21204145 . 5 <br /> by <br /> 0 <br /> Line Leak Detector Test Data Sheet <br /> Station # Arco 7092 Date $122 2022 <br /> Address 2510 S. Hwy 99, Stockton, CA 95205 <br /> Test Information <br /> 1 2 3 4 5 <br /> Product 67 91 DSL DSL DSL <br /> Manufacturer VR VR VR VR VR <br /> Model 848480 848480 848480 848480 848484 <br /> Full Operating Pressure (psi) 34 34 33 36 36 <br /> Line Bleed Back(ml) NA NA NA NA NA <br /> Trip Time (sec) NA NA NA NA NA <br /> Metering Pressure (psi) NA NA NA NA NA <br /> F/E Holding Pressure(psi) 21 20 21 22 NA <br /> Test Leak Rate (ml/min)(gph) 189ML 189ML 189ML 18 9ML 189ML <br /> PASS or FAIL PASS PASS PASS PASS PASS <br /> Comments: <br /> This letter certifies that the annual leak detector tests were performed at the above referenced facility <br /> according to the equipment manufacturers procedures and limitations and the results as listed are to my <br /> knowledge true and correct. The mechanical leak test detector test pass'fail is determined using a low <br /> flow threshold trip rate of 3 gph at 10 PSI. <br /> Inspected By: Contractor Gettler-Ryan Inc. <br /> Technician Robert Jacobs Lic#220793 <br /> Signature <br />