Laserfiche WebLink
Pneumercator Non - Discriminating <br /> Liquid Float-Switch Sensors <br /> with no false alarms or missed detections . The response and fall times are immediate <br /> ( less than 1 second ) after the liquid level rises above the threshold level for wired <br /> systems , and less than 65 seconds for wireless systems . <br /> Table 2 . Test Results for the LS600 Series Liquid Float-Switch Sensor <br /> Run No . Product Type <br /> Water Unleaded Diesel <br /> Gasoline <br /> Height to Height to Height to <br /> Alarm ( in ) Alarm ( in ) Alarm ( in ) <br /> 1 3 . 17 3 . 29 3 . 27 <br /> 2 3 . 17 3 . 29 3 . 27 <br /> 3 3 . 17 3 . 29 3 . 27 <br /> 4 3 . 16 3 . 30 3 . 27 <br /> 5 3 . 17 3 . 30 3 . 27 <br /> 6 3 . 17 3 . 30 3 . 27 <br /> Mean ( in ) 3 . 17 3 . 29 3 . 27 <br /> Accuracy 100 100 100 <br /> Threshold ( in ) 3 . 18 3 . 32 3 . 28 <br /> Precision ( Std Dev) 0 . 0037 0 . 0051 0 . 0025 <br /> Detection Time <br /> Wired Systems < 1 sec < 1 sec < 1 sec <br /> Wireless Systems < 65 sec < 65 sec < 65 sec <br /> Fall Time <br /> Wired Systems < 1 sec < 1 sec < 1 sec <br /> Wireless Systems < 65 sec < 65 sec < 65 sec <br /> Page 6 of 8 <br />