260500 ELECTRICAL WORK FOR COMMON RESULTS: 3. FOR A LINEAR FIXTURE THIS TYPICALLY MEANS TWO BRACES AT 45°TO THE HORIZONTAL AND 9. THE OWNER RESERVES THE RIGHT TO RELOCATE ALL LIGHTING, OUTLETS AND SWITCHES BEFORE 260800.02. WARRANTIES, GUARANTEES, CERTIFICATES, ETC.: <br /> 90° BETWEEN THE BRACES AT EACH END, FOR A TOTAL OF (4) BRACE WIRES. THEY ARE ROUGHED IN AT NO EXTRA COST. <br /> 1. ELECTRICAL INSTALLATION SHALL COMPLY WITH TITLE 24, CALIFORNIA 1. WARRANTIES, GUARANTEES, CERTIFICATES, ETC. THAT ARE FURNISHED AND AVAILABLE FOR <br /> CODE OF REGULATIONS, INCLUDING THE FOLLOWING: 260533. PULL OR JUNCTION BOXES: 10. SEPARATION OF WIRING OF DIFFERENT VOLTAGE CLASSIFICATIONS: EQUIPMENT AND MATERIALS FURNISHED AND INSTALLED UNDER THIS SECTION SHALL BE PROPERLY <br /> TITLE 24, CCR, PART 2, 2016 CBC FILLED OUT AS OF DATE OF ACCEPTANCE OF THE WORK BY THE OWNER AND SHALL BE DELIVERED TO <br /> TITLE 24, CCR, PART 3, 2016 CEC 1. INSTALL WHERE INDICATED, OR AS REQUIRED BY CODE, PULL BOXES AND JUNCTION BOXES OF A. WIRING FOR DIFFERENT VOLTAGE CLASSIFICATIONS SHALL BE INSTALLED IN ENTIRELY SEPARATE THE ARCHTITECT. 1 ' <br /> TITLE 24, CCR, PART 4, 2016 CMC SUFFICIENT SIZE AND CAPACITY TO FACILITATE ALL WIRING. BOXES SHALL BE SIZED TO PROPERLY RACEWAYS/CONDUITS SYSTEM AND ENCLOSURES/BOXES. <br /> TITLE 24, CCR, PART 9, 2016 CFC ACCOMMODATE ALL CONDUCTORS ENTERING SAME. 260811. OPERATIONS AND MAINTENANCE (O&M) MANUALS: ARCHITECTURE <br /> TITLE 24, CCR, PART 6, 2016 CALIFORNIA ENERGY CODE CLASSIFICATION 1 -0 TO 30V <br /> TITLE 24, CCR, PART 11, 2016 CALIFORNIA GREEN BUILDING STANDARDS CODE 2. BOXES SHALL BE OF THE SHAPE AND SIZE BEST SUITED FOR THE PARTICULAR APPLICATION AND CLASSIFICATION 2 - 100 TO 250V 1. PROVIDE AS-BUILT DRAWINGS. <br /> ALL APPLICABLE LOCAL CODES SHALL BE SUPPORTED DIRECTLY TO STRUCTURAL MEMBERS, FRAMING OR BLOCKING BY MEANS OF CLASSIFICATION 3 -251 TO 500V <br /> SCREWS, ANCHORS, BOLTS OR EMBEDDED IN MASONRY. A. UPON COMPLETION OF WORK COVERED BY THIS CONTRACT, PROVIDE AS-BUILT PLANS UPON <br /> 2. ELECTRICAL CONTRACTOR SHALL VERIFY POWER, TELEPHONE AND CABLE TV SERVICES AT SITE PRIOR B. PARTICULAR ATTENTION SHALL BE PAID TO THE WIRING FOR WHICH SHALL BE SHOWN ALL CHANGES OF FEEDERS, PANELS, CIRCUITS, LIGHT FIXTURES, ETC., FOR THIS <br /> TO BIDDING. SERVICES TO CONFORM TO UTILITY COMPANY REQUIREMENTS. ELECTRICAL CONTRACTOR A. SWITCH AND RECEPTACLE BOX SHALL BE ONE PIECE DRAWN OR STAMPED STEEL BOXES PROJECT AND INSTALLED UNDER THIS CONTRACT, WHICH ARE NOT IN ACCORD WITH THESE DRAWINGS <br /> SHALL ARRANGE FOR SERVICE INSTALLATIONS PER UTILITY COMPANY REQUIREMENTS AND PAY ALL MINIMUM SIZE SHALL BE FOUR INCHES (4") SQARE. BOXES SHALL BE FITTED WITH FLUSH DEVICE 1. ROOF TOP CONVENIENCE OUTLETS FOR SERVICING ROOF TOP EQUIPMENT. FOR THE WORK. <br /> CUSTOMER CHARGED SERVICE COSTS. COORDINATE WITH OWNER AND UTILITY COMPANY FOR SERVICE COVERS, PLASTER RINGS, OR TILE SWITCH RINGS IN MASONRY IN AREA WHERE EXPOSED WIRING IS ARCHITECT <br /> INSTALLATION. PERMISSIBLE, BOXES SHALL BEFITTED WITH SURFACE TYPE COVERS. 