Laserfiche WebLink
Environmental Health Department <br />AMENDED <br />3/30/2023 <br />Aboveground Petroleum Storage Act Inspection Report <br />Date: <br />December 08, 2022 <br /> Facility Address: <br /> 809C SNEDEKER AVE, STOCKTON <br /> Facility Name: <br /> CANARY RENEWABLES CORP <br />SUMMARY OF VIOLATIONS <br />(CLASS I, CLASS II, or MINOR - Notice to Comply) <br />RemarksItem # <br /> 713 CFR 112.7(e), 112.8(c)(6) Failed to test or inspect each container for integrity based on industry standards. <br />OBSERVATION: Facility failed to test each aboveground container for integrity based on industry standards, as <br />discussed in the SPCC Plan on a regular schedule. Per SPCC Plan facility is using API653 and SP001 standards. <br />Per SPCC Plan follows standard API653: <br />- T-631 did not observe integrity test records on site <br />- T-632 did not observe integrity test records on site <br />- T-633 did not observe integrity test records on site <br />Per SPCC Plan follows standard SP001: <br />- T-615 did not observe integrity test records on site <br />- T-616 did not observe integrity test records on site <br />- T-617 did not observe integrity test records on site <br />- T-618 did not observe integrity test records on site <br />- T-100 did not observe integrity test records on site <br />Tank integrity testing records were not observed for the following tanks. Standards for testing for the following tanks <br />were not discussed in the SPCC plan and so is unclear what the correct standards to be followed for the below <br />tanks are: <br />- T-619 was last tested via API 653 on 10/23/2017 and, if following this standard, was next due by 10/23/2022 <br />- T-127 did not observe integrity testing records on site <br />- Diesel Tank in the tank farm located in front of T-612, no integrity testing records were observed on site <br />Additionally, section 2.5 in the SPCC Plan incorrectly cites code 40 CFR 112.7(d) for Aboveground Integrity <br />Inspections. The correct citation is 112.8(c)(6) and 112.7(e). <br />REGULATION GUIDANCE: REGULATION GUIDANCE: 112.8(c)(6) Test or inspect each aboveground container <br />for integrity on a regular schedule and whenever you make material repairs. You must determine, in accordance <br />with industry standards, the appropriate qualifications for personnel performing tests and inspections, the frequency <br />and type of testing and inspections, which take into account container size, configuration, and design (such as <br />containers that are: shop-built, field-erected, skid-mounted, elevated, equipped with a liner, double-walled, or <br />partially buried). Examples of these integrity tests include, but are not limited to: visual inspection, hydrostatic <br />testing, radiographic testing, ultrasonic testing, acoustic emissions testing, or other systems of non-destructive <br />testing. You must keep comparison records and you must also inspect the container's supports and foundations. In <br />addition, you must frequently inspect the outside of the container for signs of deterioration, discharges, or <br />accumulation of oil inside diked areas. Records of inspections and tests kept under usual and customary business <br />practices satisfy the recordkeeping requirements of this paragraph. <br />112.7(e) Inspections, tests, and records. Conduct inspections and tests required by this part in accordance with <br />written procedures that you or the certifying engineer develop for the facility. You must keep these written <br />procedures and a record of the inspections and tests, signed by the appropriate supervisor or inspector, with the <br />SPCC Plan for a period of three years. Records of inspections and tests kept under usual and customary business <br />practices will suffice for purposes of this paragraph. <br />CORRECTIVE ACTION: Immediately conduct the necessary integrity testing or inspections on T-631, T-632, T-633, <br />T-615, T-616, T-617, T-618, T-100, T-127, T-619, and the diesel tank in the tank farm area based on industry <br />standards, on a regular schedule, after making material repairs, using non-destructive testing, inspecting each <br />container’s supports, foundations, and outside for signs of deterioration, discharges, or accumulation of oil inside <br />FA0018706 PR0528437 SC001 12/08/2022 <br />EHD 28-01 Rev. 12/06/2021 Aboveground Petroleum Storage Act OIRPage 16 of 18 <br />1868 E. Hazelton Avenue | Stockton, California 95205 | T 209 468-3420 | F 209 464-0138 | www.sjgov.org/EHD