SAN JOAQUIN
<br /> Environmental Health Department
<br />- COUN -1 Y
<br /> AMENDED
<br />6/22/2022
<br />Aboveground Petroleum Storage Act Inspection Report
<br />Facility Name:
<br />J & L MARKET
<br />Facility Address:
<br />8115 S EL DORADO ST, FRENCH CAMP
<br />Date:
<br />May 23, 2022
<br />SUMMARY OF VIOLATIONS
<br />(CLASS I, CLASS II, or MINOR - Notice to Comply)
<br />Rem # Remarks
<br />713 CFR 112.7(e), 112.8(c)(6) Failed to test or inspect each container for integrity based on industry standards.
<br />OBSERVATION: Per Owner Karina Valdez, testing/inspections have not been conducted on the 10,000 gallon
<br />aboveground diesel tank for integrity based on industry standards.
<br />REGULATION GUIDANCE: REGULATION GUIDANCE: 112.8(c)(6) Test or inspect each aboveground container
<br />for integrity on a regular schedule and whenever you make material repairs. You must determine, in accordance
<br />with industry standards, the appropriate qualifications for personnel performing tests and inspections, the frequency
<br />and type of testing and inspections, which take into account container size, configuration, and design (such as
<br />containers that are: shop-built, field-erected, skid-mounted, elevated, equipped with a liner, double-walled, or
<br />partially buried). Examples of these integrity tests include, but are not limited to: visual inspection, hydrostatic
<br />testing, radiographic testing, ultrasonic testing, acoustic emissions testing, or other systems of non-destructive
<br />testing. You must keep comparison records and you must also inspect the container's supports and foundations. In
<br />addition, you must frequently inspect the outside of the container for signs of deterioration, discharges, or
<br />accumulation of oil inside diked areas. Records of inspections and tests kept under usual and customary business
<br />practices satisfy the recordkeeping requirements of this paragraph.
<br />112.7(e) Inspections, tests, and records. Conduct inspections and tests required by this part in accordance with
<br />written procedures that you or the certifying engineer develop for the facility. You must keep these written
<br />procedures and a record of the inspections and tests, signed by the appropriate supervisor or inspector, with the
<br />SPCC Plan for a period of three years. Records of inspections and tests kept under usual and customary business
<br />practices will suffice for purposes of this paragraph.
<br />CORRECTIVE ACTION: Immediately conduct the necessary integrity testing and inspections on the 10,000 gallon
<br />aboveground storage tank based on industry standards, on a regular schedule. Maintain testing and inspection
<br />records. Submit a copy of the test/ inspection results to the EHD.
<br />This is a Class II violation.
<br />Overall Inspection Comments:
<br />An inspection checklist was provided to the facility operator on May 24, 2022. The checklist was amended.
<br />Violation 102 was removed and violations 103, 110, 112, 202, 619, 620, 705, 706, and 713 were added.
<br />A complete report was finished on June 22, 2022 and replaces the initial checklist.
<br />Complete and submit a copy of the Return to Compliance Certification form to the EHD with a statement
<br />documenting the corrective actions that have been or will be taken for each violation, and any supporting
<br />paperwork, by July 22, 2022.
<br />To minimize person to person contact EHD is choosing to write the name of person receiving the report instead
<br />of having them sign. Starting September 1, 2018, all in-office CERS help will be provided at END hourly rate
<br />($152). To schedule an appointment, please call (209) 468-3420.
<br />The following was observed during this inspection: one 10,000 gallon diesel tank
<br />The following was provided during this inspection: Schedule of free CUPA classes, SP001 monthly and annual
<br />FA0000110 PRO516364 SC001 05/23/2022
<br />EHD 28-01 Rev. 12/06/2021
<br />Page 9 of 10
<br /> Aboveground Petroleum Storage Act OIR
<br />1868 E. Hazelton Avenue I Stockton, California 95205 I T 209 468-3420 I F 209 464-0138 I www.sjgov.org/EHD
|