2. LINE VOLTAGE CONTROLS FOR ROOF TOP HVAC AND OTHER REQUIREMENTS. B. ALL SYMBOLS AND DESIGNATIONS USED IN PREPARING "AS-BUILT" DRAWINGS SHALL MATCH <br /> THOSE USED IN CONTRACT DRAWINGS. NJ ASSOCIATES <br /> 3. CONTRACTOR SHALL PROCURE AND PAY FOR ALL PERMITS, LICENSES, ETC. REQUIRED TO CARRY ON B. LIGHTING OUTLETS SHALL BE FOUR INCHES (4")OCTAGON, MINIMUM. C. DISCONNECTS SHALL NOT BE USED AS THROUGH RACEWAYS FOR WIRING NOT DIRECTLY 22769 N BENDER <br /> AND COMPLETE THE WORK. SERVING THE DISCONNECTS. SERVICING OUTLETS SHALL NOT BE MOUNTED ON DISCONNECTS. 2. PROVIDE OF OPERATION AND MAINTENANCE MANUAL FOR POWER, AND LIGHTING SYSTEMS. ROAD <br /> C. FLOOR BOXES: SHALL BE SINGLE SERVICE OR MULTI-SERVICE AS NOTED ON PLANS. BOXES ACAMPO CA 95220 <br /> 4. PROVIDE ALL LABOR, MATERIALS, TOOLS, PLANT EQUIPMENT, TRANSPORTATION AND PERFORM ALL SHALL BE FULLY ADJUSTABLE BEFORE AND AFTER CONCRETE POUR. BOXES SHALL BE FURNISHED 260551. INSTALLATION OF RACEWAYS AND FITTINGS 3. SCAN BOTH "AS-BUILT" PLANS AND O&M MANUAL ON TO A CD AND PROVIDE (3)COPIES OF THE CD 209.727.2040 <br /> OPERATIONS NECESSARY FOR ANY REASONABLE INCIDENTAL TO PROPER EXECUTION AND COMPLETION WITH ALL REQUIRED ACCESSORIES FOR A COMPLETE AND WORKING INSTALLATION, INCLUDING DEVICE TO OWNER PRIOR TO RELEASE OF FINAL PAYMENT. www.njaarchitecture.com <br /> OF ALL"ELECTRICAL WORK"WHETHER SPECIFICALLY MENTIONED OR NOT; ALL AS INDICATED, SPECIFIED MOUNTING BRACKETS, BOTH POWER AND COMMUNICATIONS, TRIM RING/COVERPLATE OR FLOOR PORT 1. CONCEAL RACEWAYS WITHIN CEILINGS, WALLS, AND FLOORS EXCEPT WHERE EXPOSED <br /> HEREIN, AND/OR IMPLIED THEREBY TO CARRY OUT THE APPARENT INTENT THEREOF. ACTIVATION KIT. PROVIDE POWER DEVICES AND TERMINATIONS. SINGLE SERVICE BOX SHALL BE RACEWAYS ARE SPECIFICALLY PERMITTED. 260943. INTERIOR LIGHTING CONTROL SYSTEM: <br /> HUBBELL, NON-METALLIC, CONCRETE FLOOR BOX TYPE PFB1 WITH FLUSH BRASS ROUND COVERPLATE <br /> 5. ALL MATERIALS SHALL BE NEW AND LISTED WITH THE UNDERWRITERS' LABORATORIES, INC., SHALL AS HUBBELL#S3925, FLANGE AS HUBBELL#S3082 AND DUPLEX 120V, 15A OUTLET. MULTI-SERVICE 2. WHERE CONDUIT IS ALLOWED TO BE EXPOSED, INSTALL THE CONDUIT PARALLEL WITH OR AT 1. PROVIDE A COMPLETE AND FULLY OPERATIONAL INTERIOR LIGHTING CONTROL SYSTEM FOR CLIENT <br /> MEET THEIR REQUIREMENTS AND SHALL BEAR THEIR LABEL WHEREVER STANDARDS HAVE BEEN FLOOR BOXES SHALL BE AS HUBBELL SYSTEM ONE AS FOLLOWS: RIGHT ANGLES TO STRUCTURAL MEMBERS, WALLS,AND LINES OF THE BUILDING. INTERIOR LIGHTING AS SPECIFIED HEREIN AND SHOWN ON THE DRAWINGS. <br /> ESTABLISHED AND LABEL SERVICE IS REGULARLY FURNISHED BY THAT AGENCY. .JOE HADDAD <br /> a) ON-GRADE-CASTIRON #S1CFB 3. INSTALL WHERE INDICATED, OR AS REQUIRED BY CODE, PULLBOXES AND JUNCTION BOXES OF 2. THE COMPLETE SYSTEM, INCLUDING ALL DEVICES SHALL BE IN COMPLIANCE WITH THE 2016 <br /> 6. ELECTRICAL DRAWINGS ARE ESSENTIALLY DIAGRAMMATIC AND ALTHOUGH THE SIZE AND LOCATIONS b) UPPER CONCRETE FLOORS - STEEL#S1SFB SUFFICIENT SIZE TO FACILITATE WIRING. BOXES SHALL BE SIZED TO PROPERLY ACCOMMODATE ALL CALIFORNIA ENERGY CODE. <br /> OF EQUIPMENT ARE SHOWN TO SCALE WHEREVER POSSIBLE, CONTRACTOR SHALL MAKE USE OF ALL DATA c) AV BOX-#S1SFBAV CONDUCTORS ENTERING SAME. <br /> IN ALL CONTRACT DOCUMENTS AND VERIFY THIS INFORMATION AT THE SITE. CONTRACTOR SHALL BE d) NON-METALLIC 1 #S1 PFB PROVIDE COVERPLATE AND FLANGE, FINISH PER ARCHITECT. PROVIDE 3. THE COMPLETE SYSTEM SHALL BE AS MANUFACTURED BY NLIGHT, WATTSTOPPER, OR <br /> RESPONSIBLE FOR LAYING OUT AND INSTALLING HIS WORK TO AVOID INTERFERENCE WITH OTHER TRADES. MINIMUM (1) DUPLEX OUTLET AND A 