indicate the general arrangement of under this contract shall be in full compliance with the National Electrical Code, adjusting, and balancing of systems and equipment to achieve specified maximum, when tested in accordance with ASTM E 84, NEPA 255, or UL 723. <br /> ductwork, p i p i ng, equipment, and accessories. Fo I I ow these drawings i n I ay i ng out a I I State and I oca I codes and requirements of the E I ectr i ca I Specifications for performance. B. Manufacturer: Knauf Fiber Glass; Johns Manville Corporation; Owens Corning Corp.; 15635 Alton Parkway,Suite 100, Irvine,CA 92618 <br /> the work and verify spaces for the installation of these materials and equipment. this project. 1. Submit to the Construction Manager within two weeks after completion of CertainTeed Corporation. P: 949.553.1117 F:949.474.7056 <br /> Wherever a question exists as to the exact intended location of ductwork, piping, 3.02 EXAMINATION testing, adjusting, and balancing. 2.02 GLASS FIBER, FLEXIBLE <br /> or equipment, obtain instructions from the Architect before proceeding with the A. Verify field measurements are as indicated on the Drawings. 2. Provide reports in bound manuals, complete with index page and indexing tabs, A. Insulation: ASTM C 553; flexible, noncombustible blanket. <br /> work. B. Verify all equipment locations prior to rough-in. Maintain adequate equipment with cover identification at front and side. Include set of reduced drawings 1. 'K' value: 0.31 at 75 degrees F, when tested in accordance with ASTM C 518. PROFESSIONAL STAMP of ESS S <br /> C. Notify the Architect for resolution if a discrepancy is discovered within the service clearance per manufacturer and code. with air outlets and equipment identified to correspond with data sheets, and 2. Maximum Service Temperature: 450 degrees F. PR oNq <br /> Contract Documents. Failure of the Contractor to notify the Architect of C. Verify routing of all ductwork and piping in field prior to fabrication or indicating thermostat and equipment locations. 3. Maximum Water Vapor Sorption: 5.0 percent by weight. -,� ROY S <br /> discrepancies shall result in the resolution becoming the Contractor's installation. Verify adequate clearance with structure, light fixtures, and 3. Include actual instrument list, with manufacturer name, serial number, and B. Vapor Barrier Jacket: Q- �'� C�S,1, Fti <br /> responsibility and subject to the Architect's review and possible rejection. ceiling heights. date of calibration. 1. Kraft paper with glass fiber yarn and bonded to aluminized film. /_ C '9� <br /> Should the Architect reject a discrepancy resolution of which they were not D. Verify that proper fuel and power supply is available for connection. 4. Form of Test Reports: Where the TAB standard being followed recommends a 2. Moisture Vapor Permeability: 0.029 ng/Pa s m (0.02 perm inch), when tested Co � m Z <br /> notified, the Contractor is fully responsible to correct the installation, 3.03 INTERFACE WITH OTHER PRODUCTS report format use that; otherwise, follow ASHRAE Std 111. in accordance with ASTM E 96/E 96M. CD No M332 <br /> including all associated costs, until approval of the installation is given by the A. Install all ductwork, pipe, equipment, and accessories to preserve fire resistance 5. Include the following on the title page of each report: 3. Secure with pressure sensitive tape. <br /> Architect. rating of partitions and other elements, using materials and methods specified. a. Name, address and telephone number of Testing, Adjusting, and Balancing C. Vapor Barrier Tape: <br /> 1.06 EXISTING CONDITIONS 3.04 FIELD QUALITY CONTROL Agency. 1. Kraft paper reinforced with glass fiber yarn and bonded to aluminized film, <br /> A. Verify all existing conditions prior to beginning work. A. Provide tests as necessary to establish the adequacy, quality, safety, completed b. Project: Name; location; Engineer; Contractor, Report date. with pressure sensitive rubber based adhesive. s� *CHANIGP� \P <br /> B. Any existing conditions indicated in the Contract Documents are based on status, and suitable operation of each system. Tests shall be conducted under the 1.03 WARRANTY D. Outdoor Vapor Barrier Mastic: I), R_ <br /> information drawings provided by others and possibly limited field verification. supervision of the Architect. A. The Balancing Contractor shall be prepared to return to the site at no additional 1. Vinyl emulsion type acrylic or mastic, compatible with