262417. PANELBOARDS: 265100. LIGHTING:
<br /> ELECTRICAL LEGEND ELECTRICAL LEGEND
<br /> 1. UNITS SHALL BE FLUSH OR SURFACE MOUNTED AS INDICATED ON THE PANEL SCHEDULE, WITH THE 1. ALL LUMINAIRES SHALL BE CERTIFIED BY THE MANUFACTURER TO THE CALIFORNIA ENERGY
<br /> NUMBER AND SIZE OF BREAKERS AS INDICATED ON THE PANEL SCHEDULE. SINGLE POLE, TWO POLE, AND COMMISSION: LIGHTING FIXTURES COMMUNICATIONS
<br /> THREE POLE BREAKERS SHALL BE BOLT-ON TYPE. MULTIPLE POLE BREAKERS SHALL HAVE COMMON FIXTURE NOTATIONS: 1 ■
<br /> INTERNAL TRIP CONNECTION. SINGLE POLE BREAKERS SHALL NOT BE TIED AT HANDLES TO FORM A. ALL LUMINAIRES SPECIFIED ON THIS PROJECT SHALL BE AS NOTED IN THE "LIGHT FIXTURE LINEAR FIXTURE A,(b),C-12 FIXTURE TYPE "A", SWITCH "b", CIRCUIT C-12 ' TELEPHONE BACKBOARD, PROVIDE#8 GND TO SERVICE GROUND ARCHITECTURE
<br /> MULTIPLE POLE BREAKERS. THE PANEL DOORS SHALL BE DOOR-IN-DOOR CONSTRUCTION AND SHALL SCHEDULE" ON THESE PLANS. NO SUBSTITUTES ARE PERMITTED WITHOUT WRITTEN APPROVAL OF THE - SQUARE = RECESSED
<br /> HAVE FLUSH TYPE LOCKS, ALL LOCKS SHALL BE KEYED ALIKE AND HAVE TYPEWRITTEN DIRECTORIES ENGINEER. CIRCLE =SURFACE 0 COMMUNICATIONS OUTLET, PHONE & DATA
<br /> INDICATING FIXTURES, EQUIPMENT, OR OUTLETS SERVICE BY EACH BREAKER. PANELS SHALL HAVE
<br /> COPPER BUSSING. B. ALL INTERIOR LUMINAIRES SHALL BE PROVIDES WITH 0-10V DIMMING LED DRIVERS. - -
<br /> DOWNLIGHT, SQUARE RECESSED PHONE ONLY OUTLET, PREWIRED WITH CAT 5e CABLE
<br /> -
<br /> 262726. WIRING DEVICES: C. ALL EXTERIOR LUMINAIRES SHALL BE PROVIDED WITH 0-10V DIMMING LED DRIVERS WITH WALL MOUNT Ilk. DATA ONLY OUTLET JACK, PREWIRED WITH CAT 6 CABLE
<br /> INTEGRAL MOTION SENSORS WHERE SO NOTED.