4-PORT MULTISERVICE COMMUNICATIONS FRAMES. VERIFY EXACT 4. DO NOT INSTALL CONDUIT OR TUBING WHICH HAS BEEN CRUSHED OR DEFORMED. GREENGATE CONSISTING OF: <br /> REQUIREMENT WITH OWNER PRIOR TO PROCUREMENT <br /> 7. WORK SHOWN ON THE DRAWINGS TO BE INSTALLED UNDERGROUND SHALL BE INSTALLED AT LEAST 24" 5. RUN CONDUCTORS OF SAME CIRCUIT IN SAME CONDUIT. RUN CONDUCTORS OF DIFFERENT A. LUMINAIRES WITH 0-10V DIMMING LED DRIVERS. <br /> BELOW GRADE UNLESS OTHERWISE NOTED. BACKFILL IN 6"THICK, PROPERLY MOISTENED LAYERS, D. WEATHERPROOF BOXES SHALL BE APPLETON FD SERIES AND FITTED WITH GASKETED CAST VOLTAGE SYSTEMS IN SEPARATE CONDUITS. PROJECT <br /> SOLIDLY PACKED AND IRON TAMPED TO A DENSITY NOT LESS THAN THAT OF ADJACENT, UNDISTURBED COVERS. B. WALL DIMMER SWITCHES THAT COMMUNICATE THROUGH ROOM CONTROLLERS. <br /> EARTH. RESTORE SURFACES, ROADWAYS, WALKS, CURBS, WALLS AND EXISTING UNDERGROUND 6. INSTALL NO CONDUCTORS UNTIL WORK WHICH MIGHT CAUSE DAMAGE TO SUCH CONDUCTORS LODI BOWLING <br /> INSTALLATIONS TO ORIGINAL CONDITION IN AN ACCEPTABLE MANNER. E. VOICE/DATA OUTLET BOXES SHALL BE 4_11/16"SQ.x2_1/8" DEEP MINIMUM, FITTED WITH PLASTER OR THE CONDUIT HAS BEEN COMPLETED. C OCCUPANCY SENSORS THAT COMMUNICATE THROUGH ROOM CONTROLLERS. 302 N SACRAMENTO STREET <br /> RINGS. <br /> LODI CA 95240 <br /> 8. ALL ELECTRICAL EQUIPMENT EXPOSED TO THE WEATHER SHALL BE LISTED FOR EXTERIOR USE. 7. KEEP ALL CONDUITS AT LEAST SIX INCHES AWAY FROM THE COVERING ON HOT WATER OR STEAM D WHERE LIGHT FIXTURES FALL UNDER THE PRIMARY AND SECONDARY DAYLIT ZONES AS DEFINED <br /> F. BOXES FOR SPECIAL EQUIPMENT SHALL BE SUITABLE FOR THE PARTICULAR EQUIPMENT. PIPES. BY SECTION 130.1(d)AND THE TOTAL INSTALLED GENERAL LIGHTING POWER IN THE PRIMARY DAYLIT ZONE <br /> 9. ALL U.L. LISTED EQUIPMENT SHALL BE INSTALLED AS PER THEIR LISTING OR LABELING. IS NOT LESS THAN 120W (EXCEPTION #1 TO SECTION 130.1(d)2)SUCH LIGHT FIXTURES SHALL BE PROVIDED <br /> G. BOXES SHALL BE LOCATED AND PLACED ACCORDING TO ARCHITECTURAL AND STRUCTURAL 8. CAP RACEWAY ENDS DURING CONSTRUCTION. CLEAN OR REPLACE CONDUITS IN WHICH WATER WITH AUTOMATIC DAYLIGHITNG CONTROLS IN ACCORDANCE WITH SECTION 130.1(d)(2)(D). <br /> 10. IN LOCATIONS WHERE ELECTRICAL EQUIPMENT WOULD BE EXPOSED TO PHYSICAL DAMAGE, REQUIREMENTS. OR FOREIGN MATTER HAVE ACCUMULATED, TO THE SATISFACTION OF THE ARCHITECT. <br /> ENCLOSURES OR GUARDS SHALL BE SO ARRANGED AND OF SUCH STRENGTH AS TO PREVENT SUCH E. PROVIDE A DEMAND RESPONSIVE CONTROLS FOR THE INTERIOR LIGHTING SYSTEM PER CEC <br /> DAMAGE. 260550. WIRING METHODS: LINE VOLTAGE SYSTEMS (120V AND ABOVE): 9. CONDUITS SHALL BE SUPPORTED WITH STRAPS, WITH GALVANIZED MALLEABLE SPLIT RING AND SECTION 130.5(e). PROVIDE A GATEWAY DEVICE TO ACHIEVE THIS. SET UP DEVICE SUCH THAT WHEN IT <br /> ROD FOR INDIVIDUAL RUNS OR WITH KINDORF OR UNISTRUT CHANNEL SUPPORTS FOR MULTIPLE RUNS. RECEIVES AN OPEN AUTOMATIC DEMAND RESPONSE (ADR)2.0 SIGNAL IT TRANSMITS THE ADR SIGNAL TO <br /> 11. CONFLICTS BETWEEN SPECIFICATIONS AND PLANS: 1. ALL WIRING SHALL BE INSTALLED IN CONDUITS. CONDUITS SHALL BE RUN CONCEALED IN WALLS DISTANCE BETWEEN SUPPORTS SHALL NOT EXCEED 10 FEET. CONDUITS SHALL BE SUPPORTED EACH OTHER AND TO THE ROOM LIGHTING CONTROLLERS. THE ROOM CONTROLLERS SHALL DIM THE <br /> AND CEILINGS WHERE FEASIBLE.ALL CONDUITS INSTALLED SURFACE ON