Laserfiche WebLink
AECOM <br />5. Leach Field Sizing <br />Leach field pipe length is sized per OWTS Standard section 9.7.2 for non-standard OWTS design. <br />Leach Line Length = (BCT + ADF) x Soil Factor <br />Soil factors are defied per Table 9.7.2, which is referenced as Table 2 below. <br />Table 3. Soil Factor Values per OWTS Standard 9.7.2 <br />Soil <br />Soil Factor <br />Clay and/or Peat <br />0.25 <br />Silt and/or Sandy Clay Loam <br />0.225 <br />Sand and/or Sandy Loam <br />0.2 <br />BSK prepared a Limited Geotechnical Investigation Report (E21-002-01 B) dated February 26, 2021 <br />that states that the soil type is sandy clay loam. Using that information, the leach line length is <br />calculated as: <br />Required Leach Line Length = (1,200 + 4,200) x 0.225 = 1,215 feet <br />Per Section 9.4.1 the maximum length of individual leach lines is 100 feet. Per Section 9.4.5 leach <br />lines must have a clear spacing of 10 feet. Because of this it is proposed that 8 leach lines will be <br />used where 5 lines are 100 feet long and 3 lines are 88 feet long. Seven 60 -inch diameter seepage <br />pits are proposed at the end of seven of the leach lines. Per Section 9.9.8 each 60 -inch diameter pit <br />is equivalent to 84 feet of leach line. Per Section 9.9.10 seepage pits cannot be closer than 10 feet <br />edge to edge. Thus, the total leach lines are proposed to be: <br />5 lines x 100 feet per line = 500 feet <br />3 lines x 88 feet per line = 264 feet <br />7 60 -inch diameter seepage pits x 84 feet per pit = 588 feet <br />Total Provided Leach Line Length 1,352 feet <br />6. Sewer Pumps <br />Per the OWTS Standard section 9.4, the maximum depth of leach lines is 42 -inches. The longest <br />distance between the commercial buildings and the septic tank is 266 feet. The minimum slope for <br />sewer laterals is 2% per the California Plumbing Code 718.1. Assuming that the lateral invert at the <br />building is 24 -inches below top of grade and that the lot is generally flat, the invert at the septic tank <br />would be 7.3 feet. Because this depth exceeds the 42 -inch limit, a sewer lift station is required. <br />Table 4 provides a summary of fixture unit calculations. Data is taken from the California Plumbing <br />Code Table A 103.1 for Water Supply Fixture Units. <br />