Laserfiche WebLink
Underground Storage Tank <br /> Overfill Prevention Equipment Inspection Report <br /> 6. OVERFILL PREVENTION EQUIPMENT DETAILS <br /> Tank ID (one OPE per column) DSL 1 west DSL z East <br /> Are both vent and tank riser piping �/ Yes �/ Yes Yes Yes <br /> secondarily contained? No No No No <br /> OPE Model OPw 7120 OPw Tisa <br /> What is the OPE response when activated? 21 Shut off �/ Shut off Shut off Shut off <br /> (Check all that apply.) Flow Flow Flow Flow <br /> estricts estricts estricts Restricts <br /> Flow Flow Flow Flow <br /> Audible Audible Audible Audible <br /> Alarm Alarm Alarm Alarm <br /> Visual Visual Visual Visual <br /> Alarm Alarm Alarm Alarm <br /> Are flow restrictors installed on vent piping Yes* Yes* Yes* Yes* <br /> that may interfere with the OPE operation? ✓ No �/ No HNo No <br /> At what level in the tank is the OPE set to <br /> activate? Inches from bottom of tank) 102 3/4M ias 3/4- <br /> What is the percent capacity of the tank at <br /> which the OPE activates? 92 °2� 92.02% <br /> Is the OPE in proper operating condition to r/ Yes A Yes Yes Yes <br /> respond when the stored substance No No No No <br /> reaches the designated regulatory level? <br /> 7. SUMMARY OF TESTING RESULTS <br /> OPE Inspection Results / Pass v/ Pass Pass Pass <br /> Fail Fail Fail Fail <br /> 8. COMMENTS <br /> Describe all results marked "Fail"and each proposed remedy. <br /> * Mark here if: <br /> 17 Flow restrictors interfere with overfill prevention and equipment repairs required. <br /> Additional copies of this page may be attached <br /> Attach tank chart(s), measurements, calculations and In-Tank Setup report(s) <br /> Page 2of2 <br />