Laserfiche WebLink
Results Of U. S . EPA Standard Evaluation <br /> Pipeline Release Detection Method <br /> Hourly Test <br /> This form summarizes the results of an evaluation to determine whether the pipeline release detection <br /> method named below and described in Attachment 1 complies with the federal UST regulation for <br /> conducting an hourly test . The evaluation was conducted according to the U . S . EPA ' s evaluation <br /> procedures , specified in Standard Test Procedures for Evaluating Release Detection Methods : Pipeline <br /> Release Detection . The full evaluation report includes six attachments . <br /> UST system owners and operators who use this pipeline release detection method should keep this form <br /> on file to show compliance with the federal UST regulation . UST system owners and operators should <br /> check with state and local regulatory authorities to make sure this form satisfies the requirements of their <br /> agencies . <br /> Method Evaluated <br /> Method Name : Pneumercator LLP-203 Series PLLD <br /> Version of Method : Pneumercator LLP-203 Series PLLD for use with TMS2000 TMS3000 and TMS4000 series <br /> consoles <br /> Vendor Pneumercator <br /> 1785 Expressway Drive North <br /> (Address) <br /> Hauppauge NY 11788 (631 ) 293 - 8450 <br /> (City) ( State) (Zip Code) (Phone) <br /> Evaluation Results <br /> L The performance of this method <br /> X meets or exceeds <br /> _ does not meet the federal standards established by the EPA regulation for hourly tests . <br /> The EPA regulation for an hourly test requires that the method be capable of detecting a leak as small as <br /> 3 . 0 gal/hr with a probability of detection (P(d)) of 95% and a probability of false alarm (P(fa)) of 5 % . <br /> 2 . The estimated P(fa) in this evaluation isO%% and the estimated P(d) against a leak rate of 3 . 0 gal/hr <br /> defined at a pipeline pressure of 10 psi in this evaluation is 100 % . <br /> Pipeline Release Detection System Page 2 <br />