insulation, black F 0 F C A LSF O <br /> The Contractor shall adjust for actual field conditions at no additional expense to 3.05 CLEANING AND REPAIR cost to re-adjust air quantities as required to provide uniform temperatures, color. <br /> the Owner. A. Clean fire suppression parts to remove harmful materials. eliminate drafts and objectionable noises during the first year of occupancy, E. Tie Wire: Annealed steel , 16 gage. <br /> C. The Contractor shall visit the project site, review existing conditions against the B. Clean exposed surfaces of all ductwork pipe, equipment, and accessories of all including one full heating and one full cooling season, after the acceptance of the 2.03 DUCT LINER Date. 02/23/2021 <br /> Contract Documents, and familiarize himself with the work prior to bidding and dirt, debris, splatter, and other deleterious materials. Follow the manufacturer's final balancing report. A. Insulation: Incombustible glass fiber complying with ASTM C 1071; flexible <br /> start of the work. By signing the Contract, the Contractor acknowledges the site recommendations for cleaning as applicable. blanket, rigid board, and preformed round liner board; impregnated surface and <br /> visit has been completed and the existing conditions are accepted. C. Repair or replace damaged ductwork, pipe, equipment, and accessories, as directed PART 2 PRODUCTS - NOT USED edges coated with acrylic polymer shown to be fungus and bacteria resistant by <br /> D. The Contractor shall notify the Architect of major discrepancies in writing so the by and to the satisfaction of the Architect, where marring or disfigurement has testing to ASTM G 21. <br /> appropriate modifications to the design can be made without delay to the project. occurred. All pipe, equipment, and accessories shall be new. PART 3 EXECUTION 1. Apparent Thermal Conductivity: Maximum of 0.31 at 75 degrees F. <br /> The Contractor assumes full responsibility of adjusting for discrepancies of which 3.06 PROJECT CLOSEOUT 2. Service Temperature: Up to 250 degrees F. 0) <br /> the Architect is not informed. A. Project Record Documents: At project closeout, provide one printed copy and one 3.01 GENERAL REQUIREMENTS 3. Rated Velocity on Coated Air Side for Air Erosion: 5,000 fpm, minimum. 0) <br /> 1.07 SUBMITTALS electronic copy of the project record documents to the Owner. Record documents A. Perform total system balance in accordance with one of the following: 4. Minimum Noise Reduction Coefficients: <br /> A. Shop Drawings: will not be reviewed by the Engineer. 1. AABC MN-1, AABC National Standards for Total System Balance. a. 1/2 inch Thickness: 0.30. <br /> 1. Furnish the following submittals to the Architect for review by the Engineer: B. Record Drawings: Information contained on project record drawings shall include, 2. ASHRAE Std 111, Practices for Measurement, Testing, Adjusting and Balancing b. 1 inch Thickness: 0.45. >_ 0 <br /> a. Provide product data and shop drawings for vibration isolation. as a minimum: of Building Heating, Ventilation, Air-Conditioning, and Refrigeration C. 1-1/2 inches Thickness: 0.60. <br /> b. Provide balancing firm qualifications and final test report for 1. Actual locations of all equipment, ductwork, air inlets/outlets, accessories, Systems. d. 2 inch Thickness: 0.70. 3: <br /> 0. <br /> Testing, Adjusting, and Balancing. etc. 3. NEBB Procedural Standards for Testing Adjusting Balancing of Environmental B. Adhesive: Waterproof, fire-retardant type. <br /> C. Provide product data for duct insulation. 2. Actual routing of ductwork with sizes and elevations. Systems. C. Liner Fasteners: Galvanized steel , self-adhesive pad or impact applied with w <br /> d. Provide product data for grease duct fireproofing (if specified). 3. Actual locations of control devices including valves and volume dampers. 