Laserfiche WebLink
SAN J 0 A Q I I I Irl Environmental Health Department <br /> CCUNT <br /> Aboveground Petroleum Storage Act Inspection Report <br /> Facility Name: Facility Address: Date: <br /> MID VALLEY AG SERVICES INC 1 16401 E HWY 26 , LINDEN November 14, 2022 <br /> SUMMARY OF VIOLATIONS <br /> (CLASS I,CLASS II,or MINOR-Notice to Comply) <br /> Item# Remarks <br /> 203 CFR 112.3 Failure to implement the SPCC Plan. <br /> OBSERVATION: The Spill Prevention, Control, and Countermeasure(SPCC)Plan was not implemented, as <br /> required. <br /> -Per Section 5 Inspections,Tests and Records, of the SPCC plan, "regular inspections of the storage containers, <br /> oil-containing equipment, and related secondary containment structures must be performed and documented <br /> according to the written procedure/record of inspection of the type provided in Appendix F." Appendix F shows the <br /> requirement of a weekly inspections. Per Branch Manager Tom Boster,weekly inspections are not conducted on <br /> the tanks. <br /> -Per section 8.2 Disconnection of Transfer Lines,of the SPCC plan, "tanker truck loading/unloading procedures in <br /> Appendix C must be posted at the loading and unloading areas." The procedures outlined in appendix C were not <br /> observed in the loading and unloading areas. <br /> REGULATION GUIDANCE: 112.3: The owner or operator or an onshore or offshore facility subject to this section <br /> must prepare in writing and implement a Spill Prevention Control and Countermeasure Plan (hereafter"SPCC Plan" <br /> or"Plan")," in accordance with § 112.7 and any other applicable section. 25270.4.5.(a):An owner or operator shall <br /> conduct periodic inspections of the storage tank to ensure compliance with Part 112 (commencing with Section <br /> 112.1)of Subchapter D of Chapter I of Title 40 of the Code of Federal Regulations. In implementing the spill <br /> prevention control and countermeasure plan, an owner or operator shall fully comply with the latest version of the <br /> regulations contained in Part 112(commencing with Section 112.1)of Subchapter D of Chapter I of Title 40 of the <br /> Code of Federal Regulations. <br /> CORRECTIVE ACTION: Implement the SPCC plan, as required. Submit proof of correction to the EHD. The facility <br /> posted the procedure outlined in Appendix C at the loading and unloading areas during the inspection. <br /> This is a repeat violation, Class II. <br /> FA0009357 PR0528828 SCO01 11/14/2022 <br /> EHD 28-01 Rev.12/06/2021 Page 5 of 10 Aboveground Petroleum Storage Act OIR <br /> 1868 E. Hazelton Avenue I Stockton, California 95205 1 T 209 468-3420 1 F 209 464-0138 1 www.sjgov.org/EHD <br />