Laserfiche WebLink
Attachment 3 <br /> Summary of the Configuration of the Pipeline System ( s ) <br /> Used in the Evaluation <br /> Options 1, 2, and 5 <br /> Pipeline Leak Detection System for Annual , Monthly and Hourly Testing <br /> Specialized Test Facility, Operational Storage Tank System, or Computer Simulation <br /> Inside diameter of pipeline (in . ) Range from 1 . 5 in to 4 in * <br /> Length of pipeline (tank to dispenser) (ft) 2 2533 ft <br /> Volume of product in line during testing (gal ) 3 589 . 34 <br /> Type of material (fiberglass, steel, other') Rigid ( FRP), Semi- Rigid and Flex <br /> Type of product in tank and pipeline (gasoline, diesel, others) #2 Diesel fuel <br /> Was a mechanical line leak detector present? (yes or no) No <br /> Was trapped vapor present? (yes or no) yes <br /> Bulk Modulus ( B) ( psi ) 17, 052 psi <br /> B/V ( psi/ml ) 0.0077 psi/ml <br /> Storage tank capacity (gal ) 600 gal <br /> 'Specify for each section of pipe, if different. <br /> 2Specify length of each section of pipe, if different size or material . <br /> 3Specify volume for each section of pipe, if different size or type . <br /> #Specify type of construction material for each pipe section . <br /> 'Specify type of product for each tank. <br /> 8 <br />