Laserfiche WebLink
SAN JOAQUIN <br /> Environmental Health Department <br />I Y <br /> AMENDED <br />6/22/2022 <br />Aboveground Petroleum Storage Act Inspection Report <br />Facility Name: <br />J & L MARKET <br />Facility Address: <br />8115 S EL DORADO ST, FRENCH CAMP <br />Date: <br />May 23, 2022 <br />SUMMARY OF VIOLATIONS <br />(CLASS I, CLASS II, or MINOR - Notice to Comply) <br />Item # Remarks <br />706 CFR 112.8(c)(2) Failed to provide and maintain adequate secondary containment for bulk storage tanks. <br />OBSERVATION: The facility failed to provide and maintain secondary containment for bulk storage tank installations <br />sufficient to hold the capacity of the largest container, including adequate freeboard for precipitation. Per the July <br />13, 2019 inspection report, Professional Engineer certified secondary containment calculations dated 08/ 09/2011 <br />stated that the secondary containment for the 10, 000 tank only holds 6, 942 gallons. Since the tank capacity is <br />10,000 gallons, the amount in the secondary containment appears to be not enough to hold the entire capacity of <br />the tank and sufficient freeboard to contain precipitation. Dark oily staining was observed around the secondary <br />containment. <br />REGULATION GUIDANCE: (c)(2)Construct all bulk storage tank installations (except mobile refuelers and other <br />non-transportation-related tank trucks) so that you provide a secondary means of containment for the entire capacity <br />of the largest single container and sufficient freeboard to contain precipitation. You must ensure that diked areas are <br />sufficiently impervious to contain discharged oil. Dikes, containment curbs, and pits are commonly employed for this <br />purpose. You may also use an alternative system consisting of a drainage trench enclosure that must be arranged <br />so that any discharge will terminate and be safely confined in a facility catchment basin or holding pond. <br />CORRECTIVE ACTION: Immediately provide and maintain adequate secondary containment for the 10,000 gallon <br />diesel bulk storage tank. Submit proof of correction to the EHD. <br />This is a Class II violation. <br />FA0000110 PR0516364 SC001 05/23/2022 <br />EHD 28-01 Rev. 12/06/2021 Page 8 of 10 Aboveground Petroleum Storage Act OIR <br />1868 E. Hazelton Avenue I Stockton, California 95205 I T 209 468-3420 I F 209 464-0138 I www.sjgov.org/EHD