WALL SHALL BE PAINTED TO INDEPENDENTLY OF ONE ANOTHER. LIGHT FIXTURES TO REDUCE ENERGY CONSUMPTION BY AT LEAST 15%, BUT NOT MORE THAN 50% WHEN <br /> a. ANY CONFLICT BETWEEN ELECTRICAL SPECIFICATIONS AND ELECTRICAL PLANS; OR BETWEEN MATCH WALL FINISH. MOUNT EXTERIOR CONDUITS ON WALL ON GALVANIZED UNISTRUTS. ALL SURFACE THE SIGNAL IS RECEIVED. <br /> ELECTRICAL PLANS AND PLANS OF ANOTHER DISCIPLINE SHALL BE BROUGHT TO THE ATTENTION OF THE CONDUIT INSTALLATION/ RUNS SHALL BE APPROVED BY THE ARCHITECT PRIOR TO INSTALLATION. 10. CONDUITS CONNECTED TO BOXES AND CABINETS SHALL BE FITTED WITH TWO LOCKNUTS AND <br /> ENGINEER AND A RESOLUTION RECEIVED PRIOR TO PROCUREMENT OR INSTALLATION OF THE ITEM IN INSULATED BUSHING, OA"A" SERIES. F. TIME BASED GATEWAY DEVICE THAT PROVIDES TIME-BASED SIGNAL TO ROOM CONTROLLERS FOR <br /> QUESTION. 2. ALL CONDUITS RUN WITHIN INTERIOR FINISHED SPACES SUCH AS OFFICES, BREAKROOM, ALL SPACES THAT CONTROLLED BY MOTION SENSORS TO AUTOMATICALLY SHUT-OFF LIGHTS AT THE END <br /> RESTROOM ETC. SHALL BE RUN CONCEALED. 11. CONDUITS NOT CONNECTED WITH LOCKNUTS AND BUSHINGS SHALL BE FITTED WITH GROUNDING OF DAY <br /> b. IF THE CONTRACTOR PROCEEDS WITH THE WORK WITHOUT RECEIVING ANY RESOLUTION TO THE BUSHING, OZ "BL" SERIES, U. L. APPROVED AND BONDED. <br /> CONFLICT HE/SHE DOES SO AT HIS/HER OWN RISK AND SHALL RECTIFY THE WORK TO THE SATISFACTION 3. ALL CONDUITS RUN IN DEDICATED ELECTRICAL AND MECHANICAL ROOMS SHALL BE RUN 4. ALL SYSTEM COMPONENTS SHALL BE UL LISTED.ALL SYSTEM CONTROL COMPONENTS SHALL BE <br /> OF THE ENGINEER AT NO ADDITIONAL COST TO THE OWNER OR ENGINEER. EXPOSED. 12. CONDUIT STRAPS FOR INDIVIDUAL RUNS SHALL BE SECURED BY TOGGLE BOLTS ON HOLLOW APPROVED BY THE CALIFORNIA ENERGY COMMISSION. <br /> MASONRY, EXPANSION ANCHORS ON SOLID CONCRETE OR MASONRY, MACHINE SCREWS OR BOLTS ON <br /> 260500.01. HVAC SYSTEMS: 4. MINIMUM CONDUIT SIZE SHALL BE 1/2"ABOVE GRADE AND 3/4" UNDERGROUND. METAL SURFACES AND WOOD SCREWS ON WOOD CONSTRUCTION. THE USE OF NAILS TO ANCHOR 5. ALL EQUIPMENT AND ITEMS OF CONTROL SHALL BE INSTALLED AND WIRED IN ACCORDANCE WITH <br /> STRAPS ON WOOD CONSTRUCTION IS PROHIBITED. STRAPS SHALL BE TWO HOLE MALLEABLE IRON OR MANUFACTURER'S REQUIREMENTS. <br /> 1. ELECTRICAL CONTRACTOR SHALL COORDINATE WITH MECHANICAL CONTRACTOR FOR EXACT 5. MINIMUM ACCEPTABLE CONDUITS ARE: SNAP-TYPE STEEL WITH RIBBED BACK, GALVANIZED OR CADMIUM PLATED. THE USE <br /> LOCATIONS OF ALL HVAC UNITS, DISCONNECTS AND DEVICES IN FIELD. COORDINATE ROOF PENETRATIONS 6. PROVIDE WALL OCCUPANCY SENSOR LIGHT SWITCHES WHERE SO SHOWN ON PLANS. SUCH <br /> FOR DISCONNECTS AND WEATHERPROOF OUTLETS WITH ELECTRICAL CONNECTION POINTS ON THE UNITS A. GALVANIZED RIGID STEEL- FOR USE ON: 13. PLACEMENT OF ALL BOXES SHALL BE GOVERNED BY APPLICABLE ARCHITECTURAL AND OCCUPANCY SENSOR SWITCHES SHALL BE SINGLE LEVEL AUTOMATIC "ON"/AUTOMATIC "OFF"AS SHOWN <br /> TO KEEP FLEXIBLE CONDUIT LENGTH TO A MINIMUM (36" MAXIMUM). VERIFY AND CONFIRM THE ACTUAL (1) EXTERIOR WALL SURFACES. STRUCTURAL REQUIREMENTS. ON PLANS. SENSORS SHALL COMPLY WITH SECTION 110.9 OF THE ENERGY CODE. <br /> MOUNTING LOCATION ON THE HVAC UNIT FOR THE DISCONNECT. ALL SERVICING OUTLETS ON THE ROOF <br /> OR OUTDOORS FOR HVAC UNITS SHALL BE WP/GFI. B. GALVANISED STEEL EMT FOR USE: 14. CONDUIT FITTINGS: EXCEPT WHERE