Laserfiche WebLink
2.3. An application for a permit is required for the elimination of a cross-connection at <br /> the well discharge. <br /> 2.4. The approved permit shall be good for one (1) year from date of issue. Extension <br /> may be granted by the Director for one additional year. <br /> 2.5 Prior to initiating work, the approved permit shall be available onsite until final <br /> inspection. <br /> 2.6 Special Water Well Permits may be issued for wells that do not meet these <br /> Standards. <br /> 2.6.1. Request for Special Water Well Permit shall state the conditions for the <br /> request. <br /> 2.6.2. Each Special Water Well Permit shall be reviewed on an individual basis. <br /> 3. LOCATIONS <br /> 3.1. All water wells (excluding monitoring wells) shall be located at an adequate <br /> horizontal distance from potential sources of contamination and pollution. <br /> THE FOLLOWING MINIMUM DISTANCES SHALL BE MAINTAINED: <br /> Public Water <br /> Systems Lots Recorded Lots Recorded <br /> Wells AFTER 1972* BEFORE 1972* <br /> Property Line 25 ft loft loft <br /> Septic Tank 100 ft 50 ft 50 ft <br /> Sewer Line-Cast Iron 50 ft 50 ft 50 ft <br /> Stream, Creek, River, Canal 50 ft 50 ft 50 ft <br /> Disposal Field 100 ft 100 ft 50 ft <br /> Seepage Pit, Sumps >8' Depth 150 ft 150 ft 100 ft <br /> Leaching Sump <8' Depth 100 ft 100 ft 50 ft <br /> Livestock Corrals or Fowl Enclosures 100 ft 100 ft 50 ft <br /> Underground Hazardous Materials Storage <br /> Tanks Excluding natural gas and propane 150 ft 100 ft - <br /> Aboveground Hazardous Materials Storage <br /> Containers 100 ft 50 ft - <br /> *LOTS RECORDED PRIOR TO DECEMBER 15, 1972 <br /> EHD 43-03 Page 9 of 27 WELL STANDARDS <br /> 10/9/07 <br />