Laserfiche WebLink
Environmental Health Department <br />Underground Storage Tank Program Inspection Report <br />Date: <br />May 15, 2023 <br /> Facility Address: <br /> 1196 W LOUISE AVE, MANTECA <br /> Facility Name: <br /> QUIK STOP MARKET #551121 <br />SUMMARY OF VIOLATIONS <br />(CLASS I, CLASS II, or MINOR - Notice to Comply) <br />RemarksItem # <br /> 308 CCR 2632(c), 2634(d), 2636(f) Failure of the leak detection equipment to have an audible and visual alarm. <br />OBSERVATION: The float and chain in the UDC 1/2 failed to stop the flow of product at the dispenser when tested. <br />REGULATION GUIDANCE: All monitoring equipment shall be maintained to activate an audible and visual alarm or <br />stop the flow of product at the dispenser when it detects a leak. <br />CORRECTIVE ACTION: The service technician adjusted the float and chain and verified functionality. <br />This was corrected on site. <br />This is a Class II violation. <br /> 317 CCR 2636(f)(2) Failure of the line leak detector to detect a 3.0 gph leak at 10 psi and restrict or shut off flow. <br />OBSERVATION: The 87 VMI line leak detector failed to detect a leak when tested. <br />REGULATION GUIDANCE: All line leak detectors shall be capable of detecting a 3-gallon per hour leak at 10 psi. <br />CORRECTIVE ACTION: The service technician adjusted the leak detector, retested it, and it passed. <br />This was corrected on site. <br />This is a Class II violation. <br />Overall Inspection Comments: <br />Complete and submit a copy of the Return to Compliance Certification form to the EHD with a statement <br />documenting the corrective actions that have been or will be taken for each violation, and any supporting <br />paperwork, by 06/14/2023. <br />To minimize person to person contact EHD is choosing to write the name of person receiving the report instead <br />of having them sign. Starting September 1, 2018, all in-office CERS help will be provided at EHD hourly rate <br />($156). To schedule an appointment, please call (209) 468-3420. <br />AFTER THE COMPLIANCE DATE, EHD WILL BILL FOR ALL TIME AND ACTIVITIES ASSOCIATED WITH BRINGING <br />THIS FACILITY BACK INTO COMPLIANCE. <br />THIS FACILITY IS SUBJECT TO REINSPECTION AT ANY TIME AT EHD'S CURRENT HOURLY RATE. <br /> Received by: Inspector Phone: <br /> PAUL NSO, EH Specialist <br /> Inspector:May 15, 2023 Date: <br />Printed Name and Title: <br />E mail report to: Marty Hilfinger, Environmental Contact. <br />(209) 616-3049 <br />FA0000848 PR0231430 SC001 05/15/2023 <br />EHD 23-01 Rev. 12/06/2021 Underground Storage Tank Program OIRPage 5 of 5 <br />1868 E. Hazelton Avenue | Stockton, California 95205 | T 209 468-3420 | F 209 464-0138 | www.sjgov.org/EHD