OTHERWISE NOTED, CONDUIT FITTINGS SHALL BE APPLETON 7. THE SYSTEM SHALL AUTOMATICALLY SWITCH OFF ALL LIGHTS WHEN CONTROLLED SPACE <br /> (1) CONCEALED IN INDOOR FINISHED SPACES. OR APPROVED EQUAL. UNILETS SHALL BE MALLEABLE IRON AND FITTED WITH COVERS AND GASKETS. BECOMES UNOCCUPIED AND SWITCH ON LIGHTS WHEN THE SPACE IS RE-OCCUPIED. ALL SENSORS SHALL <br /> 2. THE RATING OF THE DISCONNECT SHALL BE SUCH AS TO ENABLE THE LARGEST FUSE SIZE ON THE (2) EXPOSED INSIDE ELECTRICAL & MECHANICAL ROOMS. BE PROVIDED WITH USER ADJUSTABLE TIME DELAY(15 SEC. TO 20 MINUTES) FOR"SWITCH-OFF" FUNCTION <br /> UNIT NAMEPLATE TO BE INSTALLED IN THE DISCONNECT. PROVIDE FUSES OF THIS RATING. 15. TELEPHONE AND SIGNAL CONDUIT BENDS WHERE REQUIRED SHALL HAVE A RADIUS OF TEN TIMES AND ADJUSTABLE SENSITIVITY. <br /> C. LIQUID TIGHT STEEL FLEX: THE CONDUIT TRADE SIZE. <br /> 3. FURNISH AND INSTALL ALL LINE VOLTAGE CONDUITS AND LINE VOLTAGE WIRING (LOW VOLTAGE (1) FOR FINAL CONNECTION TO OUTDOOR EQUIPMENT. LENGTH SHALL NOT EXCEED 36". 8. LOW VOLTAGE WIRING IS NOT REQUIRED TO BE IN CONDUIT EXCEPT IN HARDLID CEILINGS WHERE <br /> CONDUITS AND WIRING BY MECHANICAL)TO HVAC EQUIPMENT AND ASSOCIATED CONTROLS AND DEVICES 16. PROVIDE PULL TAPE IN ALL EMPTY CONDUITS. SUCH WIRES SHALL BE RUN IN CONDUIT. <br /> AS SHOWN ON THE ELECTRICAL AND MECHANICAL PLANS, UNLESS OTHERWISE NOTED. D. FLEXIBLE STEEL CONDUIT: <br /> (1) FOR INDOOR FINAL CONNECTION TO RECESSED LIGHT FIXTURES. LENGTH SHALL NOT EXCEED 72". 260551.01. PENETRATIONS OF FIRE-RATED ASSEMBLIES: 262400. MAIN SERVICE SWITCHBOARD <br /> 4. RUN ALL CONDUITS FOR ROOFTOP EQUIPMENT WITHIN CEILING SPACE BELOW. SURFACE CONDUIT (2) FOR INDOOR FINAL CONNECTION TO HVAC EQUIPMENT. LENGTH SHALL NOT EXCEED 36". <br /> RUNS ON THE ROOF ARE NOT PERMITTED ON THIS PROJECT. 1. PENETRATIONS OF PIPES, CONDUITS, ETC., IN WALLS AND CEILINGS REQUIRING PROTECTED 1. SQUARE D, EATON, OR APPROVED EQUAL, METAL ENCLOSED UNIT WITH UGPS, METERING SECTION, <br /> E. "PVC" SCHEDULE 40: OPENINGS SHALL BE FIRESTOPPED IN ACCORDANCE WITH CBC SECTION 714. FIRE STOP MATERIAL SHALL MAIN DISCONNECT AND GROUP MOUNTED, MOULDED CASE BRANCH CIRCUIT BREAKERS COMPLETE WITH <br /> 5. DISCONNECTS SHALL NOT BE USED AS THROUGH RACEWAYS FOR WIRING NOT DIRECTLY SERVING (1) FOR CONDUITS RUN UNDERGROUND AND FOR UNDER BUILDING SLAB. BE A TESTED ASSEMBLY APPROVED BY AUTHORITY HAVING JURISDICTION. INTERCONNECTING BUS IN A FACTORY ASSEMBLED, INTEGRATED UNIT. ARRANGEMENT AND RATINGS OF <br /> THE DISCONNECTS. SERVICING OUTLETS SHALL NOT BE MOUNTED ON DISCONNECTS. (2) CONDUIT STUBUPS THROUGH THE FLOOR OR GRADE SHALL BE IN PVC WRAPPED RIGID STEEL EQUIPMENT ARE SHOWN ON DRAWINGS. UNIT SHALL MEET ALL UTILITY COMPANY REQUIREMENTS. <br /> CONDUIT. PVC WRAPPING SHALL EXTEND 6"ABOVE FINISHED FLOOR OR GRADE. 2. THROUGH PENETRATIONS AND MEMBRANE PENETRATIONS OF FIRE-RESISTANCE RATED WALLS <br /> 260500.02. SUBMITALLS: (3) NOT PERMITTED FOR WIRING ABOVE FINISHED FLOOR INSIDE BUILDINGS SHALL COMPLY WITH CBC 714.3. 