4. SMACNA HVAC Systems Testing, Adjusting, and Balancing. integral , or press-on head. ♦�, N <br /> e. Provide product data for HVAC piping insulation. C. Operation and Maintenance Data: Provide descriptive literature, maintenance and B. Begin work after completion of systems to be tested, adjusted, or balanced and V <br /> f. Provide product data and shop drawings for HVAC ductwork. operation data for all hvac equipment, control systems, accessories, and materials complete work prior to Substantial Completion of the Project. PART 3 EXECUTION 06 < � <br /> g. Provide product data for air duct accessories. used. Include maintenance procedures, intervals, and parts list of each item C. Where HVAC systems and/or components interface with life safety systems, including N <br /> h. Provide product data and shop drawings for HVAC power ventilators. installed under this contract. Include all manufacturer's guarantees and fire and smoke detection, alarm, and control , coordinate scheduling and testing and 3.01 INSTALLATION �- L} <br /> i . Provide product data and shop drawings for air outlets and inlets. warranties. inspection procedures with the authorities having jurisdiction. A. UJ Z 0) <br /> j. Provide product data and shop drawings for packaged rooftop units. D. Maintenance Materials: At project closeout, furnish to the Owner the following: D. TAB Agency Qualifications: Insulation Standards. O <br /> 2. Submittals other than those listed above will not be reviewed and will be 1. One set of replacement filters for all hvac equipment. 1. Company specializing in the testing, adjusting, and balancing of systems B. Insulated ducts conveying air below ambient temperature: � Q <br /> returned stating as such. 2. The maintenance contract for the hvac system, if applicable. specified in this Section with a minimum of five years experience. 1. Provide insulation with vapor barrier jackets. uJ 0� � 1 <br /> 3. Shop drawings shall be prepared by a manufacturer's representative, and shall E. Test Reports: Submit to the Owner all testing reports. 2. Certified by one of the following: 2. Finish with tape and vapor barrier jacket. � 2 Q <br /> a. 3. �J <br /> contain names of the manufacturer and cut sheets of equipment to be used on AABC, Associated Air Balance Council; upon completion submit AABC Continue insulation through walls, sleeves, hangers, and other duct <br /> the project. Use manufacturer's specification sheets identified by number END OF SECTION National Performance Guaranty. penetrations. Q Q CD Q <br /> indicated on drawings or schedules. Indicate catalog number on the cut b. NEBB, National Environmental Balancing Bureau. 4. Insulate entire system including fittings, joints, flanges, fire dampers, Z � Q <br /> sheets. As applicable, provide construction data, weight and dimensional <br /> C. TABB, The Testing, Adjusting, and Balancing Bureau of National Energy flexible connections, and expansion joints. � 1: � <br /> data, voltage ratings, performance data, listing data, pump curves, fan SECTION 230548 - VIBRATION AND SEISMIC CONTROLS FOR HVAC PIPING AND EQUIPMENT Management Institute. C. Insulated ducts conveying air above ambient temperature: W0 W O <br /> 3. 1. <br /> curves and sound data as part of the shop drawing submittal . The TAB Agency must be a completely independent, third party balancing Provide with or without standard vapor barrier jacket. <br /> 00 9 <br /> 4. Submittals are reviewed only for general compliance with the Contract PART 1 GENERAL contractor with no financial , common owners or other ties to the installing 2. Insulate fittings and joints. Where service access is required, bevel and __3 __3 <br /> Documents. Dimensions, quantities and details are not checked during contractors. seal ends of insulation. CO O <br /> submittal review. Review of the submittals does not relieve the Contractor 1.01 SECTION INCLUDES E. TAB Supervisor and Technician Qualifications: Certified by same organization as D. External Duct Insulation Application: � � � <br /> of the responsibility for providing all materials, equipment and accessories A. Vibration isolators. TAB agency. 1. Secure insulation with vapor barrier with wires and seal jacket joints with a w 0- T­ 2 <br /> necessary for a complete and operational system meeting the requirements of B. Seismic restraints. 3.02 ADJUSTMENT TOLERANCES vapor barrier adhesive or tape to match jacket. <br /> the project and the intent of the Contract Documents. The responsibility for C. Equipment: A. Air Handling Systems; Air Outlets and Inlets; Hydronic Systems: Adjust to within 2. Secure insulation without vapor barrier with staples, tape, or wires. <br /> coordination of substituted materials and equipment lies solely with the 1. Fans, axial and centrifugal plus or minus 15 percent of design. 3. Install without sag on underside of duct. Use adhesive or mechanical STORE #: 65246 <br /> substituting Contractor. 