<br /> 1. UNITS SHALL BE EQUAL TO THE DEVICES SET FORTH HEREIN, IN STANDARD COLORS (BROWN, CEILING EXHAUST FAN ARCHITECT
<br /> WHITE, GREY, BEIGE OR IVORY)AS SELECTED BY THE ARCHITECT: 265300. EXIT AND MEANS OF EGRESS EMERGENCY LIGHTING:
<br /> A. WIRING DEVICES LEVITON # HUBBELL# P &S# POLE MOUNT AREA LIGHT NJ ASSOCIATES
<br /> SINGLE POLE SWITCH, 15A 1201-2 HBL1201 PS15AC1 1. PROVIDE EXIT SIGNS IN ACCORDANCE WITH CBC SECTION 1011.1. PROVIDE MEANS OF EGRESS 22769 N BENDER
<br /> DOUBLE POLE SWITCH, 15A 1202-2 HBL1202 PS15AC2 ILLUMINATION IN ACCORDANCE WITH CBC SECTION 1006. PROVIDE FLOOR-LEVEL EXIT SIGNS PER CBC DRAFTING NOTATIONS ROAD
<br /> THREE WAY SWITCH, 15A 1203-2 HBL1203 PS15AC3 1011.7 IF REQUIRED ACAMPO CA 95220
<br /> DUPLEX CONV. OUTLET, 15A 5262 HBL5262 5262 EMERGENCY LIGHTING 209.727.2040
<br /> DUPLEX CONV. OUTLET, 20A 5362 HBL5362 5362 2. ELECTRICAL CONTRACTOR SHALL RE-VERIFY PLACEMENT OF ALL EXIT SIGNS AS TO ENSURE THAT I N## KEY NOTE, SEE SCHEDULE
<br /> DUPLEX CONV. GFI OUTLET, 15A 6599 GF15 1595L THEY ARE CLEARLY VISIBLE FROM ANY DIRECTION OF APPROACH WITHIN THE PATH OF EXIT TRAVEL TO 1411 EXIT SIGN WITH 90 MIN BATTERY BACKUP www.njaarchitecture.com
<br /> DUPLEX CONV. GFI OUTLET, 20A 6899 GF15 2095L AND WITHIN EXITS INSIDE THE BUILDING. THIS VERIFICATION SHALL BE CARRIED OUT AT ROUGHIN STAGE. N## EQUIPMENT TAG, SEE SCHEDULE
<br /> THEY SHALL BE LOCATED AS NECESSARY TO CLEARLY INDICATE THE DIRECTION OF EGRESS TRAVEL. NO `rt WALL MOUNT EMERGENCY LIGHT WITH 90 MIN BATTERY BACK CLIENT
<br /> 2. THE CONTROLLED OUTLET SHALL HAVE PERMANENT UNIQUE MARKING PROVIDED BY THE POINT IN THE EXIT PATH SHALL BE MORE THAN 100 FT. FROM THE NEAREST VISIBLE SIGN. ALL IN A ' REFERENCE TO A DETAIL VIEW "A" ON SHEET E-2
<br /> MANUFACTURER OF THE RECEPTACLE. ACCORDANCE WITH CBC SECTION 1011.1. RELOCATE AND/OR ADD EXIT SIGNS AS NECESSARY TO ACHIEVE }-I EXTERIOR LANDING EMERGENCY LIGHT. CONNECT � JOE HADDAD
<br /> THIS. PROVIDE PENDANTS TO MOUNT SIGNS AS NECESSARY TO ACHIEVE THIS. TO INTERIOR EXIT SIGN FOR POWER. 2i'
<br /> 3. THE MOUNTING HEIGHTS OF LIGHT SWITCHES, RECEPTACLES AND CONTROLS SHALL BE MAXIMUM NEW ELECTRICAL
<br /> 48" MEASURED TO THE TOP OF BOXES OR MINIMUM 16"TO THE BOTTOM OF BOXES. SEE "LEGEND" FOR 3. THE FINAL NUMBER AND LOCATION OF EXIT SIGNS SHALL BE DETERMINED IN THE FIELD BY THE FIXTURES WITH INTEGRAL EMERGENCY BALLAST
<br /> ACTUAL MOUNTING HEIGHTS OF DEVICES. VERIFY HEIGHT WITH ARCHITECT WHERE AN ACTUAL MOUNTING FIRE MARSHALL AND BUILDING INSPECTOR. - i EXISTING ELECTRICAL OR DEMOLISHED WHERE NOTED
<br /> HEIGHT IS NOT CALLED OUT ON PLANS.
