Laserfiche WebLink
SA N J O A n I I I N Environmental Health Department <br /> COUNTY <br /> E. UNDERGROUND STORAGE TANK(S): <br /> TANK# # 1 # 2 # 3 it <br /> CAPACITY 30k 15k split 15k (split) <br /> MANUFACTURER Xerxes Xerxes Xerxes <br /> MODEL XE-30000 XE-30000 Split XE-30000 Splitjj <br /> COMPOSITION Fiberglass Fiberglass Fiberglass <br /> PRODUCT Reg. Unleaded rem. Unleaded Diesel <br /> Check Code <br /> Box Section <br /> HSC* <br /> ❑ 25290.1(c)(1) Tank(s) compatible with the substance to be stored. <br /> 25290.2(c)(1) <br /> 23 CCR** Design and construction of tank(s) and all other components used to construct primary <br /> 0❑ 2631(b) containmentsystem(s) approved by independent testing organization (e.9� UL). <br /> 23 CCR <br /> X❑❑ 2631(a) Secondary Containment Provided for Underground Storage Tanks. <br /> X❑ Buoyancy Calculations submitted and signed by a Professional Engineer which <br /> demonstrates a safety factor greater than 1.25. <br /> F. SYSTEM PIPING: <br /> Primaty <br /> PIPING MANUFACTURER MODEL ---][COMPOSITION <br /> PRODUCT PIPING NOV Fiberglass Systems 011020-069-1 Rigid Fiberglass <br /> VAPOR PIPING NOV Fiberglass Systems 011030-069-1 Rigid Fiberglass <br /> VENT PIPING NOV Fiberglass Systems 011020-069-1 Rigid Fiberglass <br /> Secondaty <br /> PIPING ::] MANUFACTURER MODEL COMPOSITION <br /> PRODUCT PIPING NOV Fiberglass Systems 011030-069-1 Rigid Fiberglass <br /> VAPOR PIPING NOV Fiberglass Systems 011040-069-1 Rigid Fiberglass <br /> VENT PIPING NOV Fiberglass Systems 011030-069-1 Rigid Fiberglass <br /> *HSC-Health and Safety Code <br /> **23 CCR-Code of California Regulations <br /> 6 of 8 <br />