2. Packaged roof top equipment 3.03 RECORDING AND ADJUSTING fasteners where necessary to prevent sagging. Lift duct off trapeze hangers <br /> 5. Electrical Characteristics: Verify that proper power supply is available 1.02 SUBMITTALS A. Permanently mark settings of valves, dampers, and other adjustment devices allowing and insert spacers. PROJECT#: 88584-00 <br /> prior to ordering equipment. Verify proper voltage, phase and current rating A. Product Data: Provide schedule of vibration isolator type with location and load settings to be restored. Set and lock memory stops. 4. Seal vapor barrier penetrations by mechanical fasteners with vapor barrier <br /> of power supply and inform Engineer of any deviations prior to order, on each. B. Mark on the Drawings the locations where traverse and other critical measurements adhesive. PROFILE TYPE: CORE <br /> connection of equipment or start-up. Responsibility for verification of were taken and cross reference the location in the final report. 5. Stop and point insulation around access doors and damper operators to allow <br /> proper power supply voltage and any product returns or damage resulting from PART 2 PRODUCTS 3.04 AIR SYSTEM PROCEDURE operation without disturbing wrapping. ISSUE DATE: <br /> incorrect connections shall rest with this Contractor. A. Adjust air handling and distribution systems to provide required or design supply, E. Duct and Plenum Liner Application: PROGRAM MANAGER: <br /> B. Test Reports: Provide Testing, Adjusting, and Balancing (TAB) and Commissioning 2.01 MANUFACTURERS return, and exhaust air quantities. 1. Adhere insulation with adhesive for 90 percent coverage. <br /> reports to the Architect for review by the Engineer. All other reports shall be A. Isolation Technology, Inc.; Kinetics Noise Control , Inc.; Mason Industries. B. Make air quantity measurements in ducts by Pitot tube traverse of entire cross 2. Secure insulation with mechanical liner fasteners. Refer to SMACNA HVAC Duct STORE DESIGNER: J. RAMOS <br /> provided to the Owner. 2.02 VIBRATION ISOLATORS sectional area of duct. Construction Standards - Metal and Flexible for spacing. LE E D�AP: N/A <br /> 1.08 QUALITY ASSURANCE A. Restrained Open Spring Isolators: C. Measure air quantities at air inlets and outlets. 3. Seal and smooth joints. Seal and coat transverse joints. <br /> A. Manufacturer Qualifications: Company specializing in manufacturing the Products 1. Springs: Minimum horizontal stiffness equal to 75 percent vertical D. Adjust distribution system to obtain uniform space temperatures free from 4. Seal liner surface penetrations with adhesive. CHECKED BY: G RS <br /> specified in this section with minimum five years experience. stiffness, with working deflection between 0.3 and 0.6 of maximum deflection. objectionable drafts and noise. 5. Duct dimensions indicated are net inside dimensions required for air flow. <br /> B. Installer Qualifications: Company specializing in performing the work of this Color code springs for load carrying capacity. E. Use volume control devices to regulate air quantities only to extend that Increase duct size to allow for insulation thickness. MCG P ROJ ECT#: 20009 <br /> section, with minimum five years experience. 2. Spring Mounts: Provide with leveling devices, minimum 0.25 inch thick adjustments do not create objectionable air motion or sound levels. Effect volume 3.02 SCHEDULES <br /> C. Products: neoprene sound pads, and zinc chromate plated hardware. control by duct internal devices such as dampers and splitters. Do not use A. The Contractor may use any of the following insulating materials, at his option, MCG P ROJ. MANAGER: C.LEE <br /> 1. Listed and classified by Underwriters Laboratories Inc. as suitable for the 3. Sound Pads: Size for minimum deflection of 0.05 inch; meet requirements for diffuser, grille or register integral dampers for balancing adjustments unless the provided the selected material meets with the approval of all State, local MCG P ROJ. SPECIALIST: S. PARK <br /> purpose specified and indicated. neoprene pad isolators. plans do not indicate duct mounted devices. authorities and utility company requirements. Verification of compliance of the <br /> D. All equipment and components shall be free of all rust/corrosion or any visible 4. Restraint: Provide heavy mounting frame and limit stops. F. Vary total system air quantities by adjustment of fan speeds. Provide drive selected insulating material and thickness with all State and local codes and <br /> damage. All items not complying with this requirement shall be replaced without 5. For Exterior and Humid Areas: Hot dipped