VENT STACK DETAILS WITH VEEDER-ROOT CARBON CANISTER VAPOR POLISHER TYPICAL DOUBLE WALL SCALE: 1"= 1'-0" CLIENT: <br /> PRESSURE VACUUM VENT PRESSURE VACUUM VENT by�J� <br /> CFC 2016§2306.7.9.2.2 LOCATION 23 CAPS(SEE NOTE BELOW) 23 CAPS(SEE NOTE BELOW) <br /> VAPOR-PROCESSING EQUIPMENT SHALL BE LOCATED AT OR e <br /> ABOVE GRADE.SOURCES OF IGNITION SHALL BE LOCATED NOT NOTE: <br /> LESS THAN 50 FEET(15240-)FROM FUEL-TRANSFER FFS/HEALY CLEAN AIR SEPARATOR KR <br /> AREAS AND NOT LESS THAN 18 INCHES(457.2mm)ABOVE INCLUDES CLEAN AIR SEPARATOR TANK, <br /> TANK FILL OPENINGS AND TOPS OF DISPENSER ISLANDS. BALL VALVES,FLOAT CHECK,REDUCER <br /> GALVANIZED AIR BREATHER BUSHINGS AND ALL ACCESSORIES SHOWN <br /> VAPOR-PROCESSING UNITS SHALL BE LOCATED NOT LESS 2"GALVANIED�186 UNION&NIPPLES AIR IN OUT 12" MINIMUM <br /> P N 98 EXCEPT 1'PIPING. <br /> UNION&NIPPLES ( 94 ) ABOVE GRADE <br /> THAN 10 FEET(304Emm)FROM THE NEAREST BUILDING OR I I B 2"GALVANIZED ELBOW <br /> PROPERTY LINE OF A PROPERTY WHICH CAN BE BUILT UPON. NOTE: <br /> EXCEPTION:WHERE THE REQUIRED DISTANCES TO FFS/E CLEAN AIR SEPARATOR TANK <br /> BLO " <br /> BUILDINGS,PROPERTY LINES OR FUEL-TRANSFER AREAS TO BE LOCATED IN CONFORMANCE WITH <br /> CANNOT BE OBTAINED,MEANS SHALL BE PROVIDED TO MANUFACTURERS INSTALLATION MANUAL, <br /> PROTECT EQUIPMENT AGAINST FIRE EXPOSURE.ACCEPTABLE 2"GALVANIZED I I CARE EXECUTIVE ORDER VR-202 OR <br /> MEANS INCLUDE: 8 - " <br /> 1.APPROVED PROTECTIVE ENCLOSURES,WHICH EXTEND AT TEE VR-204 AND ALL APPLICABLE STATE AND <br /> LOCAL CODES.PER CFC 2016 SECTIONS <br /> LEASE 16 INCHES(457.2mm)ABOVE THE EQUIPMENT, I I I I - 2306.7.9.2.2&2306.7.9.2.3 <br /> CONSTRUCTED OF FIRE-RESISTANT OR I I 4TH VENT <br /> NON-COMBUSTIBLE MATERIALS OR (IF REQUIRED) NOTE: <br /> 2.FIRE PROTECTION USING AN APPROVED WATER-SPRAY ARCO SYSTEM I I CONSTRUCTADDITIONAION <br /> SCREEN WALL OR H <br /> CONSTRUCTION MAY BE REQUIRED BY <br /> VAPOR-PROCESSING EQUIPMENT SHALL BE LOCATED A LOCAL ORDINANCES,MINIMUM MOUNTING <br /> MINIMUM OF 20 FEET(6096mm)FROM DISPENSING DEVICES. 9Y9 REWIREMENTS ARE SHOWN IN THIS EP WEST COAST PRODUCTS.LLC <br /> PROCESSING EQUIPMENT SHALL BE PROTECTED AGAINST DETAIL PER CFC 2016 SECTION <br /> 2306.7.9.2.3 NO. DATE DESCRIPTION <br /> PHYSICAL DAMAGE BY GUARDRAILS,CURBS,PROTECTIVE I I Q 09/10/2021 REV.PER DD CORM. <br /> ENCLOSURES OR FENCING.WHEN APPROVED PROTECTIVE <br /> ENCLOSURES ARE USED,APPROVED MEANS SHALL BE 3 HEALY CLEAN AIR SEPARATOR 02/03/2022 