<br /> 4. INDIVIDUAL UNIT EQUIPMENT FOR EMERGENCY ILLUMINATION SHALL COMPLY WITH CEC SECTION (e) (E) EXISTING DEVICE, TO REMAIN IN OPERATION
<br /> 4. SINGLE RECEPTACLE SERVED BY INDIVIDUAL 20A BRANCH CIRCUIT DEDICATED TO THE OUTLET 700.12(F). THE BRANCH CIRCUIT FEEDING THE UNIT EQUIPMENT SHALL BE THE SAME BRANCH CIRCUIT AS BASIC LIGHTING CONTROLS
<br /> SHALL BE 20A RATED PER CEC 210.21(B)(1). ALL OTHERS SHALL BE 15A RATED. THAT SERVING THE NORMAL LIGHTING IN THE AREA AND CONNECTED AHEAD OF ANY LOCAL SWITCHES. (r) (R) REMOVE DEVICE, KEEP REMAINDER OF CIRCUIT IN OPERATION
<br /> PROJECT
<br /> 5. ALL 15A AND 20A, 120V OUTLETS IN KITCHEN SHALL BE GFCI PER CEC 210.8(B)(2). LOCATE SUCH 5. ALL EMERGENCY LIGHTS AND EXIT SIGNS SHALL BE PROVIDED WITH AN UNSWITCHED HOT WIRE. LIGHT SWITCH, +48"TO TOP OF BOX
<br /> OUTLETS SO THAT THEY ARE ACCESSIBLE AFTER APPLIANCES THAT ARE PLUGGED INTO THE OUTLETS ARE D = DIMMER (RR) REMOVE, RELOCATE AND RECONNECT DEVICE ON EXISTING CIRCUIT, EXTEND CIRCUIT LODI BOWLING
<br /> IN PLACE. 6. ALL EMERGENCY LIGHT FIXTURES WITH INTEGRAL BATTERY BALLASTS SHALL BE SWITCHED AS 3= SWAY 302 N SACRAMENTO STREET
<br /> SHOWN AND SHALL COME ON IN EMERGENCY POWER-OFF MODE UPON POWER FAILURE. TO THIS EFFECT P = PILOT SWITCH LODI CA 95240
<br /> 6. ALL RECEPTACLES INSTALLED OUTDOORS SHALL BE WEATHERPROOF AND HAVE GROUND FAULT PROVIDE AN UNSWITCHED POWER WIRE TO EACH SUCH FIXTURE FROM THE SAME CIRCUIT AS THAT os = LINE VOLTAGE OCCUPANCY SENSOR
<br /> CIRCUIT INTERRUPTER PROTECTION. FEEDING THE LIGHT FIXTURE. T= TIMMER ONE LINE DIAGRAM
<br /> • VS = VACANCY SENSOR
<br /> 7. 120V, 15A AND 20A RECEPTACLES ARE NOW SUBJECT TO CALIFORNIA ENERGY CODE, SECTION 283000. FIRE SPRINKLER SYSTEM: DP1 = NPP16 D POWER/RELAY PACK, OCCUPANCY CONTROLLED DIMMING I BUS/SWITCHBOARD 50/3 CIRCUIT BREAKER 50 AMP RATED, 3 POLE
<br /> 130.5(d). ALL SUCH OUTLETS SHALL BE CONSIDERED AS UNCONTROLLED EXCEPT THOSE WHICH ARE DP2 = NSP5 PCD ELV 120 SECONDARY RELAY PACK, PHASE CONTROL DIMMING,
<br /> SPECIFICALLY CALLED OUT ON THE PLANS AS CONTROLLED. SEE "CONTROLLED 120V RECEPTACLES" 1. THIS BUILDING IS PROVIDED WITH A FIRE SPRINKLER SYSTEM IN ACCORDANCE WITH CBC 903.4 ELECTRONIC LOW VOLTAGE, 120 VAC GFI = GROUND FAULT INTERRUPTER
<br /> PARAGRAPH BELOW. AND 907.2.9.1 AND CFC 907.2.9.1. OS1 = NCM PDT 10 LOW VOLTAGE CEILING MOUNT SNSOR, PDT, LARGE MOTION/ I I PANEL AFCI =ARC FAULT CIRCUIT INTERRUPTER
<br /> EXTENDED RANGE 360° LENS
