Laserfiche WebLink
Underground Storage Tank <br /> Secondary Containment Testing Report Form <br /> 8. SUMP/UDC TEST <br /> Test Method Developed by 0 Manufacturer 0 Industry Standard El Professional Engineer <br /> Test Type © Pressure El Vacuum E Hydrostatic <br /> Test Equipment Used: <br /> Sump/UDC ID 87 STP 91 STP Diesel STP <br /> Sump Manufacturer Fiberlite Fiberlite Fiberlite <br /> Sump Depth (inches) 46 47 47 <br /> Sump Bottom to Top of 11 13 11 <br /> Highest Pipe Penetration <br /> (inches) <br /> Test Start Time 10:16 10:16 10:16 <br /> Initial Reading 7.674 11.321 14.190 <br /> Test End Time 10:31 10:31 10:31 <br /> Final Reading 7.674 11.321 14.190 <br /> Change in Reading 0.0000 0.0000 0.0000 <br /> Pass/Fail Criteria 0.0020 0.0020 0.0020 <br /> Tightness Test Results r Pass rl Fail F1 Pass r] Fail 0✓ Pass 0 Fail [Cl Pass © Fail <br /> Sump/UDC ID UDC 1-2 UDC 3-4 UDC 5-6 UDC 7-8 <br /> Sump Manufacturer Bravo Bravo Bravo Bravo <br /> Sump Depth (inches) 9 9 9 9 <br /> Sump Bottom to Top of Bottom Bottom Bottom Bottom <br /> Highest Pipe Penetration <br /> (inches) <br /> Test Start Time 11:24 11:24 11:24 11:24 <br /> Initial Reading 3.436 5.865 6.447 6.643 <br /> Test End Time 11:39 11:39 11:39 11:39 <br /> Final Reading 3.436 5.865 6.447 6.643 <br /> Change in Reading 0.0000 0.0000 0.0000 0.0000 <br /> Pass Fail Criteria 0.0020 0.0020 0.0020 0.0020 <br /> Tightness Test Results © Pass 0 Fail © Pass 0 Fail E] Pass © Fail IM Pass r! Fail <br /> Additional copies of this page may be attached. <br /> All tests marked "Fail"and any repairs made before or during the tightness test must be described in <br /> the COMMENTS section. <br /> Page 3of5 <br />