Laserfiche WebLink
Underground Storage Tank <br /> Secondary Containment Testing Report Form <br /> 8. SUMP/UDC TEST <br /> Test Method Developed by © Manufacturer ❑Q Industry Standard El Professional Engineer <br /> Test Type © Pressure Q Vacuum E Hydrostatic <br /> Test Equipment Used: ancon TS-STS <br /> Sump/UDC ID 87-1 STP 87-2 STP 91 STP <br /> Sump Manufacturer Unknown (FRP) Unknown (FRP) Unknown (FRP) <br /> Sump Depth (inches) 42 41 39 <br /> Sump Bottom to Top of 11 10 9 <br /> Highest Pipe Penetration <br /> (inches) <br /> Test Start Time 10:23 10:44 11:02 <br /> Initial Reading 5.3591 3.7549 6.6508 <br /> Test End Time 10:38 10:59 11:18 <br /> Final Reading 5.3574 3.7558 6.6489 <br /> Change in Reading -0.0017 0.0009 -.0019 <br /> Pass Fail Criteria +/-0.002 +/-0.002 +/- 0.002 <br /> Tightness Test Results El Pass rl Fail © Pass rl Fail r Pass © Fail [Cl Pass ❑l Fail <br /> Sump/UDC ID UDC#1-2 UDC#3-4 <br /> Sump Manufacturer Bravo (Steel) Bravo (Steel) <br /> Sump Depth (inches) 9 9 <br /> Sump Bottom to Top of Bottom Bottom <br /> Highest Pipe Penetration <br /> (inches) <br /> Test Start Time 10:23 12:11 <br /> Initial Reading 0.2834 0.0744 <br /> Test End Time 10:38 12:26 <br /> Final Reading 0.2820 0.0732 <br /> Change in Reading -0.0014 -0.0012 <br /> Pass Fail Criteria +/-0.002 +/-0.002 <br /> Tightness Test Results © Pass 0 Fail © Pass 0 Fail r] Pass © Fail C Pass C Fail <br /> Additional copies of this page may be attached. <br /> All tests marked "Fail"and any repairs made before or during the tightness test must be described in <br /> the COMMENTS section. <br /> Page 3of5 <br />