<br /> 262726.01. CONTROLLED 120V RECEPTACLES: A. ELECTRICAL CONTRACTOR SHALL VERIFY ALL ELECTRICAL WORK REQUIREMENTS WITH FIRE OS2 = NCM 10 LOW VOLTAGE CEILING MOUNT SENSOR, LARGE MOTION/
<br /> SPRINKLER SYSTEM CONTRACTOR. EXTENDED GROUND DISCONNECT, RATED TO POWER SOURCE
<br /> 1. CALIFORNIA ENERGY CODE, SECTION 130.5(d) NOW REQUIRES THAT BOTH CONTROLLED AND RANGE 360° LENS VOLTAGE AND AMPERAGE RATING FOR FUSE
<br /> UNCONTROLLED 120V OUTLETS FOR PLUG LOADS BE PROVIDED IN THE FOLLOWING LOCATIONS: B. PROVIDE CONDUIT ONLY FROM SPRINKLER RISER TO TELEPHONE SERVICE TERMINAL BOARD FOR OS3 = NCM 9 LOW VOLRAGE CEILING MOUNT SENSOR, SMALL MOTION/ METER OR AS NOTED
<br /> OFF SITE MONITORING CABLES. STANDARD
<br /> A. EACH PRIVATE OFFICE. RANGE, 360° LES CURRENT TRANSFORMER 60 FUSE, SIZE = 60 AMPS
<br /> B. EACH OPEN OFFICE AREA. C. PROVIDE 120V POWER TO THE SPRINKLER SYSTEM ALARM BELL FROM THE HOUSE PANEL. OS4 = NCM PDT 9 LOW VOLTAGE CEILING MOUNT SENSOR, PDT, SMALL MOTION
<br /> C. RECEPTION LOBBY. STANDARD RANGE 360° LENS. POTENTIAL TRANSFORMER AUTOMATIC TRANSFER SWITCH
<br /> D. CONFERENCE ROOM. D. PROVIDE CONDUIT ONLY TO P.I.V. VALVE. OS5 = NWV PDT 16 KIT LOW VOLTAGE CORNER MOUNT SENSOR, PDT, 16 AMP
<br /> E. KITCHENETTE AND BREAK ROOM IN OFFICE SPACES. KIT DRY TYPE TRANSFORMER
<br /> PP1 = EXT NPP1 POWER/RELAY PACK -I ENGINE DRIVEN GENERATOR RATING AS
<br /> F. COPY ROOM. PS1 = NPS 80 POWER SUPPLY, 80 mA MOTOR G 50/3 NOTED AGAINST THE UNIT.
<br /> 2. CIRCUITS SERVING CONTROLLED RECEPTACLES SHALL BE AUTOMATICALLY BE SHUT-OFF IN S01 = WSXXX WALL SENSOR SWITCH - -
<br /> ACCORDANCE WITH SECTION 130.1(c)1. SW1 = NPODM 2P DX XX LOW VOLTAGE PUSH-BUTTON WALLPOD, 2-POLE RELAY
<br /> OCCUPANT CONTROLLED DIMMING :CR1 CR#= CONTROL RELAY �_ DRAW OUT DEVICE
<br /> 3. PROVIDE A SPLITWIRED DUPLEX RECEPTACLE WITH ONE HALF CONTROLLED AND ONE HALF SW2 = NPODM DX XX LOW VOLTAGE PUSH-BUTTON WALLPOD, OCCUPANT TDR = TIME DELAY RELAY
<br /> UNCONTROLLED DUPLEX RECEPTACLE AS SHOWN ON THE PLANS. THIS RECEPTACLE SHALL BE SPLIT ABBREVIATIONS ABBREVIATIONS CONTROLLED DIMMING. M = MOTOR STARTER 152 ANSI RELAY
<br /> DUPLEX OUTLET AS MANUFACTURED BY SAME MANUFACTURER AS THE OCCUPANCY LIGHTING SENSOR SW3 = NPODM 4S DX XX LOW VOLTAGE PUSH-BUTTON WALLPOD, 4 SCENE CONTACTOR RELAY
<br /> SYSTEM WITH A 15-AMP RELAY-SWITCHED OUTLET AND A 15-AMP CONSTANT POWER OUTLET. CONTROL, OCCUPANT CONTROLLED DIMMING. ETM = ELAPSE TIME METER
<br /> SW4 = NPODM 4P DX XX LOW VOLTAGE PUSH-BUTTON WALLPOD, FOUR POLE, _
<br /> 262726.02. DEVICE PLATES: ABV ABOVE INC U11�FER CLOSET OCCUPANT CONTROLLED DIMMING -I CONTACT (OPEN)
