Laserfiche WebLink
OBSERVATION:The owner/operator failed to provide or document initial training for each employee involved in operating a <br /> process. Per Jimmy Stout, RMS was hired to replace Schrader Mechanical a few months ago. Standard operating procedure <br /> training has not yet been provided to RMS. <br /> CORRECTIVE ACTION(S):Submit documentation to our department demonstrating that each employee involved in operating <br /> a process and each employee before being involved in operating a process has been/will be initially trained and records <br /> were/will be prepared documenting the training. <br /> Priority Responsible Person Due Date Completed Date <br /> 2 Jimmy Stout 12/01/2023 12/01/2023 <br /> Related Events <br /> No related events. <br /> Resolution <br /> SOP training has been completed and submitted to the CUPA. <br /> Linked Records <br /> Recommendation#3 <br /> CalARP 630: <br /> OBSERVATION:The owner/operator failed to correct process equipment deficiencies in a timely manner. <br /> 1)There is one recommendation from the 05/16/2019 mechanical integrity audit that has not been addressed.The due date <br /> for the recommendation was 06/30/2020. <br /> 2)The weather cap for one of the pressure release valve located on the north system roof was damaged. <br /> CORRECTIVE ACTION(S):Submit documentation to our department demonstrating that process equipment deficiencies have <br /> been/will be corrected before further use or in a safe and timely manner when necessary means are taken to assure safe <br /> operation. <br /> Priority Responsible Person Due Date Completed Date <br /> 2 Jimmy Stout 12/01/2023 12/01/2023 <br /> Related Events <br /> No related events. <br /> Resolution <br /> 1)The MI recommendation has been resolved. <br /> 2)The pop-eye on the relief valve is damaged but this does not affect the relief valve capacity.Three way valve has been <br /> changed to other valve so that if a release occurred the light would activate. <br /> Linked Records <br /> Recommendation#4 <br /> CalARP 642: <br /> OBSERVATION:The owner/operator failed to promptly respond and document each of the findings in the compliance audit. <br /> There are 2 recommendations from the 2020 audit that have not been addressed.There are 3 recommendations from the <br /> 2023 audit that have not been addressed by their due date of 08/31/2023. <br /> CORRECTIVE ACTION(S):Submit a copy of the compliance audit report of findings that includes responses and dates for <br /> completing the listed deficiencies to our department.Submit documentation to our department demonstrating that the <br /> compliance audit report findings have been/will be resolved and the actual completion dates were/are documented. <br /> Priority Responsible Person Due Date Completed Date <br /> 2 Jimmy Stout 12/01/2023 <br /> Related Events <br /> Name Date Event <br /> Jimmy Stout 12/01/2023 Audit recommendation status updates have been submitted to the CUPA.Quarterly updates will be <br /> provided until all items are resolved <br /> Resolution <br /> Linked Records <br /> Recommendation#5 <br /> HMBP 6: <br /> OBSERVATION:The site map is incomplete.The following items need to be added onto the map: <br /> 1)one 55 gallon drum of Domolish ALS and one 55 gallon drum of Alpet Surface Sanitizer was observed inside a container <br /> located outside north of the storage building. <br /> 2)one 55 gallon drum of Domolish ALS and one 55 gallon drum of Infact 750 was observed in the New North expansion <br /> building. <br />