REV.PER Ero CORRIL <br /> PROVIDED TO VENTILATE THE VOLUME WITHIN THE ENCLOSURE o 67 (36'0%93"LG.) <br /> TO PREVENT POCKETING OF FLAMMABLE VAPORS. Im P/N 9961H <br /> IF A DOWNSLOPE EXISTS TOWARD THE LOCATION OF THE I i <br /> VAPOR-PROCESSING UNIT FROM AFUEL-TRANSFER AREA, o.w FLEX CONNECTOR DETAIL "NO SMOKING/FLAMABLE VAPORS"SIGN s <br /> THE CHIEF IS AUTHORIZED TO REQUIRE ADDITIONAL <br /> SEPARATION BY DISTANCE AND HEIGHT. wo BACKGROUND <br /> WITH 3" H LETTERING ON CONTRASTING Q <br /> 1 I I -�' 1"GALVANIZED VENT PIPING MIN. <br /> CFC 2016§2306.7.9.2.3 INSTALLATION 2"SCH.40 GALV.STEEL E > SLOPE TO VENTS 1/8"PER FOOT, <br /> VAPOR-PROCESSING UNITS SHALL BE SECURELY MOUNTED ON 400 GALLON BLADDER, <br /> VENT RISER PAINT TO 1'0Ff.MAX LENGTH.MAX.DISTANCE <br /> CONCRETE,MASONRY OR STRUCTURAL STEEL SUPPORTS ON MATCH SITE CONDITIONS P/N 9943(REF.) <br /> c>� WITHOUT PIPE SUPPORT NOT TO <br /> CONCRETE OR OTHER NON-COMBUSTIBLE FOUNDATIONS. EXCEED 10',DISTANCES OVER 10' o <br /> REQUIRE PRIOR APPROVAL OF BP <br /> NOTE:BP DOES NOTE Up <br /> MEW E PERMIT THE VAPOR-PROCESSING I I DESIGN MANAGER. <br /> FASTEN VENT RISER TO FRAME W1 In <br /> OR 2"STAINLESS STEEL U-BOLT,3/8 0 0 17 1"FIRE RATED, 1"BLADDER SIPHON 91 STRAIGHT PIPE n <br /> TIRES.SEE A159LM'O`UNTl`NG"'DI LS FOR <br /> HOLE W/LOCK WASHER HEX NUT. I E STAINLESS STEEL BOLLARDS,LOCATION <br /> TEST EACH RISER FOR ELECTRICAL �I �I zo FLEXIBLE CONNECTOR VAPOR INLET ASSN. CONDITIONS <br /> 11 I i BASED ON SITE <br /> CONTINUITY TO VENT RACK(TYP.) ^ UNISTRUT P/N 9956(REF.) <br /> II 2"TEE WITH 1/4"TEST PI°I SUPPORT D <br /> PORT FITTING AND 1/4" F r �;` ________ BRACKET PLUG <br /> AIR Al I <br /> 'II PLUG(TYP.) I,_II ------ <br /> 2"SCH.40 GALVANIZED STEEL FLOAT CHECK VALVE <br /> RISER.PAINT PER SPECS(TYPJ 8 BOLTED GROUND CONNECTION TO P/N 9466G OVERFILL I AIR SEAL: <br /> VENT RACK.JUMPER R4 AWG BARE PROTECTION <br /> STRANDED CU FROM,STAND ALONE <br /> 2"TEE WITH 1/4"TEST PORT MOUNTING RACK 2"X1"REDUCER VAPOR 3 V POR <br /> FffTING AND 1/4"PLUG(TYP.) III I BUSHING <br /> 8 EXPLOSION <br /> BO%SIMOUNTEDF I I LOCKED VALVE <br /> O <br /> TO POST 8 2'GALVANIZED ELBOW OR <br /> 19 SEAL OFF 2-IN-1 SENSOR 1 I IN NORMAL N0. 