Laserfiche WebLink
Underground Storage Tank <br /> Secondary Containment Testing Report Form <br /> 8. SUMP/UDC TEST <br /> Test Method Developed by ❑ Manufacturer ❑ Industry Standard X Professional Engineer <br /> Test Type ❑ Pressure ❑ Vacuum X Hydrostatic <br /> Test Equipment Used: Caldwell Level Change Indicator <br /> Sump/UDC ID 1-87-PS 2-87-PS 3-91-PS <br /> Sump Manufacturer XERXES XERXES XERXES <br /> Sump Depth (inches) 45" 48" 49" <br /> Sump Bottom to Top of 15" 16" 16" <br /> Highest Pipe Penetration <br /> (inches) <br /> Test Start Time 8:42 8:47 9:32 <br /> Initial Reading .001 .001 .001 <br /> Test End Time 9:12 9:17 10:02 <br /> Final Reading .001 .001 .001 <br /> Change in Reading 0 0 0 <br /> Pass/Fail Criteria > .002 > .002 > .002 <br /> Tightness Test Results X Pass ❑ Fail X Pass ❑ Fail X Pass ❑ Fail ❑ Pass ❑ Fail <br /> Sump/UDC ID UDC 1&2 UDC 3&4 UDC 5&6 UDC 7&8 <br /> Sump Manufacturer Western FG Western FG Western FG Western FG <br /> Sump Depth (inches) 32" 32" 32" 32" <br /> Sump Bottom to Top of 11" 11" 11" 11" <br /> Highest Pipe Penetration <br /> (inches) <br /> Test Start Time 8:52 8:57 9:42 9:47 <br /> Initial Reading .001 .001 .001 .001 <br /> Test End Time 9:22 9:27 10:12 10:17 <br /> Final Reading .001 .001 .001 .001 <br /> Change in Reading 0 0 0 0 <br /> Pass/Fail Criteria > .002 > .002 > .002 > .002 <br /> Tightness Test Results X Pass ❑ Fail X Pass ❑ Fail X Pass ❑ Fail X Pass ❑ Fail <br /> Additional copies of this page may be attached. <br /> All tests marked "Fail"and any repairs made before or during the tightness test must be described in <br /> the COMMENTS section. <br /> Page 3 of 5 <br />