galvanized housings and neoprene changes required at no additional expense to the Owner. Vary branch air quantities utility company requirements is the sole responsibility of the installing Revision Schedule <br /> any change in the Contract amount. coated springs. by damper regulation. Contractor. <br /> E. Equipment performance and accessories shall be as scheduled on the Drawings and B. Spring Hanger: G. Measure static air pressure conditions on air supply units, including filter and B. Supply air ducts in ceiling spaces: - <br /> specified herein. Inclusion in both locations is not a prerequisite to inclusion 1. Springs: Minimum horizontal stiffness equal to 75 percent vertical coil pressure drops, and total pressure across the fan. Make allowances for 50 1. Flexible Glass Fiber Duct Insulation: 1 1/2 inches thick. Rev Date By Description <br /> in the Contract. Equipment and accessories specified in either location shall be stiffness, with working deflection between 0.3 and 0.6 of maximum deflection. percent loading of filters. 2. Flexible Glass Fiber Duct Liner Insulation: 1 inches thick. <br /> included in the Contract. Provide all necessary accessories and connections as Color code springs for load carrying capacity. H. Adjust outside air automatic dampers, outside air, return air, and exhaust dampers C. Supply, return or exhaust air ducts in crawl spaces, attics or other unconditioned <br /> required for a complete, functional system, including all required components 2. Housings: Incorporate neoprene isolation pad meeting requirements for for design conditions in all operating modes as indicated in the sequence of areas: <br /> reasonably inferred to as necessary although such components may or may not be neoprene pad isolators or rubber hanger with threaded insert. control . 1. Flexible Glass Fiber Duct Insulation: 3 inches thick. <br /> specifically indicated in the Contract Documents. 3. Misalignment: Capable of 20 degree hanger rod misalignment. I. Measure temperature conditions across outside air, return air, and exhaust dampers D. Supply air ducts exposed in finished areas: <br /> F. Code or utility company requirements shall supersede any conflicting requirements 4. For Exterior and Humid Areas: Hot dipped galvanized housings and neoprene to check leakage. 1. Flexible Glass Fiber Duct Liner Insulation: 1 inches thick. <br /> of this section. coated springs. J. Where modulating dampers are provided, take measurements and balance at extreme E. Return or exhaust air ducts exposed in finished areas: None. <br /> 1.09 DELIVERY, STORAGE, AND HANDLING C. Neoprene Pad Isolators: conditions and at all intermediate operating conditions specified in the sequence N <br /> A. Rooftop Equipment: Protect units from physical damage by storing off site until 1. Rubber or neoprene waffle pads. of control . Balance variable volume systems at maximum air flow rate, full END OF SECTION SHEET TITLE: <br /> roof mounting curbs are in place, ready for immediate installation of units. a. Hardness: 30 durometer. cooling, and at minimum air flow rate, full heating. <br /> B. Protect insulation from weather and construction traffic, dirt, water, chemical , b. Thickness: Minimum 1/2 inch. 3.05 SCOPE <br /> and mechanical damage, by storing in original wrapping. <br /> C. Maximum Loading: 50 psi . A. Equipment Requiring Testing, Adjusting, and Balancing (if present on the project): SECTION 233100 - HVAC DUCTS AND CASINGS HVAC SPECIFICATIONS <br /> C. Protect dampers and accessories from damage to operating linkages, blades and d. Rib Height: Maximum 0.7 times width. 1. HVAC Pumps; Boilers; All Air Handling Equipment; All Packaged Heating and/or 4 <br /> finishes. 2. Configuration: Single layer. Cooling Equipment; All Coil; All Heat Exchangers; Terminal Heat Transfer PART 1 GENERAL N <br /> D. Provide temporary end caps and closures on piping and fittings. Maintain in place D. Rubber Mount or Hanger: Molded rubber designed for 0.4 inch deflection with Units; Air Terminal Units; Air Inlets and OutletsO SCALE:AS SHOWN <br /> until installation. threaded insert. 3.06 MINIMUM DATA TO BE REPORTED 1.01 SECTION INCLUDES <br /> E. Protect motors stored on site from weather and moisture by maintaining factory E. Glass Fiber Pads: Neoprene jacketed pre-compressed molded glass fiber. A. Report (as applicable to the project): A. Metal ductwork. Schnackel <br /> SHEET NUMBER: <br /> engineers, <br /> M-0002 <br /> 8E JOBM 200472 <br />