<br /> AFF ABOVE FINISH FLOOR vm VABITRMIDWER SW5 = KEY NPOD KEY XX LOW VOLTAGE WALLPOD, DIGITAL KEYSWITCH. I
<br /> 1. ALL DEVICE PLATES FOR INDOOR USE SHALL BE NYLON. A/C AIR CONDITIONING LVID VOERPWG FING CONTACT (CLOSED)
<br /> ALT ALTERNATE IV VOTtHVOLTAGE -VFD- VARIABLE FREQ. DRIVE
<br /> 2. ALL DEVICE BOXES WHICH ARE INSTALLED IN FIRE RATED WALL ASSEMBLY AND IS PROVIDED WITH AL ALUMINUM LVO IfQDTtHWQTAGE LIGHTING
<br /> A FIRE-STOPPING PUTTY PAD SHALL HAVE A BRUSHED STAINLESS STEEL COVERPLATE IN ACCORDANCE I , WALL MOUNT OCCUPANCY SENSOR (LINE VOLTAGE)
<br /> WITH THE REQUIREMENTS OF THE PUTTY PAD. AFCI ARC FAULT CIRCUIT INTERUPTER CONTROL PANEL - MOTOR OVERLOAD HEATER
<br /> ARCH ARCHITECT(URAL) MDP MAIN DISTRIBUTION PANEL
<br /> 3. DEVICE COVERS FOR SURFACE MOUNTED BOXES SHALL BE 1/2" RAISED STEEL PLATES. AUTO AUTOMATIC MS MAIN ELECTRICAL SERVICER , INDICATOR LIGHT
<br /> BD BOARD MAX MAXIMUM (R) RED, (W)WHITE
<br /> 4. DEVICE COVERS FOR DEVICES LOCATED IN DAMP LOCATIONS SHALL COMPLY WITH CEC 406.9(A). BLDG BUILDING MECH MECHANICAL i.
<br /> ANTENNA
<br /> 5. DEVICE COVERS FOR DEVICES LOCATED IN WET LOCATIONS SHALL COMPLY WITH CEC 406.9(B). CLG CEILING
<br /> MIN MINIMUM I
<br /> CLR CLEAR(ENCE) MISC MISCELLANEOUS TITLE 24 LIGHTING CONTROLS H C S ENGINEERING, INC.
<br /> 262729. DISCONNECT SWITCHES: CONC CONCRETE MTD MOUNTED LIGHT SWITCH
<br /> (N) NEW FIRE ALARM CONSULTING ELECTRICAL ENGINEERS
<br /> CO CONDUIT ONLY 4512 FEATHER RIVER DRIVE,SUITE F
<br /> 1. UNITS SHALL BE HEAVY DUTY FUSED DISCONNECT SWITCHES, TWO OR THREE POLE TYPE, WHERE NIGHT LIGHT COMPONENTS OF DIMMING ROOM CONTROLLER 1A TSP#16 ADDRESSIBLE INPUT CIRCUIT
<br /> CU COPPER (N
<br /> STOCKTON,CA 95219 (209)478-8270
<br /> INDICATED ON THE DRAWINGS, OR AS REQUIRED BY CODE. SWITCHES AND FUSES SHALL BE AS REQUIRED
<br /> D DEEP DEPTH N NORTH US = LOW VOLTAGE OCCUPANCY SENSOR (CAT 5 OR AS REQUIRED) 1X 2#14 HARD WIRED NON-ADDRESSIBLE CIRCUITS
<br /> BY THE LOADS SERVING. DEEP(DEPTH) ADDRESS: richard@hcs-eng.com
<br /> DEPT DEPARTMENT NIC NOT IN CONTRACT - DRC = DIMMING ROOM CONTROLLER 1Y 2#12 VISUAL CIRCUIT
<br /> 2. DISCONNECTS FOR FRACTIONAL HORSE POWER MOTORS SHALL BE MOTOR-RATED TOGGLE TYPE DTL DETAIL NTS NOT TO SCALE XX PE = LOW VOLTAGE DIMMING PHOTOCELL (CAT 5 OR AS REQUIRED) 1Z 2#14/SHIELDED AUDIBLE CIRCUIT PROJ.2017.xxx DES.WW ENG.RCS
<br /> DISCONNECTS. NO/# NUMBER D = LOW VOLTAGE DIMMER (CAT 5 OR AS REQUIRED)
<br /> DIA DIAMETER R= PLUG LOAD CONTROLLER FIRE ALARM ABBREVIATIONS:
