Laserfiche WebLink
FLEX CONDUIT <br />FOR FIELD <br />WIRING. <br />13 1/4" <br />11 1/2" <br />BLOWER DISCHARGE. <br />CURB. <br />1 3/4" <br />3 7/8" <br />3 3/4" <br />LIFTING LUG. <br />AIRFLOW. <br />BLOWER/MOTOR <br />ACCESS DOOR <br />24" SERVICE <br />CLEARANCE REQ. <br />SERVICE <br />DISCONNECT <br />SWITCH. <br />AIRFLOW. <br />18" <br />16" <br />Ø1 1/2" <br />WATER <br />DRAIN. <br />AIRFLOW. <br />Ø1/2" NPT <br />WATER INLET <br />WATER FILTER REQUIRED <br />PROVIDED BY PLUMBER. <br />FILTER/CONTROL <br />ACCESS DOOR. <br />LPD CELDEK AIRFLOW. <br />27 3/8" <br />11 1/4" <br />21" <br />15" EQUIPMENT CURB. <br />32 1/8" <br />29 3/4" <br />21" <br />32 1/8" <br />36 3/4" <br />36 3/4" <br />ADJUSTABLE <br />LEG. <br />64 1/4" <br />117 7/8" <br />MIN. 14" <br />MINIMUM <br />STRAIGHT <br />DUCT <br />PER AMCA* <br />FAN #2 A1-15D - SUPPLY FAN <br />1. UNTEMPERED SUPPLY UNIT WITH 15" MIXED FLOW DIRECT DRIVE FAN IN SIZE #1 HOUSING. <br />2. EVAP COOLER (LPD CELDEK) – W/INTAKE HOOD W/EZ FILTERS. <br />3. DOWN DISCHARGE - AIR FLOW RIGHT -> LEFT. <br />4. 120V WIRING CONNECTION TO ENERGIZE EVAPORATIVE COOLERS FROM UNTEMPERED SUPPLY FANS. <br />5. ECM WIRING PACKAGE MODBUS CONTROL FOR SUPPLY EC MOTORS. MSC CONTROLLER. **DO NOT ORDER UNDER WARRANTY, SEE PART NUMBER "CAS <br />MSC**. <br />6. HINGED DOUBLE WALL INSULATED DOOR ASSEMBLY (BURNER/BLOWER/EVAP SECTION). <br />7. 2 YEAR PARTS WARRANTY. <br />*NOTE: SUPPLY DUCT MUST BE INSTALLED TO MEET SMACNA STANDARDS. A MINIMUM STRAIGHT DUCT LENGTH MUST BE MAINTAINED DOWNSTREAM OF <br />UNIT DISCHARGE AS OUTLINED IN AMCA PUBLICATION 201. WHEN USING RECTANGULAR DUCTWORK, ELBOWS MUST BE RADIUS THROAT, RADIUS BACK WITH <br />TURNING VANES. FLEXIBLE DUCTWORK AND SQUARE THROAT/SQUARE BACK ELBOWS SHOULD NOT BE USED. ANY TRANSITION AND/OR TURNS IN THE <br />DUCTWORK WILL CAUSE SYSTEM EFFECT. SYSTEM EFFECT WILL DRASTICALLY INCREASE STATIC PRESSURE AND REDUCE AIRFLOW. DO NOT RELY ON UNIT <br />TO SUPPORT DUCT IN ANY WAY. FAILURE TO PROPERLY SIZE DUCTWORK MAY CAUSE SYSTEM EFFECTS AND REDUCE PERFORMANCE OF THE EQUIPMENT. <br />SUGGESTED STRAIGHT DUCT SIZE IS 14" x 14". <br />L ETS DI <br />R <br />ROOF OPENING 2" SMALLER THAN CURB DIMENSION. <br />EXAMPLE: 7/12 PITCH = 30° SLOPE. <br />PITCHED CURBS ARE AVAILABLE <br />FOR PITCHED ROOFS. <br />SPECIFY PITCH: <br />0" <br />0° <br />12" <br />5" <br />5" <br />SHEET NO. <br />SCALE: <br />DWG.#: <br />DRAWN <br />DATE: <br /> BY: <br />REVISIONS <br />www.captiveaire.com ACCORDANCENo. 96BUILTNFPAWITHINSLIDTER4996088 <br />MASTER DRAWING <br />AH-86Mountain Mike's Pizza - Mountain House CAMountain House, CA, 95391Southern California Office3002 Dow Ave., Suite 410, Tustin, CA, 92780 PHONE: (714) 957-1500 FAX: (919) 227-5975 EMAIL: reg86@captiveaire.comCAPTIVEAIRE DRAWINGS <br />M-4.3 <br />PRINTED DATE: 07-21-2021PROJECT NAME/ADDRESS: <br />STAMP <br />@Mountain House <br />ARCHITECT <br />ARCH PROJECT #: <br />JOB NUMBER <br />DRAWN BY <br />SHEET CONTENT <br />SHEET NO <br />ISSUE DATE: <br />REVISIONS: <br />EM <br />21-___ <br />CHECK BY <br />ADR <br />ARCHITECTURE <br />GWA <br />1000 Corporate Center Drive <br />Suite 550 <br />Monterey Park, CA 91754 <br />tel: (626) 288-6898 <br />Member of The American Institute of Architects <br />REN. 04-30-2023