2. SWITCHBOARD SHALL BE ENCLOSED STRUCTURE OF CODE GAUGE STEEL PLATES WITH REMOVABLE H C S ENGINEERING INC. <br /> FRONT. FULL FRONT ACCESS SHALL BE PROVIDED FOR CONNECTIONS AND OPERATIONS. FRONT <br /> 1. PROVIDE THE FOLOWING SUBMITTALS FOR REVIEW AND APPROVAL. EACH SHALL BE SUBMITTED F. ALUMINUM CONDUITS, IMC CONDUITS OR ALUMINUM FITTINGS ARE NOT APPROVED FOR USE ON 3. PENETRATIONS OF FIRE RESISTANCE RATED FLOOR, FLOOR/CEILING ASSEMBLY OR THE CEILING SECTIONS SHALL BE ATTACHED WITH MACHINE SCREWS, EVENLY SPACED. HINGED DOOR SHALL HAVE CONSULTING ELECTRICAL ENGINEERS <br /> SEPARATELY TO AVOID DELAYS IN THE REVIEW OF ONE SUBMITTAL IN HOLDING UP REVIEW OF THE THIS PROJECT. MEMBRANCE OF A ROOF/CEILING ASSEMBLY SHALL COMPLY WITH CBC 714.4. VAULT TYPE HANDLES AND LOCKS. UNITS SHALL BE NEMA 3R FOR OUTDOOR INSTALLATION AND NEMA 1 4512 FEATHER RIVER DRIVE,SUITE F <br /> REMAINDER. FOR INDOOR INSTALLATION. STOCKTON,CA 95219 (209)478-8270 <br /> G. ALL CONDUIT FITTINGS SHALL BE MALLEABLE IRON/STEEL. 4. ALL ELECTRICAL BOXES INSTALLED IN A FIRE-RESISTIVE SEPARATION SHALL BE AN "APPROVED EMAIL ADDRESS: richard@hcs-eng.com <br /> a. SERVICE SWITCHBOARD BOX". AN "APPROVED BOX" IS AN ALL STEEL ELECTRICAL BOX WHICH IS UL LISTED FOR INSTALLATION IN A 3. ALL BUSES SHALL BE COPPER OR ALUMINUM SIZED TO CONFORM TO UL TO LIMIT TEMPERATURE RISE. PROJ.2017.xxx DES.WW ENG.RCS <br /> d. LIGHTING CONTROL PANEL. H. COUPLING: FIRE-RESISTIVE SEPARATION. ALL BUS CONNECTIONS SHALL BE BOLTED. BUSES SHALL BE BRACED TO WITHSTAND, AS A MINIMUM, THE <br /> e. LIGHTING CONTROLS (1) EMT COUPLING -APPLETON TWC-CS SERIES SHORT CIRCUIT CURRENT INDICATED ON DRAWINGS. BUSES SHALL BE SEQUENCE PHASED AND SHALL <br /> b. PANEL BOARDS (2) EMT CONNECTOR-APPLETON TW-CSI SERIES 5. ELECTRICAL BOXES, INCLUDING BOXES FOR RECEPTACLES, IN RATED WALLS SHALL HAVE A RUN FULL HEIGHT. <br /> f. BASIC ELECTRICAL MATERIALS (3) FLEX CONDUIT CONNECTOR -T&B "TITE BITE", INSULATED MINIMUM OF 24" HORIZONTAL SEPARATION FROM THOSE IN ADJACENT ROOMS AT THE OTHER SIDE OF PROFESSIONAL STAMP <br /> C. LIGHT FIXTURES (4) LIQUID TIGHT FLEX CONDUIT CONNECTOR-APPLETON "STB" SERIES UP TO 2", "ST" SERIES OVER 2". WALL IN ACCORDANCE WITH C.B.C. SECTION 714.3.2. IN CASE SUCH HORIZONTAL SEPARATION IS NOT <br /> POSSIBLE EACH BOX SHALL BE PROTECTED BY A LISTED FIRE-STOPPING PUTTY PAD AND BOX SHALL BE 4. SERVICE SWITCHBOARD SHALL HAVE PERMANENTLY INSTALLED USER-ACCESSIBLE METERING OF <br /> 260500.03. WORKING CLEARANCES FOR ELECTRICAL SWITCHGEAR: I. RIGID STEEL CONDUIT CONNECTED TO BOXES AND CABINETS SHALL BE FITTED WITH TWO PROVIDED WITH A METAL COVERPLATE AND NOT PLASTIC OR NYLON. TOTAL ELECTRICAL ENERGY USE PER TABLE 130.5-A OF THE 2016 CALIFORNIA ENERGY CODE. AS A <br /> LOCKNUTS AND INSULATING BUSHING, OA"A" SERIES. PROVIDE GROUNDING BUSHING OZ"BL" SERIES MINIMUM THIS REQUIRES THE FOLLOWING: QRoFESSipNq <br /> 1. PROVIDE WORKING SPACES FOR ELECTRICAL PANELS AND SWITCHGEAR TO COMPLY WITH CEC WHERE LOCKNUTS AND BUSHING IS NOT USED. CONDUITS CONNECTED TO BOXES EXPOSED TO 6. WHERE CONDUIT SLEEVE IS USED FOR THE PROTECTION OF WIRING PENETRATIONS, UL LISTED �F� PRD C. S <� <br /> 110.26. WEATHER/MOISTURE SHALL BE FITTED WITH WATERTIGHT SEALING HUBS OF STEEL OR MALLEABLE FIRESTOP COMPOUND SHALL BE USED TO SEAL THE OPENING AROUND THE CONDUIT AND TO SEAL THE a. INSTANTANEOUS KW DEMAND. <br /> IRON WITH SEALING RING AND INSULATED THREAT, T& B 370 SERIES. CONDUIT ENDS AFTER THE CABLE IS INSTALLED. b. HISTORICAL PEAK KW DEMAND. 1i 1c, <br /> 2. ELECTRICAL CONTRACTOR SHALL COORDINATE WITH ALL TRADES INVOLVED TO ENSURE THE c. RESETTABLE KWH. ExJp. 6-30039 A <br /> CLEARANCES REQUIRED BY ITEM 1 ABOVE ARE PROVIDED. J. TYPE NM AND NMC CABLES SHALL NOT BE USED ON THIS PROJECT. 