<br /> 3. DISCONNECTS FOR SINGLE PHASE MOTORS SHALL BE SINGLE PHASE AND NOT THREE PHASE. DIM DIMENSION OS OCCUPANCY SENSOR ADR=AUTOMATIC DEMAND RESPOSNE (FOR BUILDINGS OVER 10,000 SF) _ FIRE ALARM CONTROL PANEL(FACP) PROFESSIONAL STAMP
<br /> D DIMMING PC PHOTOCELL _ CD = CANDELLA
<br /> 4. LOCATE DISCONNECTS IN ACCORDANCE WITH CEC 430.102. ENSURE ALL CODE-REQUIRED DRC DIMMING ROOM CONTROLLER PVC POLYVINYL CHLORIDE :SD- SMOKE DETECTOR DSD = DUCT SMOKE DETECTOR
<br /> CLEARANCES. DN DOWN REF REFERENCE NOTES: - EOL= END OF LINE RESISTOR
<br /> DWG DRAWING HEAT DETECTOR NAC = NOTIFICATION POWER SUPPLY R�FESS/p
<br /> REFR REFRIDGERATOR 1. FOR SUBMITTAL INCLUDE FACTORY CONTROL DRAWINGS. FiD PIV= POST INDICATOR VALVE �F�ePRD C. S q<�
<br /> 263437. EMERGENCY LIGHTING CENTRAL INVERTER/POWER SUPPLY(INV): DF DRINKING FOUNTAIN REQ REQUIRED ,HD' A HEAT DETECTOR IN ATTIC (194DEGREE) TS = TAMPER SWITCH
<br /> EA EACH R RISER/RADIUS 2. CONDUCT A CONTROLS PRE-CONSTRUCTION MEETING WITH CONTROLS - WF = WATER FLOW SWITCH
<br /> 1. PROVIDE CENTRAL, BATTERY-BACKED EMERGENCY INVERTER/POWER SUPPLIES LABELED "INV" ON �, y
<br /> w No. E14303 A
<br /> PLANS, FOR EMERGENCY EGRESS LIGHTING AS SPECIFIED HERE IN AND SHOWN ON PLANS. EO EARLY OFF LIGHT(PC/TC) RM ROOM STARTUP TEAM. PROVIDE AGENDA AND ATTENDEES AS A SUBMITTAL. INCLUDE i;• STROBE WP = WEATHERPROOF Exp. 6-30-19
<br /> E EAST SHT SHEET DEVICE I.D. TAGS, PROGRAMMING, CABLE ROUTING, PROGRAM AND TIME
<br /> 2. UNITS SHALL BE AS MANUFACTURED BY ENVOY LIGHTING, TYPE SPS SERIES WITH A CAPACITY AS STC SIGNAL TERMINAL CABINET SCHEDULES AND DATE OF PROGRAMMING AND TESTING. -i COMBINATION SPEAKER/STROBE MARKINGS: �� �FCTR�GP `P
<br /> ELEC ELECTRIC(AL) a###= CIRCUIT "a" DEVICE### 9T
<br /> REQUIRED, RATED FOR 90 MINUTES PER CODE. INPUT AND OUTPUT VOLTAGES SHALL BE AS NOTED ON PNL ELECTRICAL PANEL SIM SIMILAR 3. CONTRACTOR TO HAVE SYSTEM FACTORY SUPPORT FOR START UP, I :J EXTERIOR HORN 15CD = 15 CANDELLA VISUAL DEVICE FBF cA��F�
<br /> PLANS. STC SOUND TRANSMISSION COEFF. PROGRAMMING AND COMMISSIONING. VERIFY OPERATIONAL HOURS WITH OWNER 1/2W = 1/2 WATT AUDIBLE DEVICE
<br /> ELEV ELEVATION
<br /> 3. BATTERY SHALL BE SEALED LEAD CALCIUM WITH A BATTERY PROTECTION CIRCUIT BREAKER. EMER EMERGENCY S SOUTH PRIOR TO COMMISSIONING. PULL STATION
<br /> ENCL ENCLOSURE SPEC SPECIFICATION REVISIONS
<br /> 4. UNITS SHALL BE SIZED PER LOAD SERVED. EQ EQUAL SQ SQUARE No. Description Date By
<br /> 5. INSTALL IN ACCORDANCE WITH MANUFACTURES REQUIREMENTS.
