Laserfiche WebLink
Underground Storage Tank <br /> Secondary Containment Testing Report Form <br /> 8. SUMP/UDC TEST <br /> Test Method Developed by ❑ Manufacturer ❑ Industry Standard ® Professional Engineer <br /> Test Type ❑ Pressure ❑ Vacuum ® Hydrostatic <br /> Test Equipment Used: Caldwell Level Change Indicator <br /> Sump/UDC ID UDC23-S/24-M UDC24-S/25-M UDC25-S/26-M UDC26-S/27-M <br /> Sump Manufacturer Bravo Bravo Bravo Bravo <br /> Sump Depth (inches) 30" 30" 30" 30" <br /> Sump Bottom to Top of 12" 12" 12" 12" <br /> Highest Pipe Penetration <br /> (inches) <br /> Test Start Time 9:12 9:17 9:22 9:27 <br /> Initial Reading .001 .001 .001 .001 <br /> Test End Time 9:42 9:47 9:52 9:57 <br /> Final Reading .001 .001 .001 .001 <br /> Change in Reading 0 0 0 0 <br /> Lss/FailCriteria > .002 > .002 > .002 > .002 <br /> htness Test Results ® Pass ❑ Fail ® Pass ❑ Fail ® Pass ❑ Fail ® Pass ❑ Fail <br /> Sump/UDC ID UDC 27-S <br /> Sump Manufacturer Bravo <br /> Sump Depth (inches) 30" <br /> Sump Bottom to Top of 12" <br /> Highest Pipe Penetration <br /> (inches) <br /> Test Start Time 9:32 <br /> Initial Reading .001 <br /> Test End Time 10:02 <br /> Final Reading .001 <br /> Change in Reading 0 <br /> Pass/Fail Criteria > .002 <br /> Tightness Test Results ® Pass ❑ Fail ❑ Pass ❑ Fail ❑ Pass ❑ Fail ❑ Pass ❑ Fail <br /> Additional copies of this page may be attached. <br /> All tests marked "Fail'and any repairs made before or during the tightness test must be described in <br /> the COMMENTS section. <br /> Page 8 of 9 <br />