7. WHERE A CABLE OR A GROUP OF CABLES PENETRATES MEMBRANE OR CONTINUOUS BLOCKING, <br /> UL LISTED FIRESTOP COMPOUND SHALL BE USED TO SEAL THE OPENING AROUND THE CABLES. 5. THE DISTRIBUTION SECTION SHALL BE SET UP TO PERMIT IN FUTURE THE DISAGGREGATED �� ��FCTR�GP� `P <br /> 260526. GROUNDING: K. THE PROJECT DRAWINGS ARE LAID OUT USING SOLID CONDUITS AND CABLES PULLED THROUGH MEASUREMENT OF ELECTRICAL LOAD ENERGY USES DOWNSTREAM FROM THE SERVICE ACCORDING TO 9TFCF CA1�Fp�� <br /> SUCH CONDUITS. MC CABLES MAY BE UTILIZED AS DESCRIBED BELOW, WITH RESTRICTIONS NOTED. 8. SEE ARCHITECTURAL PLANS FOR LOCATION OF FIRE-RATED WALLS AND CEILING. TABLE 130.5-B OF THE 2016 CALIFORNIA ENERGY CODE. <br /> 1. GROUND AND BOND ALL EQUIPMENT AS REQUIRED BY GOVERNING CODES AND SPECIFICALLY <br /> INCLUDING SWITCHBOARD, PANELBOARDS, MOTOR CASES, METAL PIPING SYSTEMS, STRUCTURAL STEEL, (1) PRIOR APPROVAL OF OWNER/ARCHITECT OR ENGINEER REQUIRED. 260553. NAMEPLATES & IDENTIFICATION: 6. PROVIDE "SPACES" INDICATED ON DRAWINGS WITH ALL NECESSARY MOUNTING HARDWARE <br /> ETC. PERMITTING EASY FUTURE INSTALLATION OF BREAKERS IN THE FIELD. REVISIONS <br /> (2) MC CABLES SHALL BE AS MANUFACTURED BY SOUTHWIRE TYPE EZ-MC DURACLAD TYPE WITH LIGHT 1. INSTALL ENGRAVED NAMEPLATES FOR EACH PANELBOARD, CABINET, DISCONNECT, ETC. <br /> 2. PROVIDE GROUND WIRES IN ALL FEEDERS AND BRANCH CIRCUITS, SIZE PER CEC TABLE 250.122 WEIGHT STEEL ARMOR AND INSULATED GREEN GROUNDING CONDUCTORS OR APPROVED EQUAL. NAMEPLATES SHALL BE SECURELY FASTENED TO THE EQUIPMENT WITH #4 PHILLIPS ROUND HEAD 7. PROVIDE INCOMING SERVICE TERMINALS, METERING SECTIONS, CTs, ETC. IN ACCORDANCE WITH THE No. Description Date By <br /> CADMIUM PLATED SELF-TAPPING SCREWS, BRASS BOLT. UTILITY COMPANY AND PLANS. <br /> 3. ALL GROUND WIRES SHALL BE INSULATED GROUND WIRES. (3) SHALL BE USED FOR BRANCH CIRCUITS ONLY AS NOTED BELOW. <br /> 2. PROVIDE CIRCUIT LABEL INDICATING PANEL AND CIRCUIT NUMBER ON EACH COVERPLATE FOR 8. PROVIDE A COPPER GROUND BUS. <br /> (a) CANNOT BE USED ANYWHERE EXPOSED. EACH RECEPTACLE AND LIGHT SWITCH, MOTION SENSOR SWITCH. SUCH LABEL SHALL BE SELF ADHESIVE <br /> 260529. INSTALLATION OF SUPPORT SYSTEMS WHITE TAPE WITH BLACK LETTERS MADE ON A LABEL MAKER. <br /> (b) LIGHTING: VERTICAL DROPS IN WALL FOR LIGHT SWITCHES FORM JBOX IN CEILING. HORIZONTAL <br /> 1. RACEWAYS, CABLE ASSEMBLIES, BOXES, CABINETS,AND FITTINGS SHALL BE SECURELY FASTENED RUNS IN CEILING SHALL BE IN SOLID STEEL CONDUITS. 3. ALL CONTROLLED RECEPTACLES SHALL BE PERMANENTLY MARKED TO DIFFERENTIATE THEM <br /> IN PLACE PER CEC ARTICLE 300.11. SUPPORT WIRES THAT DO NOT PROVIDE SECURE SUPPORT SHALL NOT FROM UNCONTROLLED RECEPTACLES PER CALIFORNIA ENERGY CODE SECTION 130.5(d)(3). <br /> BE PERMITTED AS THE SOLE SUPPORT. SUPPORT WIRES AND ASSOCIATED FITTINGS THAT PROVIDE (c) POWER RECEPTACLES: Project 2017.xxx <br /> SECURE SUPPORT AND THAT ARE INSTALLED IN ADDITION TO THE CEILING GRID SUPPORT WIRES SHALL BE 260573. ARC FLASH HAZARDS: <br /> PERMITTED AS THE SOLE SUPPORT. WHERE INDEPENDENT SUPPORT WIRE ARE USED, THEY SHALL BE (1) FOR UNDERGROUND HOMERUNS: SOLID CONDUIT VERTICAL RISER IN WALL FROM UNDERGROUND bpawl n WW <br /> SECURED AT BOTH ENDS. CABLES AND RACEWAYS SHALL NOT BE SUPPORTED BY CEILING