Laserfiche WebLink
p . If the storage tank is used to supply fire suppression sprinklers and /or fire <br /> hydrants , a fire pump must be installed . Storage tanks must be able to supply <br /> to required GPM and the pump must be able to provide the required GPM and <br /> pressure . <br /> q . Crash posts must be installed around the take to protect the tank but not <br /> block access to the fire department connection . <br /> r . Requirements for water storage tanks in accordance with NFPA 22 ( Standard <br /> for water tanks for private fire protection ) . <br /> 4 . Underground pipingfor the fire sprinkler system shall be approved by the Fire <br /> Department prior to permit issuance . <br /> 5 . All above ground gas meter, regulators , and piping exposed to vehicular damage <br /> shall be protected in an approved manner. <br /> 6 . Fire suppression systems : All buildings must be protected by an approved <br /> monitored automatic sprinkler system in accordance with NFPA 13 , CFC , CBC . <br /> a . Fire Alarm /Sprinkler monitoring shall be point ID . <br /> 7 . Fire Suppression Approval : Plans and specifications for fire suppression systems <br /> shall be submitted for review and approved prior to construction . If work differs <br /> from approved plans , a set of " as built " shall be submitted to the Fire <br /> Department prior to final inspection . <br /> 8 . Plans proposed to be listed as deferred submittals shall be clearly labeled on <br /> the cover building permit plan submittal cover sheet . <br /> 9 . Inspection : Fire protection systems ( fire hydrants , water mains , etc . ) shall be <br /> installed , tested and approved by the AHJ prior to the issuance of any building <br /> permits . The Fire Department shall witness all system and acceptance tests . <br /> Please provide a minimum of 24 - hour notice prior to any system or acceptance <br /> tests ( �Nw \N . frenchcampfirP_. co_ f ) <br /> 10 . A Fire Department approved " key lock box " shall be properly installed nearthe <br /> main entrance and may be required at other locations deemed appropriate by <br /> the Fire Department . A 3200 series Knox Box ( s ) can be ordered online at <br /> ww \iv`frenchcami) �i' ii_e . corn . Contact fire prevention with any questions . <br /> 11 . All above ground gas meters , regulators , and piping exposed to vehicular <br /> damage shall be protected in an approved manner. <br /> 12 . Trash enclosures /dumpsters shall not be allowed within 5 feet of any <br /> combustible walls , openings , or combustible roof eaves , unless protected by an <br /> automatic fire sprinklers . <br /> 13 . Operations that require operational permits ( high piled storage , hot work , <br /> compressed gas , battery storage and all others listed in CFC 105 ) shall be <br /> identified on the plan submittal . <br />