Laserfiche WebLink
2482 East Carpenter Road, Stockton <br />APN 17914018, PA -1900132, SR0084253 <br />November 12, 2021 <br />Page 2 <br />5. Written OWTS Operations and Maintenance Plan (O/M Plan) was not included in the Design. <br />All engineered designed OWTS shall be operated and maintained pursuant to an O/M Plan <br />compiled by the OWTS designer SJC OWTS Standards 1.12.1) Provide O/M Plan to EHD <br />for approval (SJC OWTS Standards 1.12.3). The O/M Plan shall include the following: <br />- Monitoring, sampling, and reporting requirement based the OWTS design parameters <br />(SJC OWTS Standards 2.10.2) <br />- Regular monitoring by a certified sewage plant operator is required SJC OWTS <br />Standards 7.12). Analysis required should be based on the O/M Plan and OWTS design <br />parameters. <br />6. An Annual Operating Permit is required for the engineered OWTS (SJC OWTS 2.10.1- <br />2.10.3). <br />Note: OWTS inspections based on this Annual Operation Permit will be at least two times <br />per year (SJC OWTS Standards 2.10.3) <br />7. Abandoned the three existing septic tanks under permit and inspection by this department. <br />(SJC OWTS Standards 4.6) <br />If you have any questions or comments you may reach Aaron Gooderham, REHS, at <br />agooderham(a--)siaov.org or (209) 616-3062. <br />A4��t UV <br />-�' <br />- Or Steven Shih, REHS <br />Program Coordinator <br />CC: AECOM attn.: Daniel Cronquist <br />5001 E. Commercenter Dr., suite 100 <br />Bakersfield, CA 93309 <br />2 of 2 <br />