36475 <br /> BOX 8 OULNTED TO POST J-BOX OPERATION * NO 36475 <br /> 2-IN-1 SENSOR 1 III IIS 19 SEAL OFF BALL VALVE P/N 996123 IV11- <br /> LOCK P/N 996124 <br /> I USE KEY P/N 996125 SYPHONADAPTER 704 PLACARD CF CPLIF� <br /> 1 MINIMUM 2,500 PSI /4 AWG BARE STRANDED <br /> HYDROSTATIC SENSOR INSIDE CU GROUND WIRE TO I O PLUG P/N 9939(REF.) <br /> PRI ARY ANOMETER RESERVOIR i� CONCRETE FOUNDATION TANK FIELD GROUNDING °I <br /> Jz( <br /> ATTACHED TO SUMP PER MANUFACTURER'S SYSTEM 11 11 (-SEE BELOW <br /> II 11 SPECIFICATIONS. B"THICK CONCRETE SIPHON TUB <br /> �11 r <br /> RADEBALL GRADE SLAB GRADE d z <br /> Q. a <br /> 6"WIDE DETECTABLE ���\ LOCKED VALVE <br /> 7ANIE• bAB. - <br /> UNDERGROUND MARKING TAPE n �� $ U z <br /> \\\\\ m <br /> 'MAINTAIN CLEARANCE a•�. < <br /> BURIED 6"-12'BELOW FINISHED %�• \ OR <br /> GRADE:EMPIRE 31-143 // --- -- -- - ------- -- -- - --- -- - - -- <br /> IN DIRECT UNE TO � Z <br /> /����r\ ALLOW FOR CONNECYION < ' •", ��'" r^^ <br /> �� G OF TESTING APPARATUS. o m <br /> �/. IN NORMAL a CS u, m <br /> 2"BELLxALE ADAPTER P. 4 /\�� INSTALL((1)1' SEE EXHIBIT 4 OF OPERATION N - .9 m Z v d <br /> TO MONft11G" LATEST VR-202 E.O. /\��� ,` '..~••. _ < <br /> 3'FRP BONDED FIRING PANEL IN BALL VALVE P/N 996123 _ w1.,- <br /> < <br /> p <br /> W TEST PORT 2 I 7 2"FLEX I BUILDING LOCK P/N 996124 ��\��\ a 25 W i z F <br /> 2"INSIDE 3' 4 a n' C�)ECTOR ° _ I :+. USE KEY P/N 996125 /4 4 \ \ • `NE OLTEDGROEU�ND, `[!.�•[:�;�:;.1%^ h a Z O z o <br /> n SUBGRADE w o O <br /> DOUBLE WALL FRP - I--1 HYDROSTATIC SENSOR INSIDE \����/ CON CTION TO HEALY . r 0 <br /> VENT UNE.SEE --- - PRIMARY MANOMETER RESERVOIR 1 /7 ,\��\. TANK BASE. \��\��\� i Z-0 0 0 <br /> NOTE BELOW. 2'SCHED 40 ATTACHED TO SUMP 14 AWG BARE 8"2,500 PSI "�//���/ a w w z O <br /> BLACK IRON STRANDE CU GROUND CONCRETE TANK z rn z ro <br /> 4"x3'CONCENTRIC 2 ELBOW BY GC SLAB.SUB DESIGN <br /> REDUCER P. „ ° 2"INSIDE 3"DOUBLE WALL FRP 4 4 WIRE.ROUTE TO TANK w v <br /> e FIELD GROUNDING PER CALCULATIONS <br /> LIQUID VENT LINE.SLOPE TO TANK AT °� <br /> DOUBLE WALL VENT CONTAINMENT 0 SENSOR 1/8"PER FOOT MINIMUM.SEE 17 2'FLEX CONNECTOR SYSTEM 1B"0,2,500 PSI Q C7 O <br /> SUMP FILLED WITH PROPYLENE NON-DISCRIMINATING NOTE BELOW.(TYP.) (TYP.) gi STRAIGHT BOLLARD(TYP.) z a <br /> GLYCOL INTERSTITIAL FLUID,SUPPUED ° SEE SITE PUN FOR CONCRETE g <br /> LIQUID SENSOR FOUNDATION(TYP.) <br /> BY BRAVO ONLY 0 DOUBLE WALL VENT CONTAINMENT LAYOUT AND QUANTITY <br /> NON-DISCRIMINATING 11 SUMP FILLED WITH PROPYLENE REQUIRED <br /> 1'-0"MIN. OVER COMPACTED SOIDL % ` FRONT ELEVATION SUPP�ED BY BRAVO OINTERSTITIAL LNLID, DEVELOPMENT INFORMATION: <br /> Q <br /> 2 COMPACTED SOIL(TYPICAL)Q <br /> SIDE ELEVATION 6"THICK O <br /> CONCRETE SLAB .a � � � � �:m