Laserfiche WebLink
Underground Storage Tank <br /> Secondary Containment Testing Report Form <br /> 8. SUMP/UDC TEST (continued) <br /> Test Method Developed by ❑ Manufacturer ❑ Industry Standard ® Professional Engineer <br /> Test Type ❑ Pressure ❑ Vacuum ® Hydrostatic <br /> Test Equipment Used: Caldwell Level Change Indicator <br /> Sump/UDC ID UDC 9&10 UDC 11&12 UDC 13&14 UDC 15&16 <br /> Sump Manufacturer Western FG Western FG Western FG Western FG <br /> Sump Depth (inches) 32" 32" 32" 32" <br /> Sump Bottom to Top of 11" 11" 11" 11" <br /> Highest Pipe Penetration <br /> (inches) <br /> Test Start Time 10:22 10:27 10:32 10:37 <br /> Initial Reading .001 .001 .001 .001 <br /> Test End Time 10:52 10:57 11:02 11:07 <br /> Final Reading .001 .001 .001 .001 <br /> Change in Reading 0 0 0 0 <br /> Pass/Fail Criteria > .002 > .002 > .002 > .002 <br /> Tightness Test Results M Pass ❑ Fail ® Pass ❑ Fail ® Pass ❑ Fail ® Pass ❑ Fail <br /> Sump/UDC ID UDC 17&18 <br /> Sump Manufacturer Western FG <br /> Sump Depth (inches) 32" <br /> Sump Bottom to Top of 11" <br /> Highest Pipe Penetration <br /> (inches) <br /> Test Start Time 11:12 <br /> Initial Reading .001 <br /> Test End Time 11:42 <br /> Final Reading .001 <br /> Change in Reading 0 <br /> Pass/Fail Criteria > .002 <br /> Tightness Test Results ® Pass ❑ Fail ❑ Pass ❑ Fail ❑ Pass ❑ Fail ❑ Pass ❑ Fail <br /> Additional copies of this page may be attached. <br /> All tests marked "Fail"and any repairs made before or during the tightness test must be described in <br /> the COMMENTS section. <br /> Page 4 of 5 <br />