GRIDS. CONDUIT TO FIRST RECEPTACLE JBOX. THEN HORIZONTAL RUNS WITHIN WALLS TO OTHER 1. PROVIDE WARNING LABEL ON ELECTRICAL EQUIPMENT OF POSSIBLE ARC FLASH HAZARDS PER eKbcke RCS <br /> RECEPTACLE BOXES IN MC CABLE. C.E.C. 110.16. <br /> 2. FURNISH ALL NECESSARY FOUNDATIONS, SUPPORTS, BACKING, ETC., FOR ALL ELECTRICAL (2) FOR OVERHEAD HOMERUNS: VERTICAL DROPS FROM JBOX IN CEILING THEN HORIZONTAL RUNS d By. <br /> ENCLOSURES, CONDUITS AND EQUIPMENT. WITHIN WALLS TO OTHER RECEPTACLES. HORIZONTAL RUNS IN CEILING SHALL BE IN SOLID STEEL 260800. TESTING: <br /> CONDUITS. <br /> 3. ATTACH ALL BOXES, CABINETS, ETC. TO WOOD WITH WOOD OR LAG SCREWS, TO METAL WITH 1. THE ENTIRE ELECTRICAL INSTALLATION SHALL BE FREE FROM SHORT CIRCUITS AND IMPROPER <br /> MACHINE SCREWS OR BOLTS AND TO CONCRETE WITH EXPANSION ANCHORS AND MACHINE SCREWS OR (d) NO OTHER USE IS PERMITTED WITHOUT SPECIFIC WRITTEN APPROVAL OF THE ARCHITECT OR GROUNDS. TEST ALL WIRING AND CONNECTIONS FOR CONTINUITY AND GROUNDS BEFORE ANY FIXTURES <br /> BOLTS. ENGINEER. OR EQUIPMENT ARE CONNECTED AND WHERE SUCH TESTS INDICATE FAULTY INSULATION OR OTHER PERMIT SET <br /> DEFECTS, THEY SHALL BE LOCATED, REPAIRED AND RETESTED AT THE CONTRACTOR'S EXPENSE. 8.17.18 <br /> 2. RIGID STEEL CONDUIT SHALL BE SUPPORTED AT INTERVALS NOT GREATER THAN 10 FT, ELECTRICAL (4) ALL FITTINGS AND TERMINATIONS FOR THE MC CABLING SYSTEM SHALL BE METAL AND SUITABLE PROVIDE ALL INSTRUMENTS TO MAKE SUCH TESTS. <br /> METALLIC TUBING AT INTERVALS NOT GREATER THAN 5 FT. AND LISTED FOR SUCH USE. <br /> 2. DEMONSTRATE TO THE OWNER AND THE ARCHITECT, THAT THE ENTIRE INSTALLATION IS <br /> 3. A SUPPORT SHALL BE PROVIDED NOT MORE THAN 3 FT. FROM ANY CHANGE IN DIRECTION. (5) ALL SUPPORTS, ATTACHMENTS SPACING SHALL BE PER CEC 330.30. COMPLETE, IN PROPER OPERATING CONDITION AND THAT THE CONTRACT HAS BEEN PROPERLY AND <br /> ADDITIONAL SUPPORTS TO THOSE SPECIFIED ABOVE SHALL BE INSTALLED WHERE REQUIRED TO SUIT JOB FULLY EXECUTED. <br /> CONDITIONS AND TO PROVIDE A SECURE INSTALLATION. ALL HANGERS AND SUPPORTS SHALL BE THE (6) FOR MULTI-WIRE BRANCH CIRCUITS SUCH CABLES SHALL HAVE MULTIPLE NEUTRALS, ONE FOR GENERAL NOTES <br /> PRODUCTS OF ONE MANUFACTURER. EACH CIRCUIT. 260800.01. CERTIFICATE OF COMPLETION: <br /> 260519.01. SEISMIC BRACING FOR SUSPENDED FIXURES: 6. CONDUCTORS SHALL BE COPPER CONDUCTORS TYPE THHN/THWN UNLESS OTHERWISE NOTED 1. ACCEPTANCE OF THE CONTRACT FOR THIS WORK INCLUDES THIS GUARANTEE: THE CONTRACTOR <br /> OR REQUIRED BY CODE. GUARANTEES THAT HE HAS PERFORMED THE WORK IN ACCORDANCE WITH THE CONTRACT DOCUMENTS. <br /> 1. ALL SUSPENDED FIXTURES SHALL BE ABLE TO SWING AND SWAY 45° IN ANY DIRECTION WITHOUT CONTRACTOR AGREES TO REPLACE OR REPAIR, AS NEW ANY DEFECTIVE WORK, MATERIALS, OR PART <br /> HITTING AN OBSTRUCTION SUCH AS DUCT, PIPE, BEAM, ETC. 7. ALL DEVICES, CONDUITS, RACEWAYS AND CABLES SHOWN ARE NEW TO BE PROVIDED UNLESS WHICH MAY APPEAR WITHIN ONE YEARS (1) OF FINAL ACCEPTANCE, IF, IN THE OPINION OF THE <br /> OTHERWISE NOTED. ARCHITECT OR THE OWNER, THE DEFECT IS DUE TO WORKMANSHIP OR MATERIAL. <br /> 2. IF NOT, PROVIDE SEISMIC RESTRAINT PER CBC AND AS REQUIRED, USING#10 GA WIRES WITH <br /> MINIMUM (3)TWISTS AROUND THE TIE AT EACH END U.O.N. SPECIFICALLY. 8. FLASH AND COUNTERFLASH ALL ITEMS PASSING THROUGH THE ROOF. <br /> EOmla <br /> v <br />