g. . <br /> a <br /> LINT"QUID SENSOR A q a <br /> NON-DISCRIMINATING O VEPIPNIG AOUNTIN a RAMC, 1 2-I2-IN-1 SENSOR a .. SITE ADDRESS: <br /> INOTES- <br /> 0 DER TO PROVIDE MECHANICAL FLEXIBILITY WITHIN THE RIGID PIPING SYSTEM, PROVIDE HYDROSTATIC SENSOR INSIDE d e 1949 WEST MARCH LANE <br /> AT LEAST 4 FEET OF STRAIGHT PIPE RUN BEFORE A CHANGE IN DIRECTION OF 30 DEGREES PRIMARY MANOMETER RESERVOIR 1 $° 8 BTOCKTON CAO W <br /> OR MORE. [NFPA 30A(2012)§5.3.3(2)], [IFC (2015)§5703.6.9.11,[3 RCNY§3403.6.9.11, ATTACHED TO SUMP 4 <br /> [CFC (2016)§5703.6.9.11. <br /> n <br /> THE VENT CONFIGURATION SHOWN IS IN ACCORDANCE WITH CP-201 THE NUMBER OF VENT <br /> CAPS AT ANY GDF SHALL NOT PERMIT AN ADDITIVE LEAK RATE OF MORE THAN .17 CHF AT DESIGNED BY: <br /> 2"OF WATER COLUMN. MAX ALLOWED WITHOUT MANIFOLDING IS(3). 2"BELLxMALE ADAPTER 4 CHECKED BY: <br /> THE VENT DISCHARGE SHALL BE LOCATED SO THAT VAPORS ARE RELEASED AT A SAFE POINT DRANK BY: ER <br /> OUTSIDE OF BUILDINGS AND NOT LESS THAN 12 FT H(3.6 M ABOVE THE ADJACENT GROUND 3"FRP BONDED FITTING 2 A�.. DATE: PROJECT NO. <br /> WAL S.VENL. ORS SHALL BE T OUTLETS SHALL BE LOCATED GED UPWARD <br /> T AT VAPORS��LY OT BEWAY FROM TRAPP DACENT BY EAVES W/TEST PORT(1YP.) °'.s, .I I ° 09)10)2021 <br /> 7161OR OTHER OBSTRUCTIONS AND SHALL BE AT LEAST 5 FT(1. M) FROM BUILDING OPENINGS. 4"x3"CONCENTRIC 2 I' I'I�°4 I 'I.I 4 a.' DRAWING TITLE: <br /> SHALL5 <br /> VENTS SHALL BE INSTALLED IN ACCORDANCE WITH [NFPA 30 (2012)§5.7.21, [IFC (2015) REDUCER(TYP.) I I I o <br /> §5704.2.7.3.31,[3 RCNY§2206.7.9.2.2.1],[CFC(2016)§5704.2.7.3.3]. DESIGN INTENT:VENT STACKINSTALLAIWN <br /> VENT RISERS SHOULD STAND NO LESS THAN 3' FROM OUTSIDE EDGE OF CURB A INSIDE 3'DOUBLE 4 I I I I I DETAILS E HORIZONTAL <br /> WALL FRP VENT LINES III I i i � FFS�HEALY CLEAN AIR SEPARATOR <br /> THE ACTUAL NUMBER OF VENT RISERS IS DETERMINED BY THE NUMBER OF UNDERGROUND (VACUUM MONITORED) I I i i O (CALIFORNIA ONLY) <br /> STORAGE TANKS. THE DIESEL VENT RISER (IF INSTALLED) IS ALWAYS SEPARATE. I I I I I <br /> IIi IIi IIi IIi 11 DOUBLE WALL VENT CONTAINMENT SHEET NO, <br /> SU <br /> UGLYCOL MP FILLED WITH PROPYLENE NOTE: THIS DRAWING APPLICABLE WITH: <br /> INTERSTITIAL FLUID, PLAN VIEW <br /> SUPPLIED BY BRAVO ONLY -HEALY VAC ASSIST STAGE II VAPOR RECOVERY PER L/16- DIA. HOLES TYP. 4 GW�W"W5 <br /> PLAN VIEW 'I W J W J W J W CARB E.O. VR-202 by <br /> >I� >I� >l� >l� -VST BALANCE STAGE II VAPOR RECOVERY PER <br /> CARB E.O. VR-204 <br />