<br /> EXH EXHAUST SF SQUARE FOOT ELECTRICAL POWER
<br /> FINISHED CEILING
<br /> (E) EXISTING SS STAINLESS STEEL �, ALL LINE VOLTAGE WIRING IN CONDUIT, SEE GENERAL NOTES MOUNTING HEIGHTS
<br /> 6. UNITS SHALL BE SO CONNECTED THAT THE LIGHTS POWERED BY THE UNIT SHALL COME ON EXIST EXISTING STD STANDARD TICKS =#OF#12 WIRE, SHORT= HOT, LONG = NEUTRAL, DOT= GROUND, AUDIBLE FIRE ALARM APPLIANCE
<br /> AUTOMATICALLY UPON POWER FAILURE ON THESE LIGHTS, IRRESPECTIVE OF WHETHER THE LIGHTS ARE FA FIREALARM STL STEEL UNLESS NOTED OTHERWISE NOT LESS THEN 90"AFF OR AT
<br /> "ON" OR"OFF". THESE LIGHTS ARE ALSO REQUIRED TO BE USED AS CODE-REQUIRED EMERGENCY EGRESS TEL TELEPHONE LEAST 6" BELOW CEILING
<br /> LIGHTS. FLR FLOOR '�' 120V OUTLET, +18"TO BOTTOM OF BOX
<br /> FT FOOT/FEET TTB TELEPHONE TERMINAL BOARD S = SIGN VISUAL APPLIANCE TO BE
<br /> 7. TEST SYSTEM TO ENSURE IT WORKS AS INTENDED AND REQUIRED. GRC GALVANIZED RIGID CONDUIT TV TELEVISION F = FLOOR NOT LESS THAN 80"AFF MIN,
<br /> GND GROUND TC TIME CLOCK GFI = GROUND FAULT INTERUPTER AND NOT MORE THAN 96"AFF Project 2017.xxx
<br /> GRD GROUND TYP TYPICAL t* COUNTER OUTLET 12"TYPICAL TO BOTTOM bpawl n WW
<br /> GFI GROUND FAULT CIRCUIT US ULTRASONIC OCCUPANCY FIRE ALARM MANUAL
<br /> Ki?cke RCS
<br /> INTERUPTER SENSOR QUADRUPLEX OUTLET
<br /> PULL STATION SHALL NOT
<br /> HVAC HEATING/VENTILATING/AIR UNO UNLESS NOTED OTHERWISE t SYSTEMS FURNITURE REQUIRE "TIGHT GRASPING, d By:
<br /> CONDITION VERT VERTICAL HALF SWITCHED OUTLETS CONNECTIONS +15"TO PINCHING OR TWISTING OF
<br /> HT HEIGHT BOTTOM OF BOXES THE WRIST"
<br /> OUTLETS ON EMERGENCY SYSTEMS
<br /> CONVIENCE OUTLETS,
<br /> SD DUCT SMOKE DETECTOR PHONE & DATA OUTLETS, Q �� THERMOSTAT PERMIT SET
<br /> +15"TO BOTTOM OR WALL PHONE
<br /> JUCTION BOX OF BOX 8.17.18
<br /> 'k• • LIGHT SWITCHES
<br /> k MOTOR /DISCONNECT )]0 48"TO TOP
<br /> •.• - OF BOX
<br /> PANELBOARD FINISHED FLOOR
<br /> TRANSFORMER/SWITCHBOARD AS NOTED GENERAL NOTES